FireClass FC503 User manual

Page 2of 38
To program the FC503 and FC506 fire control panels, use
the software FireClass FC500 (FC501_FC503_FC506)
Console release 01.00.01 or control panel FW version
1.01 or higher.
Johnson Controls assumes no responsibility for damage to
products arising from improper application or misuse.
Installation of this control panel must be carried out strictly
in accordance with the instructions in the Installation
manual, and in compliance with the local laws and by laws
in force.
The FC503 and FC506 fire control panels comply with the
essential requirements of standards EN54-2, EN54-4, and
EN 54-21.
Recycling information
The manufacturer advises that customers dispose of any
used equipment, such as panels, detectors, sirens, and
other devices, in an environmentally friendly manner.
Potential methods include reuse of parts or whole products
and recycling of products, components, and materials.
Waste Electrical and Electronic Equipment (WEEE)
Directive
In the European Union, this label indicates that you must
dispose of this product separately from household waste at
an appropriate facility to enable recovery and recycling.
Note: The FC503 and FC506 fire control panels support
several addressable devices, such as detectors, modules,
manual call points, and so on. The present manual
includes the instructions for the programming of the fire
control panels. For further information about these devices
and their accessories, refer to: www.fireclass.net.
The manufacturer reserves the right to change the
technical specifications of these products without prior
notice.
Maintenance
To ensure that the system continues to operate normally, it
must be maintained with regular testing by the user and
periodic maintenance by the installer in accordance with
local laws.
Note: For the maintenance of other devices such as
detectors, modules, and so on, follow the dedicated
instructions for the devices.
The following operations must be carried out regularly:
1. Using a damp cloth (do not use solvents of any
kind), remove dust from the control panel cabinet.
2. Using the LAMP TEST key, check that the LEDs
and buzzer are functioning properly.
3. Ensure the batteries are sufficiently charged and
functioning properly. If not, replace them
immediately.
4. Ensure all cables and connections are intact.
5. Ensure there are no unrelated objects inside the
control panel case.
6. Ensure the control panel is capable of processing
a fire alarm, and if a siren (sounder) is present in
the system, it is activated in consequence of this
alarm. If there is a facility for transmission of fire
alarm signals to a central station, it should also be
ensured that the signal is correctly received.
7. Verify the functionality of the circuit for the
detection of earth fault. The procedure is as
follows:
oConnect one of the SH terminals of the loop to
the panel earth.
oVerify that the fault is reported correctly by the
fire panel.
oRemove the connection previously made.
Note: Points 1and 2may be carried out by users. Points
3, 4, 5, 6, and 7must be carried out by qualified persons.

Page 3of 38
Table of Contents
Introduction ........................................................................4
FC503 and FC506 fire control panels ............................ 4
Accessory items.............................................................4
User access level...............................................................4
Access level 1 (L1).........................................................4
Access level 2 (L2).........................................................5
User interface.....................................................................5
Panel command keys.....................................................6
VIEW LOG Parameters....................................................19
1 Key - View loop data .................................................19
2 Key - View devices....................................................20
3 Key - View SW zones................................................22
4 Key - View output......................................................22
5 Key – View network devices .....................................23
6 Key – View communicators.......................................23
7 Key – View system options .......................................23
8 Key – View the log.....................................................24
9 Key – View the FW version.......................................25
0 Key – View panel information....................................25
View lists.......................................................................25
MODIFY...........................................................................27
1 Key – INIT MSG (Modify panel label)........................27
2 Key - User password.................................................27
3 Key - Day and night modes.......................................28
4 Key - Time and date..................................................28
5 Key - Clear LOG........................................................28
6 Key – Walk Test........................................................29
DISABLE..........................................................................30
2 Key – Devices (Disable)............................................31
Select the loop..............................................................31
Select the device..........................................................31
Disable device on the loop...........................................32
3 Key – SW Zone.........................................................32
Disable SW zone..........................................................33
4 Key - Outputs ............................................................33
Select the output ..........................................................33
Disable Output..............................................................33
5 Key - Network............................................................34
6 Key - COMMUNIC. Device........................................34
7 Key - Password disable.............................................36
Select the password.....................................................36
Disable password.........................................................36
8 Key - Fire relay...........................................................36
9 Key - Sounder (Disable).............................................37
FC500 repeater signaling..............................................37
CPR information............................................................38

