GE AF-60 LP User manual

AF-60 LPTM Micro Drive
Installation & Set-up
Quick Guide
Guia rapida
Kurzanleitung
Guide rapide
Guida rapida
The instructions do not purport to cover all details or variations in equipment nor to provide for every possible
contingency to be met in connection with installation, operation or maintenance. Should further information be
desired or should particular problems arise which are not covered suciently for the purchaser’s purposes, the
matter should be referred to the GE company.
AF-650 GP is a trademark of the General Electric Company.
GE
41 Woodford Avenue
Plainville, CT 06062
www.geelectrical.com/drives
132R0038 *MG02H26S* DET-416264A/S/D/F/I
GE

1QuickGuide
1.1.1 Warnings
High Voltage Warning:
The voltage of the frequency converter is dangerous whenever it is connected to mains. Incorrect installation of the motor or frequency
converter may cause damage to the equipment, serious injury or death. Consequently, it is essential to comply with the instructions in this
manual as well as local and national rules and safety regulations.
Warning:
Touching the electrical parts may be fatal - even after the equipment has been disconnected from mains.
Also make sure that other voltage inputs have been disconnected (such as external DC bus power supplies).
Be aware that there may be high voltage on the DC link even when the LEDs are turned off.
Before touching any potentially live parts of the frequency converter, wait at least 4 minutes for all M1, M2 and M3 sizes.
Wait at least 15 minutes for all M4 and M5 sizes.
Leakage Current:
The earth leakage current from the frequency converter exceeds 3.5 mA. According to IEC 61800-5-1 a reinforced Protective Earth connec-
tion must be ensured by means of a min. 10mm² Cu or an addtional PE wire - with the same cable cross section as the Mains wiring - must
be terminated separately.
Residual Current Device:
This product can cause a DC current in the protective conductor. Where a residual current device (RCD) is used for extra protection, only an
RCD of Type B (time delayed) shall be used on the supply side of this product.
Protective earthing of the frequency converter and the use of RCDs must always fo
Motor Thermal Protection:
Motor overload protection is possible by setting Parameter 1-90 Motor thermal protection to the value Electronic overload trip. For the
North American market: Electronic overload functions provide class 20 motor overload protection, in accordance with NEC.
Installation in high altitudes:
For altitudes above 2 km, please contact GE .
AF-60 LPറMicro Drive
DEH-41264A
1
1

1.1.2 Safety Instructions
• Make sure the frequency converter is properly connected to earth.
• Do not remove mains connections, motor connections or other power connections while the frequency converter is connected to power.
• Protect users against supply voltage.
• Protect the motor against overloading according to national and local regulations.
• The earth leakage current exceeds 3.5 mA.
• The [OFF] key is not a safety switch. It does not disconnect the frequency converter from mains.
1.1.3 Available Literature
NB!
This quick guide contains the basic information necessary for installing and running the drive.
If more information is needed, the literature below can be downloaded from: www.geelectrical.com/drives
1.1.4 Approvals
1.1.5 IT Mains
IT Mains
Installation on isolated mains source, i.e. IT mains.
Max. supply voltage allowed when connected to mains: 440 V.
As an option, GE offers line filters for improved harmonics performance.
1.1.6 Avoid unintended Start
While the frequency converter is connected to mains, the motor can be started/stopped using digital commands, bus commands, references or via the drive
Keypad.
• Disconnect the frequency converter from mains whenever personal safety considerations make it necessary to avoid unintended start of any motors.
• To avoid unintended start, always activate the [OFF] key before changing parameters.
AF-60 LPറMicro Drive
2
DEH-41264A
1

1.1.7 Disposal Instruction
Equipment containing electrical components must not be disposed of together with domestic waste.
It must be separately collected with electrical and electronic waste according to local and currently valid legisla-
tion.
1.1.8 Before Commencing Repair Work
1. Disconnect AF-60 LPറMicro Drive from mains (and external DC supply, if present.)
2. Wait for 4 minutes (M1, M2 and M3) and 15 minutes (M4 and M5) for discharge of the DC-link.
3. Disconnect DC bus terminals and brake terminals (if present)
4. Remove motor cable
1.1.9 Side-by-Side Installation
The frequency converter can be mounted side-by-side for IP 20 rating units and requires 100 mm clearance above and below for cooling. Please refer to the
specifications near the end of this document for details on environmental ratings of the frequency converter.
1.1.10 Mechanical Dimensions
A template for drilling can be found on the flap of the packaging.
Illustration 1.1: Mechanical dimensions.
Power (kW) Height (mm) Width (mm) Depth
1)
(mm) Max. Weight
Unit
Size 1 X 200-240 V 3 X 200 -240 V 3 X 380-480 V AA (incl. decoupling plate) a B b C Kg
M1 0.18 - 0.75 0.25 - 0.75 0.37 - 0.75 150 205 140.4 70 55 148 1.1
M2 1.5 1.5 1.5 - 2.2 176 230 166.4 75 59 168 1.6
M3 2.2 2.2 -3.7 3.0 - 7.5 239 294 226 90 69 194 3.0
M4 11.0-15.0 292 347.5 272.4 125 97 241 6.0
M5 18.5-22.0 335 387.5 315 165 140 248 9.5
1)
For Keypad with potentiometer, please add 7.6 mm.
Table 1.1: Mechanical Dimensions
AF-60 LPറMicro Drive
DEH-41264A
3
1

