manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Fike
  6. •
  7. Control Unit
  8. •
  9. Fike FIK-IM-10 User manual

Fike FIK-IM-10 User manual

BEFORE INSTALLING
If the modules will be installed in an existing operational system, inform the
operator and local authority that the system will be temporarily out of service.
Disconnect the power to the control panel before installing the modules. This
system contains static sensitive components. Always ground yourself with a
proper wrist strap before handling any circuits so that static charges are re-
moved from the body. The housing cabinet should be metallic and suitably
grounded.
NOTICE: This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
The FIK-IM-10 Ten Input Monitor Module is intended for use in an intelligent
alarm system. Each monitor module is intended to interface between a control
panel and normally open contact devices, such as pull stations. A common
SLC input is used for all modules, and the initiating device loops share a
common supervisory supply and ground. Otherwise, each monitor operates
independently from the others. Each module has its own unique address.
A pair of rotary code switches is used to set the address of the first mod-
ule from 01 to 150 (01 to 90 on panels that support up to 99 addresses).
The remaining modules are automatically assigned to the next nine higher
addresses. Provisions are included for disabling a maximum of two unused
modules to release the addresses to be used elsewhere. Each module also has
panel controlled green LED indicators. The panel can cause the LEDs to blink,
latch on, or latch off.
C0202-00
SHIPPED ON BOARD:
(1) Shunt in Class A/B position
(Shipped in Class B position, remove shunt for Class A)
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a compatible
Fike system control panel.
COMPONENTS
The following is a description of the FIK-IM-10 mounting framework:
• One or two FIK-IM-10 modules can be installed in an FIK-BB-2 cabinet.
The FIK-BB-2 cabinet has a built-in chassis that will accommodate one or two
FIK-IM-10 modules.
The front FIK-IM-10 module positions of each chassis are offset below the rear
0
1
2
3
4
56789
0
78
6
5
4
3
21
910
11
12
13
14
15
BASE ADDRESS
ADDRESS
DISABLE
NONE
ONE
TWO
THREE
0
1
2
3
4
56789
0
78
6
5
4
3
21
9
BASE ADDRESS
ADDRESS
DISABLE
NONE
ONE
TWO
THREE
10
11
12
13
14
15
C0234-05
FIGURE 1: FIK-BB-2 CABINET
FIK-IM-10 module positions so that all of the status indicators are visible. For
cabinet dimensions refer to the FIK-BB-2 instruction manual.
INCLUDED:
(6) 1 x 4 Terminal
Blocks
(2) 1¼" (32mm)
Stand offs
(3) Shunts (10) 47k Ohm End
of Line Resistors
(2) Nuts
(4) Machine Screws
SPECIFICATIONS
Normal Operating Voltage: 15-32 VDC
Stand-By Current: 3.75 mA @ 24V
Alarm Current: 55 mA (assumes all ten LEDs solid on)
Temperature Range: 32°F to 120°F (0°C to 49°C)
Humidity: 10 to 93% Non-condensing
Dimensions: 6.8" H x 5.8" W x 1.25" D
Accessories: FIK-BB-2 Cabinet and Chassis
Wire Gauge: 12-18 AWG
Maximum IDC
Wiring Resistance: 1500 Ohms
Maximum IDC Voltage: 10.2 VDC
Maximum IDC Current: 240 µA (each circuit)
I56-6893-000
INSTALLATION AND MAINTENANCE INSTRUCTIONS
R
704 SW 10th Street
Blue Springs, MO 64015
Phone: 816.229.3405; Fax: 816.228.9277
www.fike.com
FIK-IM-10
Ten Input Monitor Module
http://www.fike.com/06-912
Fo
r system/product documentation including
installation, operation, and maintenance,
scan QR code or enter URL provided.
1 I56-6893-000
1/15/2021
INSTALLATION STEPS
1. Cabinet Mounting
In a clean, dry area, mount the backbox using the four holes pro-
vided in the back surface of the cabinet. (See Figure 2.)
2. Module Installation
There are two methods for installing a module in the rear position
of a chassis. Method one is for installation of a rear module only,
when no module will be installed in front of it. Refer to Figure 3 for
instructions. Method two is for installation of a rear module when