Page 4of 38
Introduction
FC503 and FC506 fire control panels
The FC503 and FC506 fire control panels follow Johnson
Controls’ highest standards of quality and performance.
FC503
FC503 is an analogue addressable fire control panel with
one main loop (three sub-loops), that can support up to 250
addressable devices and 128 zones. BAQ140T24 switching
power supply powers FC503 at 5.5A @ 27.6 ±1 %V.
Suitable batteries include two *12 V/ 17Ah or two *12 V/
38Ah. The user interface has LEDs and icons.
The FC503 fire control panel is a modular system. The
configuration of the FC503 system depends on the size
and requirements of the application; therefore, some of the
described devices and functions may not be present on
your system.
The FC503 system consists of the following components:
• One FC503 control panel
• Max. 8 FC500 repeaters
• Max. 4 FC500MFI multifunction modules
• Max. 7 client panels Max. 250 devices in three different
sub-loops or 250 max in a single sub-loop only
FC506
FC506 is an analogue addressable fire control panel with two
main loops (six sub-loops). The panel can support up to 500
addressable devices and a maximum of 250 devices in a
single main loop, and 256 zones. BAQ140T24 switching
power supply powers FC506 at 5.5A @ 27.6 ±1 %V. Suitable
batteries include 2 * 12 V/ 17Ah or 2 * 12 V/ 38Ah. The user
interface has LEDs and icons.
The FC506 fire control panel is a modular system. The
configuration of the FC506 system depends on the size
and requirements of the application; therefore, some of the
described devices and functions may not be present on
your system.
The FC506 system consists of the following components:
• One FC506 control panel
• Max. 8 FC500 repeaters
• Max. 4 FC500MFI multifunction modules
• Max. 7 client panels
• Max. 500 devices in six different sub-loops or two main
loops (250 devices max per main loop)
The FC503 and FC506 fire control panels allow you to
manage the functions of the fire control system up to
2000m (loop) with shielded 2 core cable 2x2.5mm².
Accessory items
FC500 repeater
Repeaters are peripherals that provide system status
information, emit audible signals, and allow users to
control the functions of the FC503 and FC506 system (up
to 1000m, with twisted pair shielded cable).
FC500MFI
The FC500MFI is a programmable multifunctional module
for connection to a real time event printer. The terminal
blocks also make it possible to connect a standard
interface to remotely control and manage a set of inputs
and outputs to control the panel.
FC500IP
This module connects the control panel to a Local Area
Network (LAN).
FC503 and FC506 client
The FC503/FC506 master control panel can support up to
seven FC503 or FC506 client control panels. These
control panels can be used to expand the FC503/FC506
system in modular way.
FireClass FC500 (FC501_FC503_FC506) Console
This is a software application operating on Microsoft
Windows 7 and higher. The console offers a quick and
easy way to program the control panel and also provides
event log and printout functions.
FireClass console multi account engine (FCMAE)
The FCMAE allows you to monitor multiple FireClass
systems across the world from a single workstation. It
manages up to 32 FC500 series panels (FC501, FC503,
FC506, FC510, and FC520) connected to Ethernet
through the FC500IP3 module. It shows the real time
status and alerts the operator when an event occurs in one
of the monitored systems.
User access level
Access level 1 (L1)
At access level 1 (L1) or viewing level, all users can view
the control panel status. See Table 1 for information about
the control panel operations and statuses available at L1.
Table 1: Access level 1 (L1)
Operations
Status available
ANALYZE
1. Loop
2. Device
3. SW Zones
4. Outputs
5. Network
6. Communication
7. Options
8. Log
9. FW Vers
0. Panel
VIEWLOG
Log
VIEWLISTS
1. DIS.ZONES
2. DIS. DEVICES
3. DIS. PARTS
4. WALK TEST
5. FAULTS
6. WARNINGS
7. DEV. in TEST

Page 5of 38
Access level 2 (L2)
Access level 2 (L2) is for operating the system, and
requires an access code. At this level, all the
operations at L1 are also available. See Table 2 for
information about the L2 operations and statuses:
Table 2: Access level 2 (L2)
Operations
Status available
MODIFY
1. INIT. MSG
2. USER PASSWORD
3. DAY/NIGHT
4. TIME and DATE
5. Clear log
6. WALK TEST
7. Options
8. Log
9. FW Vers
0. Panel
DISABLE
1. Dis. LISTS
3. SW. ZONES
4. OUTPUTS
5. NETWORK
6. COMMUNIC
8. FIRE relay
User interface
Figure 1: User interface view of FC503 and FC506
Description of keys
To manage the panel from the User Interface (UI), use the
following controls:
• Alphanumeric keypad. Numbers 0 – 9 and letters A-Z.
• Cursors keys: Up, Down, Right, and Left
• ESC key
• ENTER key
• HELP button to open the Help screens on the Display.
See Figure 2.
• Command keys
Note: Use the cursors keys Up, Down, Right, and Left,
and the command keys LAMP TEST and SILENCE
BUZZER, and the alphanumeric keypad to enter the
characters A,B,C,D,E, and F. Use these characters to
enter hexadecimal numbers for planned future use.
The function of the cursors keys, the ESC key, the ENTER
key, and the command keys, is different in every LCD
display and is fully described in this manual. Also, the
amount of time spent pressing the keys has a different
function in the different LCD displays. In future, it will be
possible to use the HELP key to access more information.
SILENCE / RESOUND / SOUNDERS
The control panel can operate in day mode or night mode.
If the system is silenced during day mode, the silence
status remains until the system is unsilenced (unless new
alarms or faults occur). If the system is silenced during
night mode, the silence status remains until the night mode
silence time expires. On power up, the system starts in
day mode by default. During this operating mode, silenced
alarms/faults will not be unsilenced automatically.
RESET
Reset will stop alarm, delay to alarm, warning, and fault
conditions. Access to this command is limited to
authorized personnel using an installer or user access
code. The system reprocesses any alarm, delay to alarm,
warning or fault signal that is not cleared by a reset.
Command keys cannot be used when a reset is running.
The repeaters can be reset by using the user access code.