1.1.11 Electrical Installation in General
NB!
All cabling must comply with national and local regulations on cable cross-sections and ambient temperature. Copper conductors required, (60-75rC) rec-
ommended.
Details of terminal tightening torques.
Power (kW) Torque (Nm)
Unit Size 1 x 200-240 V 3 x 200-240 V 3 x 380-480 V Line Motor DC connection/Brake Control Terminals Earth Relay
M1 0.18 - 0.75 0.25 - 0.75 0.37 - 0.75 1.4 0.7 Spade1) 0.15 3 0.5
M2 1.5 1.5 1.5 - 2.2 1.4 0.7 Spade1) 0.15 30.5
M3 2.2 2.2 - 3.7 3.0 - 7.5 1.4 0.7 Spade1) 0.15 3 0.5
M4 11.0-15.0 1.3 1.3 1.3 0.15 30.5
M5 18.5-22.0 1.3 1.3 1.3 0.15 3 0.5
1) Spade connectors (6.3 mm Faston plugs)
Table 1.2: Tightening of terminals.
1.1.12 Fuses
Branch circuit protection:
In order to protect the installation against electrical and fire hazard, all branch circuits in an installation, switch gear, machines etc., must be short-circuited
and overcurrent protected according to national/international regulations.
Short circuit protection:
GE Drive is suitable for a circuit capable of supplying a maximum of 100,000 Arms (symmetrical), 480 V maximum.
Overcurrent protection:
Provide overload protection to avoid overheating of the cables in the installation. Overcurrent protection must always be carried out according to national
regulations.
Non UL compliance:
If UL/cUL is not to be complied with, GE recommends using the fuses mentioned in the below table, which will ensure compliance with EN50178/IEC61800-5-1:
In case of malfunction, not following the fuse recommendation may result in damage to the frequency converter.
AF-60 LPറMicro Drive
4
DEH-41264A
1

Max. fuses UL
Max. fuses non UL
Bussmann Bussmann Bussmann Littel fuse Ferraz-
Shawmut
Ferraz-
Shawmut
1 X 200-240 V
Type RK1 Type J Type T Type RK1 Type CC Type RK1 Type gG
1/4 - 1/2 KTN-R15 JKS-15 JJN-15 KLN-R15 ATM-R15 A2K-15R 16A
1KTN-R25 JKS-25 JJN-25 KLN-R25 ATM-R25 A2K-25R 25A
2 KTN-R35 JKS-35 JJN-35 KLN-R35 - A2K-35R 35A
3KTN-R50 JKS-50 JJN-50 KLN-R50 -A2K-50R 50A
3 x 200-240 V
1/3 KTN-R10 JKS-10 JJN-10 KLN-R10 ATM-R10 A2K-10R 10A
1/2 KTN-R15 JKS-15 JJN-15 KLN-R15 ATM-R15 A2K-15R 16A
1KTN-R20 JKS-20 JJN-20 KLN-R20 ATM-R20 A2K-20R 20A
2 KTN-R25 JKS-25 JJN-25 KLN-R25 ATM-R25 A2K-25R 25A
3KTN-R40 JKS-40 JJN-40 KLN-R40 ATM-R40 A2K-40R 40A
5 KTN-R40 JKS-40 JJN-40 KLN-R40 - A2K-40R 40A
3 x 380-480 V
1/2 - 1 KTS-R10 JKS-10 JJS-10 KLS-R10 ATM-R10 A6K-10R 10A
2KTS-R15 JKS-15 JJS-15 KLS-R15 ATM-R15 A2K-15R 16A
3 KTS-R20 JKS-20 JJS-20 KLS-R20 ATM-R20 A6K-20R 20A
4KTS-R40 JKS-40 JJS-40 KLS-R40 ATM-R40 A6K405R 40A
5 KTS-R40 JKS-40 JJS-40 KLS-R40 ATM-R40 A6K-40R 40A
7.5 KTS-R40 JKS-40 JJS-40 KLS-R40 -A6K-40R 40A
10 KTS-R40 JKS-40 JJS-40 KLS-R40 - A6K-40R 40A
15 KTS-R60 JKS-60 JJS-60 KLS-R60 -A6K-60R 63A
20 KTS-R60 JKS-60 JJS-60 KLS-R60 - A6K-60R 63A
25 KTS-R60 JKS-60 JJS-60 KLS-R60 -A6K-60R 80A
30 KTS-R60 JKS-60 JJS-60 KLS-R60 - A6K-60R 80A
Table 1.3: Fuses
AF-60 LPറMicro Drive
DEH-41264A
5
1