another module will be installed in the chassis position in front of
it. Refer to Figures 4a and 4b for method two. All necessary screws
and standoffs are supplied with the modules.
C0237-00
FIGURE 3. INSTALLATION OF REAR MODULE ONLY, METHOD ONE
2
3
1
Step 1: Insert the bottom edge of the FIK-IM-10 module down into a rear slot
of the chassis.
Step 2: Carefully swing the upper edge of the board towards the back of the
chassis until it touches the short standoff attached to the chassis.
Step 3: Align the long standoff with the short stand off and tighten.
FIGURE 4A. INSTALLATION OF FIK-IM-10 MODULE IN A REAR CHASSIS
POSITION, METHOD TWO
1
2
3
1
FIGURE 4B. INSTALLATION OF FIK-IM-10 MODULE IN FRONT CHASSIS
POSITION
Step 1: Insert the bottom edge of the FIK-IM-10 module down into a front slot
of the chassis.
Step 2: Carefully swing the upper edge of the board towards the back of the
chassis until it touches the 11⁄4" (31.75mm) standoffs installed on the
rear module.
Step 3: Align two 4-40 screws with the two standoffs and tighten.
Step 4: Address and wire the modules according to the instructions in this manual.
WIRING
NOTE: All wiring must conform to applicable local codes, ordinances, and
regulations.
1. Install module wiring in accordance with the job drawings and appropri-
ate wiring diagrams.
2. All wiring to the FIK-IM-10 is done via terminal blocks. In order to prop-
erly make electrical connections strip approximately 1⁄4" of insulation
from the end of wire, sliding the bare end of the wire under the clamping
plate screw.
3. Set the address on the modules per the job drawing. Use the rotary code
switches to set the address of the first module between 01 and 90 (or 01
and 150 for panels that support 159 addresses).
In Class B operation, the remaining modules are automati
cally assigned to the next nine higher addresses. For example, if the base ad-
dress switch is set to 28, the next nine modules will be addressed to 29, 30, 31,
32, 33, 34, 35, 36, and 37.
The module is shipped in Class B position, remove shunt for Class A.
When operating in Class A, alternate modules are paired together (+0/+1,
+2/+3, +4/+5, +6/+7, +8/+9), resulting in a total of five modules. For
example, if the base address switch is set to 28, then 30, 32, 34 and 36 will be
automatically assigned to the modules while 29, 31, 33, 35 and 37 are avail-
able to be used for other modules on the SLC. For Class A and B operation,
DO NOT set the lowest address above 90 (or 150 for panels that support 159
addresses), as the other modules will be assigned to nonexistent addresses.
NOTE: The FIK-IM-10 must have power cycled for shunt changes to take ef-
fect.
4. A shunt is provided to disable a maximum of two unused modules in
Class B operation and one unused module in Class A operation. Modules
are disabled from the highest address and work downward. If two mod-
ules are disabled, the lowest eight addresses will be functional, while the
highest two will be disabled. For example, in Class B operation, if the
shunt for Address Disable is placed on “two” and the base switch is set
to 28, the modules will be assigned to 28, 29, 30, 31, 32, 33, 34 and 35
while disabling the highest two positions.
5. A communications loss feature is available on some panels. Upon a com-
munication loss, due to a microprocessor failure at the control panel, the
FIK-IM-10 will send a signal to the control panel to activate the notifica-
tion device circuits upon initiating of an alarm on the FIK-IM-10. A single
shunt is used to enable (shunt on) or disable (shunt off) this feature for
all modules on the board.
NOTE: All references to power limited represent “Power Limited (Class 2)”.
NOTE: Place unused shunts on single pin to store on board for future use.
WIRING NOTES
• Power-limited circuits must employ type FPL, FPLR, or FPLP cable as
required by Article 760 of the NEC.
PROGRAMMING
The modules are programmed as devices in each system according to the pro-