Page 6of 38
Panel command keys
Table 3: Description of the control panel and repeater keys
Key
Description
SILENCE/ RESOUND
SOUNDERS
Restores the silenceable outputs and the loop devices to standby status
Note: The silence status remains until you press the SILENCE key again
in day mode; or until the night mode silence time expires in night mode;
or until the system detects a new alarm condition.
RESET
Resets the fire detectors and restores all outputs to standby status
INVESTIGATION
DELAY
Refreshes the delay to alarm time
Note: If you press this during a delay to alarm condition, the remaining
delay to alarm time is increased with the programmed investigation delay.
EVAC
Activates the evacuation
If you press this key, the system generates an alarm.
SILENCE BUZZER
Silences the local buzzer on the control panel
Note: The buzzer operates every time a new event is activated.
LAMP TEST
Tests the buzzer and the LEDs
Note: If you press this key when the control panel is functioning as
intended, all LEDs will be on and the buzzer emits a continuous beep.
HELP
Explains the information on the LCD display in the different screens
Notes:
•This is an embedded help feature present on the panel LCD
display.
•The Help key is disabled on repeater panels.
System fault
acknowledgement
switch
In the case of a system fault LED latch, press the system fault
acknowledgement switch to identify the fault and then press RESET.
Notes:
•To access the system fault acknowledgement switch, open the
front cover of the panel. The switch is located on the bottom left
of the PCB.
•The system fault acknowledgment switch is not available on
repeater panels.
•The system fault LED latches if one of the following conditions
occur:
oThe system resets itself (a watchdog reset) when an
internal logical fault occurs.
oThe system is powered ON after a complete panel shut
down.
Note: You can operate only the LAMP TEST, SILENCE
BUZZER, and EVAC command keys without the access
code (access level L1). Entering the access level L2 and
L3 codes allows you to operate all the other command
keys.
HELP key
Note: This section describes the functionality of the HELP
key.
To explain the information on the LCD display in the
different screens, an embedded help feature is present on
the panel LCD.
See Table 4 for key HELP functions for the MAIN screen.
Table 4: HELP key functions
Key
Help functions
1
Selects program or analyze mode
2
Selects disable or view list mode
3
Showsthepanel eventlogorselect the
modifymode
4
Selects between the function groups
related to the keys 1, 2, and 3
ENTER
No function
ESC
Exits from the Help to MAIN screen, or
EVENT DRIVEN screen, if any
Press the keyfor more than 3 seconds to
force the panel to level 1.
Up and
Down
Scrolls through the Help list.

Page 7of 38
Right
and
Left
No function
Figure 2: Example of the LCD display after pressing
the Help key
1
Access level
2
Control panel status
3
If blinking, the control panel is working
normally
4
Control panel name (you can modify this)
5
Working activity
Signaling
The system status is indicated by the following signals:
• Control panel LEDs
• Backlit display (40 characters on 4 lines)
• Buzzer
Status LEDS
Table 6 describes how the control panel LEDs operate,
and the actions that can be taken during the various states
signaled on the LEDs.
Notes:
• During standby status and if the control panel is in day
mode, only the green mains LED and the day mode LED
should be ON.
• The general fault LED and the LED specific to the fault
are ON or blinking during a fault condition.
• To manage the brightness and contrast of the LCD
display, see the MAIN screen.
Buzzer (audible signals)
The control panel buzzer provides an audible indication of
the panel status. See Table 5 for a description of each
buzzer signal.
Note: When an Alarm status is silenced and a new fault
signal is detected, the control panel restarts the buzzer
with the previous alarm signal.
To test the buzzer press LAMP TEST. The buzzer cannot
work when the SILENCE BUZZER is pressed.
Table 5: Buzzer signaling
Condition
Frequency
(Hz)
Sound
Pause
System Fault
(main processor
fail)
1300
2.5 s
2.8 s
General Fault
(Programming
data
corrupted)
660
1 s
1 s
Alarm
3300
0.2 s
0.2 s
Fault
660
1 s
1 s
Delay to Alarm
880
0.5 s
0.5 s
Warning
440
2 s
2 s
Reset
No sound
Test
No sound
Description of the FC500 repeater LEDs
Table 6 describes the function of the LEDs. Table 4
describes the functions of the keys on the repeater UI.
Display
The information on the LCD display is organized as
screens, as follows:
• START-UP screen
• FRONT screen
• MAIN screen
• DIAGNOSTIC screens
• MENU screen
• EVENTS DRIVEN screen
Start-up screen
When the panel starts, the START-UP screen displays by
default, unless you program the UI to display other
information. The information included is shown in Figure 3.

Page 8of 38
Figure 3: Event driven screens and MAIN screen basic
interactions
*
Only if the panel is in
normal activity.
**
No timeout for ANALYZE
menu, VIEW LOG screen,
VIEW LIST screen. The
timeout can be extended
to four minutes in the
programming menu when
you enter the parameters.
Table 6: Description of the status LEDs
LED
Description
FIRE (Red)
ON indicates the alarm status. In the event of an alarm, the control panel activates
the unbypassed alarm outputs.
GENERAL
FAULT
(Amber)
ON indicates the presence of a fault. The following LEDs or the screen on the
display indicates the type of fault. Off indicates no fault.
SYSTEM
FAULT
(Amber)
ON ** indicates a blocked control panel and *** indicates the control panel restart.
IMPORTANT: Maintenance required.
Blinking *** indicates that the data panel programming is corrupted.
Notes:
•When the control panel is switched on for the first time, this LED blinks
until you perform a reset.
•** indicates the buzzer system fault pattern;
•*** indicates the buzzer fault pattern.
•The system fault LED latches if one of the following conditions occur:
oThe system resets itself (a watchdog reset) when an internal
logical fault occurs.
oThe system is powered ON after a complete panel shut down.
FIRE
SIGNAL
FAULT
(Amber)
ON indicates that the communicator is disabled.
Blinking indicates that the communicator is faulty.
POWER
SUPPLY
FAULT
(Amber)
ON indicates a mains failure (230 V).
Blinking indicates a Switching Power supply fault.
During this condition, the control panel is powered by the batteries.
EARTH
FAULT
(Amber)
ON indicates a voltage leakage to Earth.
IMPORTANT: Check wiring insulation.
BATTERY
ON indicates that the batteries are empty or faulty. If this condition persists, the
batteries will be unable to function as intended in the event of a blackout.