1.1.13 Connecting to Mains and Motor
The frequency converter is designed to operate all standard three-phased asynchronous motors.
The frequency converter is designed to accept mains/motor cables with a maximum cross-section of 4 mm2/10 AWG (M1, M2 and M3) and maximum cross-
section 16 mm2/6 AWG (M4 and M5).
• Use a shielded/armored motor cable to comply with EMC emission specifications, and connect this cable to both the decoupling plate and the motor
metal.
• Keep motor cable as short as possible to reduce the noise level and leakage currents.
• For further details on mounting of the decoupling plate, please see instruction MI.02.BX.YY.
• Also see EMC-Correct Installation in Operating Instruction MG.02.AX.YY.
Step 1: First, mount the earth wires to earth terminal.
Step 2: Connect motor to terminals U, V and W.
Step 3: Mount mains supply to terminals L1/L, L2 and
L3/N (3-phase) or L1/L and L3/N (single-phase) and tighten.
Illustration 1.2: Mounting of earth cable, mains and motor
wires.
AF-60 LPറMicro Drive
6
DEH-41264A
1

1.1.14 Control Terminals
All control cable terminals are located underneath the terminal cover in
front of the frequency converter. Remove the terminal cover using a screw-
driver.
NB!
See back of terminal cover for outlines of control terminals and switches.
Illustration 1.3: Removing terminal cover.
The illustration below shows all control terminals of the frequency converter. Applying Start (term. 18) and an analog reference (term. 53 or 60) make the fre-
quency converter run.
Illustration 1.4: Overview of control terminals in PNP-configuration and factory setting.
AF-60 LPറMicro Drive
DEH-41264A
7
1

1.1.15 Power Circuit - Overview
Illustration 1.5: Diagram showing all electrical terminals.
* Brake (BR+ and BR-) are not applicable for Unit Size M1.
Brake resistors are available from GE.
Improved power factor and EMC performance can be achieved by installing optional GE line filters.
GE power filters can also be used for load sharing.
1.1.16 Load sharing/Brake
Use 6.3 mm insulated Faston Plugs designed for high voltage for DC (Load Sharing and brake).
Load sharing: Connect terminals UDC- and UDC/BR+.
Brake: Connect terminals BR- and UDC/BR+ (Not applicable for Unit Size M1).
Note that voltage levels of up to 850 V DC may occur between terminals
UDC+/BR+ and UDC-. Not short circuit protected.
AF-60 LPറMicro Drive
8
DEH-41264A
1

1.1.17 Programming with Keypad
For detailed information on programming, please see Programming Guide, AF-60 LPറMicro Drive.
NB!
The frequency converter can also be programmed from a PC via RS485 com-port by installing the DCT-10 Drive Control Tool.
This software can be downloaded from the GE web site: www. geelectrical.com/drives
Illustration 1.6: Description of Keypad buttons and display
Use the [MENU] key to select one of the following menus:
Status:
For readouts only.
Quick Menu:
For access to Quick Menus 1 and 2, respectively.
Main Menu:
For access to all parameters.
Navigation Keys:
[Back]: For moving to the previous step or layer in the navigation structure.
Arrows [
Ⴃ
] [
Ⴍ