gramming instructions in the appropriate FACP manual.
C0225-00
C0226-00
BACKBOX
MOUNTING
HOLES
C0235-00
FIGURE 2: TYPICAL MOUNTING HOLE LOCATIONS
Step 1: Insert the bottom of the FIK-IM-10 module down into a rear slot on
the chassis.
Step 2: Carefully swing the upper edge of the board back towards the back of
the chassis until it touches the two standoffs.
Step 3: Align two 4-40 screws with the two standoffs and tighten.
Step 4: Address and wire the modules according to the instructions in this
manual.
The steps in Figures 4a and 4b describe and illustrate module in-
stallation when the rear chassis position and the position in front of
it will be filled. Front position installation is possible only if the rear
position is filled with a module.
2 I56-6893-000
1/15/2021
0
1
2
3
456789
BASE ADDRESS
TO NEXT
DEVICE
–
STATUS
INDICATORS
—
+
—
+
—
+
—
+
—
+
—
+
IDC
ADDRESS
+0
+1
+2
+3
+4
+5
+6
+7
+8
+9
IDC
ADDRESS
IDC
ADDRESS
IDC
ADDRESS
IDC
ADDRESS
—
+
—
+
SLC
—
+
—
+
+
–
+
FROM PANEL OR
PREVIOUS DEVICE
47K
EOL
RESISTOR
ELR-47K
CONNECT MODULES TO
LISTED COMPATIBLE
FIKE CONTROL PANELS ONLY
SIGNAL LINE CIRCUIT (SLC) 32 VDC MAX.
SEE PANEL INSTRUCTION MANUAL
FOR WIRE REQUIREMENTS.
CLASS B IDC (TYPICAL)
—
+
—
+
A/B SLCT
COM LOSS
DISABLE 1
DISABLE 2
0
1
2
3
45678910
11
12
13
14
15
POWER LIMITED
AND SUPERVISED
NOTE: Any number of UL listed contact closure devices may be used.
DO NOT mix fire alarm initiating and supervisory devices on the same initiat-
ing device circuit. Install contact closure devices per manufacturer’s installa-
tion instructions.
C0810-04
FIGURE 5. TYPICAL INITIATING DEVICE CIRCUIT CONFIGURATION – CLASS B
BASE ADDRESS
TO NEXT
DEVICE
–
STATUS
INDICATORS
—
+
—
+
—
+
—
+
—
+
—
+
IDC
ADDRESS
+0
+1
+2
+3
+4
+5
+6
+7
+8
+9
IDC
ADDRESS
IDC
ADDRESS
IDC
ADDRESS
IDC
ADDRESS
—
+
—
+
SLC
—
+
—
+
+
–
+
FROM PANEL OR
PREVIOUS DEVICE
CONNECT MODULES TO
LISTED COMPATIBLE
FIKE CONTROL PANELS ONLY
SIGNAL LINE CIRCUIT (SLC) 32 VDC MAX.
SEE PANEL INSTRUCTION MANUAL
FOR WIRE REQUIREMENTS.
CLASS A IDC (TYPICAL)
—
+
—
+
A/B SLCT
COM LOSS
DISABLE 1
DISABLE 2
IDC 2
IDC 3
IDC 4
IDC 5
0
1
2
3
456789
0
1
2
3
45678910
11
12
13
14
15
POWER LIMITED
AND SUPERVISED
REMOVE SHUNT FOR CLASS A.
FIGURE 6. TYPICAL FAULT TOLERANT INITIATING DEVICE CIRCUIT CONFIGURATION – CLASS A
NOTE: Any number of UL listed contact closure devices may be used. DO NOT
mix fire alarm initiating and supervisory devices on the same initiating device cir-
cuit. Install contact closure devices per manufacturer’s installation instructions.
C0811-04
DEVICE AND SYSTEM SECURITY
Before installing this product ensure that the tamper
seal on the packaging is present and unbroken and
the product has not been tampered with since leaving
the factory. Do not install this product if there are
any indications of tampering. If there are any signs
of tampering the product should be returned to the
point of purchase.
It is the responsibility of the system owner to ensure
that all system components, i.e. devices, panels, wir-
ing etc., are adequately protected to avoid tampering
of the system that could result in information disclo-
sure, spoofing, and integrity violation.
FCC STATEMENT
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may cause undesired operation.
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed
to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not
installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not
occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off
and on, the user is encouraged to try to correct the interference by one or more of the following measures:
– Reorient or relocate the receiving antenna.
– Increase the separation between the equipment and receiver.
– Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
– Consult the dealer or an experienced radio/TV technician for help.
Fike®is a registered trademark of Fike Corporation.
3 I56-6893-000
©2021. 1/15/2021