Page 9of 38
TROUBLE
(Amber)
IMPORTANT: New batteries are required.
POWER ON
(Green)
ON indicates that the panel is supplied with power. OFF indicates a mains failure
whereby both mains and battery power is lost (the battery disconnect threshold is
19.2 V). Power must be restored before the batteries reach the disconnect
threshold.
MORE INFO
(Amber)
ON indicates that there is hidden information with lower priority.
View List shows the hidden information.
OFF indicates no hidden information is available.
SOUNDERS
SILENCED
(Amber)
ON indicates that the silenceable outputs and loop device have been forced into
standby by means of the SILENCE/ RESOUND SOUNDERS key. In day mode,
the silence status remains until the SILENCE/RESOUND SOUNDER key is
pressed again. In night mode, the silence status remains until the night mode
silence time expires or until the system detects a new alarm or a new trouble
condition.
FIRE
SIGNAL ON
(Red)
ON indicates that the transmission was successful.
Blinking indicates that the transmission is in progress. On the control panel
screen, the connection type, such as PSTN, GSM, or LAN network, is displayed.
SOUNDERS
FAULTS/DIS
(Amber)
ON indicates that the output is disabled or outputs configured to "act as SC1" are
disabled.
Blinking indicates that the SC1 is in fault or outputs configured to "act as SC1"
are in fault.
OFF indicates that all the main sounder outputs (EN54-1, TYPE "C" outputs)
function properly.
DISABLED
(Amber)
ON indicates the disabled status of any bypassable entity.
TEST
(Amber)
ON indicates the test conditions on at least one zone.
DAY MODE
(Amber)
ON indicates that the control panel is operating in day mode.
OFF indicates that the control panel is operating in night mode.
1-8
SOFTWARE
ZONES
(Red)
ON indicates that the corresponding software zones are in Alarm status *.
Note: * indicates that the zone outside the 1- 8 range does not have a related
LED, its alarm status is displayed only by the LCD.
Blinking indicates that the corresponding Software zones are in Delay to Alarm
status.
CONTROLS
ON
(Amber)
ON indicates that the control panel is at least at level 2 so the
SILENCE/RESOUND SOUNDERS, RESET and INVESTIGATION DELAY keys
are enabled.
Note: * the zone outside the 1 to 8 range does not have a related LED, its alarm status is displayed
only by the LCD, ** buzzer SYSTEM FAULT pattern, *** buzzer FAULT pattern.

Page 10 of 38
Figure 4: Display MAIN screen access to the
management of the panel
1
Access level
2
Control panel status
3
Control Panel name
(you can modify this)
4
Panel activity/Current
phase
System option
• Selected language
• Panel identification number
• The panel type (FC503/ FC506)
• The installed battery capacity (17Ah/38Ah)
The selected language is vital for the user interface
(UI) to select between the two available languages in
the panel. The panel identification number is vital for
the panel to name and manage the files over the
USB memory stick.
Note: When the START-UP screen is initialising, the
panel is not fully operative and the control keys are
not working.
Front screen
The Front screen is generally displayed when the
panel is in standby status. It can contain an
advertisement message set by the installer. The
screen content and the enablement to display it are
set by the FC500 FC503/FC506 software (SW). For
information about FRONT screen key functions, see
Table 7.
Table 7: Alphanumeric, Cursor, ESC and ENTER
key functions on the FRONT screen
Key
Function
Alphanumeric
keypad
No functions
Cursor keys
No function
ESC
Exits from the FRONT
screen, and moves the UI
to the MAIN or EVENT
DRIVEN screen, activated
directly by events:
warning, delay to alarm,
alarm, fault, or walk test
ENTER
No function
Note: You can permanently remove or replace the
FRONT screen using the configuration options in
FireClass FC500 (FC501_FC503_FC506)Console.
MAIN screen
The MAIN screen is the first screen displayed by the
panel after it powers up (see Figure 4). This screen
can be replaced by the EVENT DRIVEN screen. After
30 seconds of inactivity, the FRONT screen appears.
Fields
See Figure 4.
The Access level field shows the current access level
of the panel. 10 seconds before leaving the present
access level this field starts to blink.
The Control panel status field displays the current
panel status, the possible values include ACTIVE (its
normal state).
A continuous and steady blinking indicates that the
control panel is functioning properly.
The Panel activity/current phase field displays the
current activity of the panel. For more information,
see Table 8.
Table 8: Panel activity field values
Value in panel activity
field
Description
RESETTING
Panel is resetting
LOC. PROG
Panel is being
programmed by a local
access
REM.ACCESS
Panel is remotely
accessed (PC via serial
port, USB or IP)
SYS. INIT
Panel is initializing
SYS. VER
Panel is verifying itself
CLEAR LOG
Panel is clearing the
event log
WAITS
Panel is waiting to be
configured
————
No activity
SCANNING LOOPS
Panel is in its normal
activity
Note: The date and time field blinks until the date
and time is set.