]: For manoeuvring between parameter groups, parameters and within parameters.
[OK]: For selecting a parameter and for accepting changes to parameter settings.
Operation Keys:
A yellow light above the operation keys indicates the active key.
[Hand]: Starts the motor and enables control of the frequency converter via the Keypad.
AF-60 LPറMicro Drive
DEH-41264A
9
1

[Off/Reset]: Stops the motor (off). If in alarm mode the alarm will be reset.
[Auto]: The frequency converter is controlled either via control terminals or serial communication.
[Potentiometer]: The potentiometer works in two ways depending on the mode in which the frequency converter is running.
In Auto Mode the potentiometer acts as an extra programmable analog input.
In Hand Mode the potentiometer controls local reference.
Arrows [
Ⴃ
] and [
Ⴍ
] toggles between the choices in each menu.
The display indicates the status mode with a small arrow above “Status”.
The Quick Menu gives easy access to the most frequently used parameters.
1. To enter the Quick Menu, press [MENU] key until indicator in display is placed above Quick Menu.
2. Use [
Ⴃ
] [
Ⴍ
] to select either QM1 or QM2, then press [OK].
3. Use [
Ⴃ
] [
Ⴍ
] to browse through the parameters in the Quick Menu.
4. Press [OK] to select a parameter.
5. Use [
Ⴃ
] [
Ⴍ
] to change the value of a parameter setting.
6. Press [OK] to accept the change.
7. To exit, press either [Back] twice to enter Status, or press [Menu] once to enter Main Menu.
No Name Range Default Function
1-20 Motor Power [kW]/[HP] [0.09kW/0.12HP -30kW/40HP] Unit dependent Enter motor power from nameplate data
1-22 Motor Voltage [50 - 999V] 230/400 Enter motor voltage from nameplate data
1-23 Motor Frequency [20 - 400 Hz] 50 Enter motor frequency form nameplate data
1-24 Motor Current [0.01 - 100.00 A] Unit dependent Enter motor current from nameplate data
1-25 Motor nominal speed [100 - 9999 RPM] Unit dependent Enter motor nominal speed from nameplate data
1-29 Auto Tune [0] = off
[2] = Enable Auto Tune
[0] = off Use Auto Tune to optimize motor performance.
1. Stop Drive
2. Choose [2]
3. "Hand "
3-02 Minimum reference [-4999 - 4999] 0 Enter value for minimum reference
3-03 Maximum reference [-4999 - 4999] 50.00 Enter value for maximum reference
3-41 Accel time 1 [0.05 - 3600s] 3.00 (10.00
1)
)Accel time from 0 to rated motor frequency par. 1-23
3-42 Decel time 1 [0.05 - 3600s] 3.00 (10.00
1)
)Decel time form rated motor frequency par. 1-23 to 0
1)
M4 and M5 only
Table 1.4: Basic Settings Quick Menu 1
The Main Menu gives access to all parameters.
1. To enter the Main Menu, press [MENU] key until indicator in display is placed above Main Menu.
2. Use [
Ⴃ
] [
Ⴍ
] to browse through the parameter groups.
3. Press [OK] to select a parameter group.
4. Use [
Ⴃ
] [
Ⴍ
] to browse through the parameters in the specific group.
5. Press [OK] to select the parameter.
6. Use [
Ⴃ
] [
Ⴍ
] to set/change the parameter value.
7. Press [OK] to accept the value.
8. To exit, press either [Back] twice to enter Quick Menu, or press [Menu] once to enter Status.
AF-60 LPറMicro Drive
10
DEH-41264A
1

