7 Commissioning
Note
Commissioning only by qualified personnel.
When incompressible media (e.g. neutral water) are used, switching the valve
causes pressure surges in the tubing system. Prior to commissioning, check
the compatibility of the devices in the system to avoid damaging them. If
necessary, adjust your application parameters.
Observe the information on the rating plate.
Start up the solenoid valve only when it is completely assembled and installed.
Check the connection points for leaks.
Prior to commissioning, check for compliance with the operating conditions and
the permissible limit values (èTechnical data).
8 Operation
Observe the operating conditions.
Always observe the permissible limit values.
Warning
Danger of burning on hot surfaces.
The surface temperature of the solenoid valve can exceed 75 °C.
Do not touch the solenoid valve.
9 Dismantling
Warning
Danger of injury due to hot media under pressure.
The media in the piping system and the solenoid valve can be hot and can be
under pressure.
Allow the solenoid valve and pipelines to cool and depressurise them.
Note
The solenoid valve may be dismantled only by qualified personnel.
1. Depressurise the pipeline.
2. Switch off the voltage.
3. Completely drain the pipeline and valve.
– Allow the solenoid valve and pipeline to cool off.
– Make sure that no one is in front of the outlet opening.
– Catch escaping media in a suitable container.
4. Remove the solenoid valve from the pipeline (unplug the electrical plug con
nector, detach the mounting bracket and unscrew the fittings).
10 Changing the solenoid coil
The solenoid coil can be changed for repairs.
Warning
Danger of injury from hot surfaces.
The surface temperature of the solenoid valve can exceed 75 °C.
Let the solenoid valve cool off.
Dismantling:
1. Switch off the voltage.
2. Disconnect the electrical plug connector.
3. Undo the knurled nut and remove the solenoid coil from the armature guiding
tube.
Mounting:
1. Push the O-ring and solenoid coil over the armature guiding tube.
2. Secure the solenoid coil with the O-ring and knurled nut.
– Torque for tightening the knurled nut: finger-tight (about 1...1.5 Nm).
11 Service and maintenance
Check the solenoid valve for leakage at least every 6 months.
Check the functioning of the solenoid valve at least every 6 months.
Regularly clean the outside of the valve with a soft cloth. The permissible
cleaning agent is soap suds.
12 Eliminating malfunctions
Malfunction Possible cause Remedy
Solenoid valve
not closing
Solenoid valve is defective. Replace the solenoid valve.
Flow direction is incorrect Install the solenoid valve in accord
ance with the flow arrow
Nominal voltage is still applied Check electrical connection.
Differential pressure too low Make sure the specified minimum
differential pressure is supplied.
Solenoid valve
does not open
Solenoid coil or solenoid valve is
defective.
Replace the solenoid coil.
Replace the solenoid valve.
Nominal voltage interrupted or
not sufficient
Check voltage.
Fig. 4
13 Technical data
General VZWP-L-M22C-...
Valve function 2/2-way, closed, monostable
Design Pilotactuated piston poppet valve
Actuation type Electrical
Mounting position Coil preferably on top
Sealing principle Soft
Medium Compressed air in accordance with ISO85731:2010 [7:4:4]
Inert gases, Neutral fluids1)
Direction of flow Non-reversible
Viscosity [mm2/s] š22
Grade of filtration [μm] 40
Temperature of medium [°C] –10...+80
Ambient temperature [°C] –10...+35
Protection class IP65 as per DIN EN 60529
Degree of contamination 3 as per IEC 60664-1
Attachment type In-line installation
Materials information, housing Cast brass
Materials information for seals NBR, FPM
1) Other media on request
Fig. 5
Electrical data VZWP-...1-... VZWP-...2A-... VZWP-...3A-...
Nominal voltage
– DC voltage
– AC voltage (50...60 Hz)
[V DC]
[V AC]
24 (±10%)
–
–
110 (±10%)
–
230 (±10%)
Rated output [W]
[VA]
6.8 –
7.5
–
10.5
Surge resistance [kV] – 2.5 4.0
Duty cycle 100% (continuous duty)
Electrical connection Device plug per DIN EN 175301-803, format A
Connecting cable
– Cable cross-section [mm2] 0.75…1.5
– Cable diameter [mm] 5…9
– Cable entry thread M20x1.5
Fig. 6
Port size [˝] ¼y½¾1
Pipe thread per DIN ISO 228
Pipe thread per ANSI B 1.20.1
G¼
N¼
GÅ
NÅ
G½
N½
G¾
N¾
G1
N1
Differential pressure [bar] 0.5
Nominal size DN [mm] 13 25
Standard nominal flow rate [l/min] 1600 2100 2650 8750 12250
Flow factor Kv[m3/h] 1.5 2.0 2.5 8.2 11.5
Operating pressure [bar] 0,5…40
Overload pressure [bar] 45
Switching times for gaseous media1)
–On [ms] 100 130
– Off [ms] 250 300
Tightening torques
– Pipe connection [Nm] 35 60 105 200 350
– Mounting of solenoid coil [Nm] 2
Weight [g] 600 575 550 1500 1400
1) Depending on the viscosity, longer switching times with fluid media
Fig. 7