Page 11 of 38
Table 9: Alphanumeric keypad, Cursor, ESC and
ENTER key functions on the MAIN screen
Key
Function
1
Moves to Program or Analyze mode
2
Moves to Disable or View lists mode
3
Shows the View log or moves to Modify
mode
4
Selects between the function groups
related to the keys 1, 2, and 3
Up
Increases the brightness of LCD display
Down
Decreases the brightness of LCD display
Right
Increases the contrast of LCD display
Left
Decreases the contrast of LCD display
ESC
Exits from the MAIN screen
Changes the UI to the FRONT or EVENT
DRIVEN screen.
Pressing the key for more than 3 seconds
forces the panel to access level 1.
ENTER
No function
Diagnostic screens
The following functions are available through the
diagnostic screens:
• A display of some electrical parameters inside
the panel (Panel meter screen)
• A display of some functional parameters related
to the loops (Loop screen)
• Execution of the panel keyboard test (Keyboard
Test screen).
To access the diagnostic screens from the MAIN
screen, press and hold the 4 key.
Figure 5: Interaction between the diagnostic
screens
1
Press ESC key to go to
MAIN screen
2
Press ESC key for 32
milliseconds to go to
MAIN screen
Table 10: Field information on the diagnostic screens
Field
Screen display
v-PSU
Displays the output voltage of the
panel power supply
I-PSU
Displays the output current of the
panel power supply
If I-
PSU<150mA
Displays “LOW”; Vbatt displays
the battery voltage
Batt.Res
Displays the value of the battery
internal resistance plus the
battery wiring resistance.
If
Batt.res>999
mOm or
Vbatt.<19Vdc
Displays NO BATT
Loop diagnostic screen
This is a general purpose screen used to display
the values of firmware (FW) parameters related to
loop management, in real time. The rows labelled
A and B display the average, minimum and
maximum value of the relevant FW parameter. The
row labelled C counts the occurrence of events
related to the assigned FW parameter. If you press
the 0 key, all the displayed values reset.
Keyboard test
This screen allows you to test all keys in the panel
UI. If you press any key on the panel UI, the
relevant part of the display goes blank when the
key press is detected.
Menu screen
The MENU screens allow access to the program,
analyze, disable, and modify features of the panel.
For more information on user interaction, see the
User access level, Disable, and Modify sections of
this manual. For installation information, refer to the
FC503/FC506 Installation manual.
Event driven screens
The event driven screens activate when the system
detects events. When an event activates, it overrides
the screen present on the display at that time. An
event driven screen may be overridden by another
event driven screen that has a higher priority.
Table 11 contains the event driven screen priority
assignment.
Table 11: Event Driven screen priority
Event Driven
screens
Priority
Alarm
0 (highest)
Delay to Alarm
1
Fault
2
Warning
3
Walk Test
4 (Lowest)

Page 12 of 38
If a lower priority event screen is suppressed by a
highest priority event screen, the MORE INFO LED
switches on.
To manually access the suppressed event screens in
this condition, use the View list entry on the MAIN
screen.
Warning status
You can program the FC503/ FC506 fire control
panel to provide warning or delay to alarm status
before alarm status.
The warning status is signaled by the warning
display, see Figure 6.
Figure 6: Display Warning status
1
First warning
2
Last warning
3
Warnings number
4
Stored warning index
5
Control panel status
6
If blinking, the control
panel is working
normally
7
First block: point
identification.
Note: The arrow symbol
pointing right indicates
that they are more
blocks to view by using
the Right cursor key. An
arrow symbol pointing
left indicates that there
are previous blocks
available to view by
using the left cursor
key.
The panel will generate a warning when an input
point (detector) exceeds its warning threshold and
there is risk of an alarm.
The following features signal the warning status:
• Warning output points
• Fire control panel display
• Intermittent audible signal on the panel buzzer
• The FC500 repeater
Figure 7: Warning status scrolling Right key
1
To scroll the second block of data for
the WARNING zones, press the Right
key.
2
To scroll the third block of data for the
WARNING causes, press the Right
key.
3
To scroll the fourth block of data for
the WARNING times, press the Right
key.
Table 12: Alphanumeric keypad functions in a
warning status
Key
Function
1
Jumps to the zone status visualization
screen.
2
If the first warning is related to a point,
jump to loop device status visualization
screen.
3
If the last warning is related to a point,
jump to loop device status visualization
screen.
4
Use to display further warning.
When a point warning is present in the
fourth row, a further 4 key press will
cause the UI to jump to the related
loop device status visualization screen.
In the warning status (see Figure 6), use the Right
key to scroll through the second string of data for
warning zones; then use the Right key to scroll
through the third string of data of warning causes;
then use the Right key to scroll through the fourth
string of data of warning times and events.
Note: If the events are linked to the devices, the zone
label alternates with the point label every 3 seconds.
If the zone has not been associated with the point,
only the point label will appear.