Parameter Overwiev
0-XX Operation/Display
0-0X Basic Settings
0-03 Regional Settings
[0] International
*[1] US
0-04 Oper. State at Power-up (Hand)
[0] Resume
*[1] Forced stop, ref = old
[2] Forced stop, ref = 0
0-1X Set-up Handling
0-10 Active Set-up
*[1] Setup 1
[2] Setup 2
[9] Multi Setup
0-11 Edit Set-up
*[1] Setup 1
[2] Setup 2
[9] Active Setup
0-12 Link Setups
[0] Not Linked
*[20] Linked
0-31 Custom Readout Min Scale
0.00 – 9999.00 * 0.00
0-32 Custom Readout Max Scale
0.00 – 9999.00 * 100.0
0-4X Keypad
0-40 [Hand] Key on Keypad
[0] Disabled
*[1] Enabled
0-41 [Off / Reset] Key on Keypad
[0] Disable All
*[1] Enable All
[2] Enable Reset Only
0-42 [Auto] Key on Keypad
[0] Disabled
*[1] Enabled
0-5X Copy/Save
0-50 Keypad Copy
*[0] No copy
[1] All to Keypad
[2] All from Keypad
[3] Size indep. from Keypad
0-51 Set-up Copy
*[0] No copy
[1] Copy from setup 1
[2] Copy from setup 2
[9] Copy from Factory setup
0-6X Password
0-60 (Main) Menu Password
0 - 999 * 0
1-XX Load/Motor
1-0X General Settings
1-00 Configuration Mode
*[0] Speed open loop
[3] Process
1-01 Motor Control Principle
[0] U/f
*[1] Adv.Vector Control
1-03 Torque Characteristics
*[0] Constant torque
[2] Energy Saving
1-05 Local Mode Configuration
[0] Speed Open Loop
*[2] As config in par. 1-00
1-2X Motor Data
1-20 Motor Power [kW] [HP]
[1] 0.09 kW/0.12 HP
[2] 0.12 kW/0.16 HP
[3] 0.18 kW/0.25 HP
[4] 0.25 kW/0.33 HP
[5] 0.37 kW/0.50 HP
[6] 0.55 kW/0.75 HP
[7] 0.75 kW/1.00 HP
[8] 1.10 kW/1.50 HP
[9] 1.50 kW/2.00 HP
[10] 2.20 kW/3.00 HP
[11] 3.00 kW/4.00 HP
[12] 3.70 kW/5.00 HP
[13] 4.00 kW/5.40 HP
[14] 5.50 kW/7.50 HP
[15] 7.50 kW/10.00 HP
[16] 11.00 kW/15.00 HP
[17] 15.00 kW/20.00 HP
[18] 18.50 kW/25.00 HP
[19] 22.00 kW/29.50 HP
[20] 30.00 kW/40.00 HP
1-22 Motor Voltage
50 - 999 V * 230 - 400 V
1-23 Motor Frequency
20 - 400 Hz * 60 Hz
1-24 Motor Current
0.01 - 100.00 A * Motortype dep.
1-25 Motor Nominal Speed
100 - 9999 rpm * Motortype dep.
1-29 Auto Tune
*[0] Off
[2] Enable Auto Tune
1-3X Adv. Motor Data
1-30 Stator Resistance (Rs)
[Ohm] * Dep. on motor data
1-33 Stator Leakage Reactance (X1)
[Ohm] * Dep. on motor data
1-35 Main Reactance (Xh)
[Ohm] * Dep. on motor data
1-5X Load Indep. Setting
1-50 Motor Magnetisation at 0 Speed
0 - 300 % * 100 %
1-52 Min Speed Norm. Magnet. [Hz]
0.0 - 10.0 Hz * 0.0 Hz
1-55 U/f Characteristic - U
0 - 999.9 V
1-56 U/f Characteristic - F
0 - 400 Hz
1-6X Load Depen. Setting
1-60 Low Speed Load Compensation
0 - 199 % * 100 %
1-61 High Speed Load Compensation
0 - 199 % * 100 %
1-62 Slip Compensation
-400 - 399 % * 100 %
1-63 Slip Compensation Time Constant
0.05 - 5.00 s * 0.10 s
1-7X Start Adjustments
1-71 Holding Time
0.0 - 10.0 s * 0.0 s
1-72 Start Function
[0] DC hold / delay time
[1] DC brake / delay time
*[2] Coast / delay time
1-73 Start Mode
*[0] Disabled
[1] Enable - Catch Spinning Load
1-8X Stop Adjustments
1-80 Function at Stop
*[0] Coast
[1] DC hold
1-82 Min Speed for Funct. at Stop [Hz]
0.0 - 20.0 Hz * 0.0 Hz
1-9XMotor Temperature
1-90 Motor Thermal Protection
*[0] No protection
[1] Termistor warning
[2] Thermistor trip
[3] Electronic Overload warning
[4] Electronic Overload trip
1-93 Thermistor Resource
*[0] None
[1] Analog input 53
[6] Digital input 29
2-XX Brakes
2-0XDC-Brake
2-00 DC Hold Current
0 - 150 % * 50 %
2-01 DC Brake Current
0 - 150 % * 50 %
2-02 DC Braking Time
0.0 - 60.0 s * 10.0 s
2-04 DC Brake Cut In Speed
0.0 - 400.0 Hz * 0.0 Hz
2-1X Brake Energy Funct.
2-10 Brake Function
*[0] Off
[1] Resistor brake
[2] AC brake
2-11 Brake Resistor (ohm)
5 - 5000 * 5
2-16 AC Brake, Max current
0 - 150 % * 100 %
2-17 Over-voltage Control
*[0] Disabled
[1] Enabled (not at stop)
[2] Enabled
2-2* Mechanical Brake
2-20 Release Brake Current
0.00 - 100.0 A * 0.00 A
2-22 Activate Brake Speed [Hz]
0.0 - 400.0 Hz * 0.0 Hz
3-XX Reference / Ramps
3-0X Reference Limits
3-00 Reference Range
*[0] Min - Max
[1] -Max - +Max
3-02 Minimum Reference
-4999 - 4999 * 0.000
3-03 Maximum Reference
-4999 - 4999 * 50.00
3-1X References
3-10 Preset Reference
-100.0 - 100.0 % * 0.00 %
3-11 Jog Speed [Hz]
0.0 - 400.0 Hz * 5.0 Hz
3-12 Catch up/slow Down Value
0.00 - 100.0 % * 0.00 %
AF-60 LPറMicro Drive
DEH-41264A
11
1