This manual suits for next models

1

Other Fike Control Unit manuals

Fike FAV User manual

Fike

Fike FAV User manual

Fike FIK-CR-6 User manual

Fike

Fike FIK-CR-6 User manual

Fike FIK-M500M User manual

Fike

Fike FIK-M500M User manual

Fike 55-046 User manual

Fike

Fike 55-046 User manual

Fike TWINFLEX SRM 100-0010 User manual

Fike

Fike TWINFLEX SRM 100-0010 User manual

Fike EIV User manual

Fike

Fike EIV User manual

Fike FIK-FML Technical manual

Fike

Fike FIK-FML Technical manual

Fike P Service manual

Fike

Fike P Service manual

Fike Lantronix XPort 10-2627 Operating instructions

Fike

Fike Lantronix XPort 10-2627 Operating instructions

Fike 55-043 User manual

Fike

Fike 55-043 User manual

Fike MICROMIST 10-2340 User manual

Fike

Fike MICROMIST 10-2340 User manual

Fike FIK-RVM User manual

Fike

Fike FIK-RVM User manual

Fike TWINFLEX IRM 100-0011 User manual

Fike

Fike TWINFLEX IRM 100-0011 User manual

Popular Control Unit manuals by other brands

Gema MagicControl 4.0 operating instructions

Gema

Gema MagicControl 4.0 operating instructions

Keyautomation CT-724 Series Instructions and warnings for installation and use

Keyautomation

Keyautomation CT-724 Series Instructions and warnings for installation and use

Alfalaval Unique RV-P instruction manual

Alfalaval

Alfalaval Unique RV-P instruction manual

KEBCO COMBIVERT  H6 Instructions for use

KEBCO

KEBCO COMBIVERT H6 Instructions for use

FRO­NIUS LCG11 installation instructions

FRO­NIUS

FRO­NIUS LCG11 installation instructions

ZepSolar Zep System I installation manual

ZepSolar

ZepSolar Zep System I installation manual

Delta R1-EC5614 user guide

Delta

Delta R1-EC5614 user guide

HYDACELECTRONIC CSI-B-2 user manual

HYDACELECTRONIC

HYDACELECTRONIC CSI-B-2 user manual

Murrelektronik MVK-MPNIO Series manual

Murrelektronik

Murrelektronik MVK-MPNIO Series manual

Multitech MultiConnect xDot Series Developer's guide

Multitech

Multitech MultiConnect xDot Series Developer's guide

USR IOT USR-C322 user manual

USR IOT

USR IOT USR-C322 user manual

Vemco VEMoDRIVE VSI 2.0 HD instruction manual

Vemco

Vemco VEMoDRIVE VSI 2.0 HD instruction manual

Avtech DCCS BOX quick start guide

Avtech

Avtech DCCS BOX quick start guide

GOAL ZERO Yeti Link user manual

GOAL ZERO

GOAL ZERO Yeti Link user manual

protech SORADIO installation instructions

protech

protech SORADIO installation instructions

Ublox NEO-M8P-2 Hardware Integration Manual

Ublox

Ublox NEO-M8P-2 Hardware Integration Manual

Delta MultiChoice T27976-CZLHP installation instructions

Delta

Delta MultiChoice T27976-CZLHP installation instructions

Signature Control Systems SoloRain 8014 DuraLife Series quick start guide

Signature Control Systems

Signature Control Systems SoloRain 8014 DuraLife Series quick start guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.