Page 13 of 38
Table 13: Cursor key functions
Key
Function
Up
Shows the next event, other than the
first and the last
Down
Shows the previous event, other than
the first and the last
Right
Shows the next string of data
Left
Shows the previous string of data
Table 14: ESC and ENTER key functions on the
MAIN screen
Key
Function
ESC
Cancels the operation
Returns to the MAIN screen
ENTER
Blocks or reactivates the exchange
between the labels of the devices and
those of the zones
Note: When the block is enabled, the
@ character appears on the top left
corner of the display.
Delay to alarm status
The Delay to Alarm status indicates that an input
point (detector) has exceeded its alarm threshold.
The fire control panel will not generate an alarm until
the preset delay to alarm time ends. However, if a
second input point such as a detector in the same
SW zone, detects alarm conditions during the delay
to alarm state (and the double knock (DK) option has
been programmed for that zone), the fire control
panel generates an instant alarm.
If the fire control panel is operating in night mode, it
generates instant alarms only and Delay to Alarm
status is bypassed automatically. If an alarm
procedure is already running, the fire control panel
ignores delay to alarm conditions.
Figure 8: Display: Delay to Alarm status
1
First zone in pre-alarm
2
Number of zones in pre-
alarm (blinking)
3
Control panel status
4
If blinking, the control
panel is operating
normally
5
The arrow symbols
show the presence of
further information such
as point/zone
coordinate, cause, and
time.
6
Point/Zone label
7
To view further zones in
pre-alarm
8
Last zone in pre-alarm
Note: EN54-2 requires the display of the first zone
in delay to alarm, the most recent zone in delay to
alarm, and the number of zones in delay to alarm.

Page 14 of 38
To supply the information about the points in delay
to alarm, the visualization of the delay to alarm is
by zones (default) or by points.
The following features signal the delay to alarm
status:
• Fire control panel display
• LED (1-8) relative zone in delay to alarm mode
blinking
• Intermittent audible signal on the control panel
buzzer
• Delay to alarm output points
During the delay to alarm state you can
silence, investigate, or reset the system, and
view the log.
Table 15: Alphanumeric keypad functions in the
delay to alarm state
Key
Function
1
Jumps to the zone status visualization
screen.
2
Jumps to the first activated loop device
status
3
Jumps to the last activated loop device
status
4
Displays further points in Delay to Alarm.
When a point information is present in
the fourth row, press the 4key further to
cause the UI to jump to the related loop
device status visualization screen
Note: Alphanumeric keypad functions are the same
for the delay to alarm by zones or by points.
Table 16: Cursor key functions in the Delay to
Alarm state
Key
Function
Up
Shows the next available point in Delay to
Alarm, other than the first and the last.
Down
Shows the previous available point in
Delay to Alarm, other than the first and the
last.
Right
Displays the next auxiliary information
about the point (see Figure 2).
Left
Displays the previous auxiliary information
about the point.
Note: Cursor key functions are the same for the
delay to alarm by zones or by points.
Figure 9: Delay to Alarm status: Scrolling Right
key
1
Press the Right key to
scroll to the second
block of data; the
coordinates of the
points
2
Press the Right key to
scroll to the third block
of data; the causes of
the pre-alarms
3
Press the Right key to
scroll to the fourth block
of data; the times of the
pre-alarms
4
Press the Left key to
scroll back to the third
block of data
5
Press the Left key to
scroll back to the
second block of data
6
Press the Left key to
scroll back to the first
block of data
Table 17: ESC and ENTER key functions in the
Delay to Alarm state
Key
Function
ESC
Returns to the MAIN screen.
ENTER
Press for 1 second: Changes between the
visualization modes.
Press for 32 milliseconds: Stops or
restarts the zone/point swap.
Note: The point related to the first zone in Delay to
Alarm is the first point in the zone that becomes
active. For all other zones in delay to alarm, the
related point is the last that becomes active. This
information is updated in real time. The first point in
the Delay to Alarm field contains the information
about the first device that becomes active.

Page 15 of 38
Irrespective of which zone it belongs to; the last point
in the Delay to Alarm field contains the information
about the last activated point.
Alarm status
In the Alarm status, an alarm has been raised by a
detector or manual call point.
The following features signal the Alarm status:
• Alarm LEDs switch ON
• Message on the fire control panel/Repeater
Display (see Figure 10)
• Intermittent audible signal on the fire control
panel
• Alarm output points programmed to signal the
alarm status
Note: EN54-2 requires the display of the first zone in
alarm, the most recent zone in alarm, and the
number of zones in alarm.
Figure 10: Displaying Alarm status
1
First zone in alarm
2
Number of zones in
alarm (blinking)
3
Control panel status
4
If blinking, the control
panel is operating
normally
5
The arrow symbols
show the presence of
further information such
as point/zone
coordinate, cause, and
time.
6
Point/Zone label
7
To view further zones in
alarm
8
Last zone in alarm
Table 18: Alphanumeric keypad functions in the
Alarm state
Key
Function
1
Jumps to the zone status visualization
screen.
Note: To visualize, on the FC500
repeater, press the 1key and also the
ENTER key.
2
Jumps to the first activated Loop
Device Status Visualisation screen.
3
Jumps to the last activated Loop
Device Status Visualisation screen.
4
Displays further points in alarm.
When point information is present in
the fourth row, a further 4key press
causes the UI to jump to the related
Loop Device Status Visualisation
screen.
Note: The alphanumeric keypad use for the alarm by
zones or by points is the same.
Table 19: Cursor key functions in an Alarm by
zone or by point status
Key
Function
Up
Shows the next point in alarm, other
than the first and the last
Down
Shows the previous available point
in alarm, other than the first and the
last
Right
Displays the next auxiliary
information about the point
Left
Displays the previous auxiliary
information about the point
Figure 11: Alarm status scrolling Right key
1
Press the Right key to
scroll to the second
block of data
2
Press the Right key to
scroll to the third block
of data
3
Press the Right key to
scroll to the fourth block
of data