3-14 Preset Relative Reference
-100.0 - 100.0 % * 0.00 %
3-15 Reference Resource 1
[0] No function
*[1] Analog Input 53
[2] Analog input 60
[8] Pulse input 33
[11] Local bus ref
[21] Keypad Potentiometer
3-16 Reference Resource 2
[0] No function
[1] Analog Input 53
*[2] Analog input 60
[8] Pulse input 33
*[11] Local bus ref
[21] Keypad Potentiometer
3-17 Reference Resource 3
[0] No function
[1] Analog Input 53
[2] Analog input 60
[8] Pulse input 33
*[11] Local bus ref
[21] Keypad Potentiometer
3-18 Relative Scaling Ref. Resource
*[0] No function
[1] Analog Input 53
[2] Analog input 60
[8] Pulse input 33
[11] Local bus ref
[21] Keypad Potentiometer
3-4X Accel/Decel 1
3-40 Accel/Decel 1 Pattern
*[0] Linear
[2] S-Shape
3-41 Accel Time 1
0.05 - 3600 s * 3.00 s (10.00 s
1)
)
3-42 Decel Time 1
0.05 - 3600 s * 3.00 s (10.00 s
1)
)
3-5X Accel/Decel 2
3-50 Accel/Decel 2 Pattern
*[0] Linear
[2] S-Shape
3-51 Accel Time 2
0.05 - 3600 s * 3.00 s (10.00 s
1)
)
3-52 Decel Time 2
0.05 - 3600 s * 3.00 s (10.00 s
1)
)
3-8X Other Ramps
3-80 Jog Accel and Decel Time
0.05 - 3600 s * 3.00 s (10.00 s
1)
)
3-81 Quick Stop Decel Time
0.05 - 3600 s * 3.00 s(10.00 s
1)
)
4-XX Limits / Warnings
4-1X Motor Limits
4-10 Reverse Lock
[0] Reverse Lock
[1] Reverse
*[2] Both
4-12 Motor Speed Low Limit [Hz]
0.0 - 400.0 Hz * 0.0 Hz
4-14 Motor Speed High Limit [Hz]
0.1 - 400.0 Hz * 65.0 Hz
4-16 Torque Limit Motor Mode
0 - 400 % * 150 %
4-17 Torque Limit Generator Mode
0 - 400 % * 100 %
4-5X Adj. Warnings
4-50 Warning Current Low
0.00 - 100.00 A * 0.00 A
4-51 Warning Current High
0.00 - 100.00 A * 100.00 A
4-58 Missing Motor Phase Function
[0] Off
*[1] On
4-6X Jump Frequencies
4-61 Jump Frequency From [Hz]
0.0 - 400.0 Hz * 0.0 Hz
4-63 Jump FrequencyTo [Hz]
0.0 - 400.0 Hz * 0.0 Hz
5-1X Digital Inputs
5-10 Terminal 18 Digital Input
[0] No function
[1] Reset
[2] Coast inverse
[3] Coast and reset inv.
[4] Quick stop inverse
[5] DC-brake inv.
[6] Stop inv
*[8] Start
[9] Latched start
[10] Reversing
[11] Start reversing
[12] Enable start forward
[13] Enable start reverse
[14] Jog
[16-18] Preset ref bit 0-2
[19] Freeze reference
[20] Freeze output
[21] Speed up
[22] Speed down
[23] Setup select bit 0
[28] Catch up
[29] Slow down
[34] Ramp bit 0
[60] Counter A (up)
[61] Counter A (down)
[62] Reset counter A
[63] Counter B (up)
[64] Counter B (down)
[65] ResetCounter B
5-11 Terminal 19 Digital Input
See par. 5-10. * [10] Reversing
5-12 Terminal 27 Digital Input
See par. 5-10. * [1] Reset
5-13 Terminal 29 Digital Input
See par. 5-10. * [14] Jog
5-15 Terminal 33 Digital Input
See par. 5-10. * [16] Preset ref bit 0
[26] Precise Stop Inverse
[27] Start, Precise Stop
[32] Pulse Input
5-4X Relays
5-40 Function Relay
*[0] No opreation
[1] Control ready
[2] Drive ready
[3] Drive ready, Remote
[4] Enable / No warning
[5] Drive running
[6] Running / No warning
[7] Run in range / No warning
[8] Run on ref / No warning
[9] Alarm
[10] Alarm or warning
[12] Out of current range
[13] Below current, low
[14] Above current, high
[21] Thermal warning
[22] Ready, No thermal warning
[23] Remote ready, No thermal warning
[24] Ready, Voltage ok
[25] Reverse
[26] Bus ok
[28] Brake,NoWarn
[29] Brake ready/NoFault
[30] BrakeFault (IGBT)
[32] Mech.brake control
[36] Control word bit 11
[51] Local ref. active
[52] Remote ref. active
[53] No alarm
[54] Start cmd active
[55] Running reverse
[56] Drive in hand mode
[57] Drive in auto mode
[60-63] Comparator 0-3
[70-73] Logic rule 0-3
[81] Logic Controller digital output B
5-5X Pulse Input
5-55 Terminal 33 Low Frequency
20 - 4999 Hz * 20 Hz
5-56 Terminal 33 High Frequency
21 - 5000 Hz * 5000 Hz
5-57 Term. 33 Low Ref./Feedb. Value
-4999 - 4999 * 0.000
5-58 Term. 33 High Ref./Feedb. Value
-4999 - 4999 * 50.000
6-XX Analog In/Out
6-0X Analog I/O Mode
6-00 Live Zero Timeout Time
1 - 99 s * 10 s
6-01 Live Zero TimeoutFunction
*[0] Off
[1] Freeze output
[2] Stop
[3] Jogging
[4] Max speed
[5] Stop and trip
6-1X Analog Input 1
6-10 Terminal 53 Low Voltage
0.00 - 9.99 V * 0.07 V
6-11 Terminal 53 High Voltage
0.01 - 10.00 V * 10.00 V
6-12 Terminal 53 Low Current
0.00 - 19.99 mA * 0.14 mA
1)
M4 and M5 only
AF-60 LPറMicro Drive
12
DEH-41264A
1