Page 16 of 38
4
Press the Left key to
scroll back to the third
block of data
5
Press the Left key to
scroll back to the
second block of data
6
Press the Left key to
scroll back to the first
block of data
Table 20: ESC and ENTER key functions in the
Delay to Alarm state
Key
Function
ESC
Returns to the MAIN
screen.
ENTER
1 second: Changes
between the
visualization
modes
32 milliseconds:
Stops or restarts the
zone or point
swap
Note: The point related to the first zone in Alarm is
the first point in the zone that becomes active. For all
other zones in alarm the related point is the last that
became active. This information is updated in real
time. Irrespective of which zone it belongs to, the
First Point in Alarm field contains the information
about the first device that becomes active; the Last
Point in Alarm field contains the information about
the last activated point.
Fault status
The following features signal the FAULT
status:
• On or blinking fault LEDs
• Message on the fire control panel display
• Blinking of specific fault LEDs, if present:
•POWER SUPPLY FAULT
•SYSTEM FAULT
•FIRE SIGNAL FAULT
•SOUNDERS FAULT/DIS
• Intermittent audible signal on the fire
control panel
• Alarm output points programmed to signal
the alarm status
Fault output points
Figure 12 shows the FAULT status of the control
panel. The SILENCE key can be used to
momentarily force the fault silenceable output to
STANDBY status.
Figure 12: Display fault states
1
Total number of
faults
2
Control panel
status
3
If blinking, the control
panel is operating
normally
4
First block: Point
identification
Note: The right
arrow symbol
indicates the
presence of more
blocks of fault
information.
5
Stored faults
index
6
Last fault
7
First fault
If the fault condition is cleared (back to normal), all
fault outputs will restore automatically to standby
and clear the fault.
Table 21: Alphanumeric keypad functions in the
Fault state
Key
Function
1
Jumps to the Zone Status Visualization
screen.
2
If the first fault is related to a point, use the
2key to jump to Loop Device Status
Visualization screen.
If the first fault is a loop break fault, use the
2key to jump to the Locate The Loop
Break screen.
If the first fault is related to an item that may
be disabled, the UI moves to the disabling
screen, allowing a fast disablement
procedure.
Note: If the access level is less than L2, the
password will be required before
proceeding to disablement.

Page 17 of 38
3
If the last fault is related to a point, use the
3key to jump to the last activated Loop
Device Status Visualization screen.
If the last fault is a loop break fault, jump to
the Locate the Loop Break screen.
If the last fault is related to an item that can
be disabled, the UI moves to the disabling
screen, in order to allow a fast disablement
procedure.
Note: If the access level is less than L2, the
password will be required before
proceeding to disablement.
4
Displays further faults.
When a point information is present in the
fourth row, a further 4key press will cause
the UI to jump to the related Loop Device
Status Visualization screen.
When a point fault is present in the fourth
row, a further 4key press will cause the UI
jump to the Locate the Loop Break
screen.
If there is a fault related to an item that may
be disabled present in the fourth row, the UI
moves to the disabling screen to allow a
fast disablement procedure.
Note: If the access level is less than L2, the
password will be required before
proceeding to disablement.
Scrolling Right key
As shown in Figure 13, in the FAULT status, use the
Right key to scroll the second string of data of fault
zones; next use the Right key to scroll the third
string of data of fault causes; and then use the Right
key to scroll the fourth string of data of fault times
and events.
Figure 13: Fault status, scrolling right key
1
Press the Right key to
scroll to the second
block of fault zone data
2
Press the Right key to
scroll to the third block
of fault zone data
3
Press the Right key to
scroll to the fourth block
of fault zone data
Note: In the case that a fault is related to a Loop device,
the faulty point label is swapped with the assigned zone
label every3 seconds. If the zone has not been
associated with the point, only the point label will
appear.
Table 22: Cursor key, ESC and ENTER key
functions in Fault status
Key
Function
Up
Shows the previously available fault,
other than the first and the last
Down
Shows the next available fault, other
than the first and the last
Right
Shows the next auxiliary information
about the point
Left
Shows the previous auxiliary
information about the point
ESC
Returns to the MAIN screen
ENTER
Blocks or reactivates the exchange
between the labels of the devices and
those of the zones
Locate loop break screens
These screens are used to manage the Locate loop
break procedure that helps to understand where the
loop is broken. The results of this procedure provide
the number of sensed detector on the left and on the
right side of the analyzed loop.
The screen's sequence is depicted in Figure 15.
Figure 14: Locate loop break screen

Page 18 of 38
Note: During the locate loop break procedure all
the
detectors power down. At the end of the procedure, a
full loop initialization is executed. The devices not in
the configuration are not found.
Locate the not addressed devices
In the case of a NOT POGRAMMED DEV. fault, it is
possible to locate all the unaddressed devices. For
visibility, all the unaddressed devices that have an
LED will be activated (constant on). The sounders
start to sound, while the beacons start to flash.
Ifthere are toomanyunaddressed devices,the
overall current required to keep all the LEDs,
sounders, and beacons active at the same time may
be so high that the loop overcurrent protection
circuit is triggered.
Figure 15: Locatenotaddressed device screens
diagram flow
1
The not addressed
devices are made
visible
2
The not addressed
devices are not made
visible – the process
fails
3
The not addressed
devices are made
visible
4
The not addressed
devices are silenced
5
To MAIN screen

Page 19 of 38
VIEW LOG Parameters
This section provides an overview of the
programming features on the FC503/FC506 panels.
For information on the parameters of each state, refer
to the FC503/FC506 Installation Manual.
You do not require a code to access the following
functions from the MAIN screen:
•View parameters (Use 1=ANALYZE)
•View Log (Use 3=View Log or 1=ANALYZE
and then press the 8 Key)
•View Lists (Use 2= View List)
You require an access code to manage the following
functions:
•Modify
•Disable
•View parameters
See Figure 16 for information on how to view the
different parameters.
Table 23: Alphanumeric keypad functions on the
View Parameters screen
Key
Function
1
Loop: Starts the procedure to allow
you to select and view loop data.
2
Device: Activates the selection and
visualization sequence of real time
loop device data.
3
SW zone: Activates the selection and
displayprocedure for the data
corresponding to all SW zones.
4
Output: Activates the selection and
viewing procedure for the data
corresponding to an output.
5
Network: Starts the procedure to view
all devices (repeaters and MFI
modules) on the RS485 Network.
6
Communic.: Activates the viewing
sequence for the main data on all
communication units.
7
Option: Activates the viewing
sequence for all locally programmed
system options.
8
Log: Starts the procedure to allow you
to view logged events.
9
FW ver.: Starts the procedure to view
the firmware versions of all of the
panel’s processors.
0
Panel: Starts the procedure to allow
you to view the panel information.
Table 24: Cursor, ESC and ENTER key functions
Key
Function
Up, Down, Right,
Left
No functions
ESC
Return to the MAIN
screen.
ENTER
No function
Figure 16: Viewing parameters
1
Access level
2
Control panel status
3
If blinking, the control
panel is operating
normally
4
Options
1 Key - View loop data
Use the 1 key to view the loop data. See Figure 17.
Table 25: Alphanumeric, Cursor, ESC and ENTER
key functions to view loop data
Key
Function
Alphanumeric
keypad
No functions
Up
Selects the next loop
Down
Selects the previous
loop
Right, Left
No functions
ESC
Returns to the
previous screen
ENTER
No function.
Fields
The Loop field shows the current loop on display.
See Figure 18.
The Detectors field displays the number of detectors
sensed on the relevant loop.
The Modules field displays the number of modules
detected on the relevant loop.
The Status field displays the status of the selected
loop. The following are the possible values:
•Working
•Fault
•Standby
•Disabled

Page 20 of 38
The Loop field displays the total current supplied to
all three loops in real time. This field has a 5 second
refresh rate.
2 Key - View devices
Use the 2 key to view the loop device data (select the
loop and then the device). See Figure 17.
Table 26: Alphanumeric, Cursor, ESC and ENTER
key functions to select a loop
Key
Function
Alphanumeric
keypad
Use the 1, 2 or 3 key to
view the loop (see Figure
18)
Note: Use the 1, 2, 3, 4, 5,
and 6 keys to select up to 6
loops on the FC506 panel
Up, Down
No functions
Right
Selects the next available
loop
Left
Selects the previously
available loop
ESC
Cancels the operation
Returns to the previous
screen
ENTER
Confirms and displays the
screen of the selected loop
Figure 17: Viewing loop choice and loop details
1
Access level
2
If blinking, the control
panel is operating
normally
3
Control panel name
4
Selected loop
Figure 18: Viewing loop details
1
Loop number
2
Detector number
3
If blinking, the control
panel is operating
normally
4
Module number
5
Overcurrent that powers
OFF the loop
6
Current value in the 3
loops
7
Current status of the
loop
Selecting the device
After selecting the loop, the loop details are shown.
See Figure 19.
Use the Alphanumeric keypad to insert the device
address. If the address does not exist, the next
available device is selected.
Note: If the device is in the system, square brackets
are present near the address. If the address does not
exist, or is different from that selected in the
underlying bar, arrows are shown.
Table 27: Cursor, ESC and ENTER key functions
to select a device
Key
Function
Up, Down
No functions
Right
Selects the next available
device
Left
Selects the previously
available device
ESC
Cancels the operation
Returns to the previous
screen
ENTER
Confirms and displays the
information for the selected
device
Viewing device data on the loop
Select the loop and then the device. See Figure 19.
Table 28: Alphanumeric keypad, Cursor, ESC and
ENTER key functions to view device data
Key
Function
0
Disables the device (detectors only)
Note: Access level 2 or above is
required
Up
Scrolls through modules with several
inputs or outputs
Down
Scrolls through modules with several
inputs or outputs
Right
Displays the status of the next device
on the same loop
Left
Displays the status of the previous
device on the same loop
ESC
Cancels the operation
Returns to the previous screen
ENTER
No function
Other manuals for FC503
4
This manual suits for next models
1
Table of contents
Other FireClass Control Panel manuals

FireClass
FireClass FC600 User manual

FireClass
FireClass FC503 Owner's manual

FireClass
FireClass FC32-1 Owner's manual

FireClass
FireClass FC503 Technical manual

FireClass
FireClass FC500 Owner's manual

FireClass
FireClass FC501-L User manual

FireClass
FireClass ESSENTIAL 2 User manual

FireClass
FireClass FC501-HK User manual

FireClass
FireClass FC501 Series Technical manual

FireClass
FireClass FC501 Series User manual