6-13 Terminal 53 High Current
0.01 - 20.00 mA * 20.00 mA
6-14 Term. 53 Low Ref./Feedb. Value
-4999 - 4999 * 0.000
6-15 Term. 53 High Ref./Feedb. Value
-4999 - 4999 * 50.000
6-16 Terminal 53 Filter Time Constant
0.01 - 10.00 s * 0.01 s
6-19 Terminal 53 mode
*[0] Voltage mode
[1] Current mode
6-2X Analog Input 2
6-22 Terminal 60 Low Current
0.00 - 19.99 mA * 0.14 mA
6-23 Terminal 60 High Current
0.01 - 20.00 mA * 20.00 mA
6-24 Term. 60 Low Ref./Feedb. Value
-4999 - 4999 * 0.000
6-25 Term. 60 High Ref./Feedb. Value
-4999 - 4999 * 50.00
6-26 Terminal 60 Filter Time Constant
0.01 - 10.00 s * 0.01 s
6-8X Keypad potentiometer
6-81 Keypad potm. Low Reference
-4999 - 4999 * 0.000
6-82 Keypad potm. High Reference
-4999 - 4999 * 50.00
6-9X Analog Output xx
6-90 Terminal 42 Mode
*[0] 0-20 mA
[1] 4-20 mA
[2] Digital Output
6-91 Terminal 42 Analog Output
*[0] No operation
[10] Output Frequency
[11] Reference
[12] Feedback
[13] Motor Current
[16] Power
[20] Bus Reference
6-92 Terminal 42 Digital Output
See par. 5-40
*[0] No Operation
[80] Logic Controller Digital Output A
6-93 Terminal 42 Output Min Scale
0.00 - 200.0 % * 0.00 %
6-94 Terminal 42 Output Max Scale
0.00 - 200.0 % * 100.0 %
7-XX Controllers
7-2X Process Ctrl. Feedb
7-20 Process CL Feedback 1 Resource
*[0] NoFunction
[1] Analog Input 53
[2] Analog input 60
[8] PulseInput33
[11] LocalBusRef
7-3X Process PI
Ctrl. 7-30 Process PI Normal/ Inverse Ctrl
*[0] Normal
[1] Inverse
7-31 Process PI Anti Windup
[0] Disable
*[1] Enable
7-32 Process PI Start Speed
0.0 - 200.0 Hz * 0.0 Hz
7-33 Process PI Proportional Gain
0.00 - 10.00 * 0.01
7-34 Process PI Integral Time
0.10 - 9999 s * 9999 s
7-38 Process PI Feed Forward Factor
0 - 400 % * 0 %
7-39 On Reference Bandwidth
0 - 200 % * 5 %
8-XX Comm. and Options
8-0X General Settings
8-01 Control Site
*[0] Digital and ControlWord
[1] Digital only
[2] ControlWord only
8-02 Control Word Source
[0] None
*[1] GE Drive RS485
8-03 Control Word Timeout Time
0.1 - 6500 s * 1.0 s
8-04 Control Word Timeout Function
*[0] Off
[1] Freeze Output
[2] Stop
[3] Jogging
[4] Max. Speed
[5] Stop and trip
8-06 Reset Control Word Timeout
*[0] No Function
[1] Do reset
8-3X GE Drive Port Settings
8-30 Protocol
*[0] GE Drive
[2] Modbus RTU
8-31 Address
1 - 247 * 1
8-32 GE Drive Port Baud Rate
[0] 2400 Baud
[1] 4800 Baud
*[2] 9600 Baud
[3] 19200 Baud
[4] 38400 Baud
8-33 GE Drive Port Parity
*[0] Even Parity, 1 Stop Bit
[1] Odd Parity, 1 Stop Bit
[2] No Parity, 1 Stop Bit
[3] No Parity, 2 Stop Bits
8-35 Minimum Response Delay
0.001-0.5 * 0.010 s
8-36 Max Response Delay
0.100 - 10.00 s * 5.000 s
8-5X Digital/Bus
8-50 Coasting Select
[0] DigitalInput
[1] Bus
[2] LogicAnd
*[3] LogicOr
8-51 Quick Stop Select
See par. 8-50 * [3] LogicOr
8-52 DC Brake Select
See par. 8-50 * [3] LogicOr
8-53 Start Select
See par. 8-50 * [3] LogicOr
8-54 Reversing Select
See par. 8-50 * [3] LogicOr
8-55 Set-up Select
See par. 8-50 * [3] LogicOr
8-56 Preset Reference Select
See par. 8-50 * [3] LogicOr
8-9X Bus Jog / Feedback
8-94 Bus feedback 1
0x8000 - 0x7FFF * 0
13-XX Controller Logic
13-0X Logic Controller Settings
13-00 Logic Controller Mode
*[0] Off
[1] On
13-01 Start Event
[0] False
[1] True
[2] Running
[3] InRange
[4] OnReference
[7] OutOfCurrentRange
[8] BelowILow
[9] AboveIHigh
[16] ThermalWarning
[17] MainOutOfRange
[18] Reversing
[19] Warning
[20] Alarm_Trip
[21] Alarm_TripLock
[22-25] Comparator 0-3
[26-29] LogicRule0-3
[33] DigitalInput_18
[34] DigitalInput_19
[35] DigitalInput_27
[36] DigitalInput_29
[38] DigitalInput_33
*[39] StartCommand
[40] DriveStopped
13-02 Stop Event
See par. 13-01 * [40] DriveStopped
13-03 Reset Logic Controller
*[0] Do not reset
[1] Reset Logic Controller
AF-60 LPറMicro Drive
DEH-41264A
13
1

13-1X Comparators
13-10 Comparator Operand
*[0] Disabled
[1] Reference
[2] Feedback
[3] MotorSpeed
[4] MotorCurrent
[6] MotorPower
[7] MotorVoltage
[8] DCLinkVoltage
[12] AnalogInput53
[13] AnalogInput60
[18] PulseInput33
[20] AlarmNumber
[30] CounterA
[31] CounterB
13-11 Comparator Operator
[0] Less Than
*[1] Approximately equals
[2] Greater Than
13-12 Comparator Value
-9999 - 9999 * 0.0
13-2X Timers
13-20 LC Controller Timer
0.0 - 3600 s * 0.0 s
13-4X Logic Rules
13-40 Logic Rule Boolean 1
See par. 13-01 * [0] False
[30] - [32] LC Time-out 0-2
13-41 Logic Rule Operator 1
*[0] Disabled
[1] And
[2] Or
[3] And not
[4] Or not
[5] Not and
[6] Not or
[7] Not and not
[8] Not or not
13-42 Logic Rule Boolean 2
See par. 13-40 * [0] False
13-43 Logic Rule Operator 2
See par. 13-41 * [0] Disabled
13-44 Logic Rule Boolean 3
See par. 13-40 * [0] False
13-5X States
13-51 LC Controller Event
See par. 13-40 * [0] False
13-52 LC Controller Action
*[0] Disabled
[1] NoAction
[2] SelectSetup1
[3] SelectSetup2
[10-17] SelectPresetRef0-7
[18] Select Accel/Decel 1.
[19] Select Accel/Decel 2.
[22] Run
[23] RunReverse
[24] Stop
[25] Qstop
[26] DCstop
[27] Coast
[28] FreezeOutput
[29] StartTimer0
[30] StartTimer1
[31] StartTimer2
[32] Set Digital Output A Low
[33] Set Digital Output B Low
[38] Set Digital Output A High
[39] Set Digital Output B High
[60] ResetCounterA
[61] ResetCounterB
14-XX Special Functions
14-0X Carrier Frequency
14-01 Motor Noise
(Carrier Frequency)
[0] 2 kHz
*[1] 4 kHz
[2] 8 kHz
[4] 16 kHz
14-03 Overmodulation
[0] Off
*[1] On
14-1X Mains monitoring
14-12 Function at mains imbalance
*[0] Trip
[1] Warning
[2] Disabled
14-2X Trip Reset
14-20 Reset Mode
*[0] Manual reset
[1-9] AutoReset 1-9
[10] AutoReset 10
[11] AutoReset 15
[12] AutoReset 20
[13] Infinite auto reset
14-21 Automatic Restart Time
0 - 600 s * 10 s
14-22 Restore Factory Settings
*[0] Normal Operation
[2] Restore Factory Settings
14-26 Action At Drive Fault
*[0] Trip
[1] Warning
14-4X Energy Savings
14-41 Energy Savings Minimum Magnetisation
40 - 75 % * 66 %
15-XX Drive Information
15-0X Operating Data
15-00 Operating Days
15-01 Running Hours
15-02 kWh Counter
15-03 Power Ups
15-04 Over Temps
15-05 Over Volts
15-06 Reset kWh Counter
*[0] Do not reset
[1] Reset counter
15-07 Reset Running Hours Counter
*[0] Do not reset
[1] Reset counter
15-3X Fault Log
15-30 Fault Log: Error Code
15-4X Drive Identification
15-40 GE Drive Type
15-41 Power Section
15-42 Voltage
15-43 Software Version
15-46 Frequency Converter Order. No
15-48 Keypad Id No
15-51 Frequency Converter Serial No
16-XX Data Readouts
16-0X General Status
16-00 Control Word
0 - 0XFFFF
16-01 Reference [Unit]
-4999 - 4999 * 0.000
16-02 Reference %
-200.0 - 200.0 % * 0.0%
16-03 Status Word
0 - 0XFFFF
16-05 Main Actual Value [%]
-200.0 - 200.0 % * 0.0%
16-09 Custom Readout
Dep. on par. 0-31, 0-32 and 4-14
16-1X Motor Status
16-10 Power [kW]
16-11 Power [hp]
16-12 Motor Voltage [V]
16-13 Frequency [Hz]
16-14 Motor Current [A]
16-15 Frequency [%]
16-18 Motor Thermal [%]
16-3X Drive Status
16-30 DC Link Voltage
16-34 Heatsink Temp.
16-35 Inverter Thermal
16-36 Drive Nominal current
16-37 Drive Maximum Current
16-38 Logic Controller State
16-5X Ref. / Feedb.
16-50 External Reference
16-51 Pulse Reference
16-52 Feedback [Unit]
16-6X Inputs / Outputs
16-60 Digital Input 18,19,27,33
0 - 1111
16-61 Digital Input 29
0 - 1
16-62 Analog Input 53 (volt)
16-63 Analog Input 53 (current)
16-64 Analog Input 60
16-65 Analog Output 42 [mA]
16-68 Pulse Input [Hz]
16-71 Relay Output [bin]
16-72 Counter A
16-73 Counter B
16-8X Fieldbus / GE Drive Port
16-86 GE Drive Port REF 1
0x8000 - 0x7FFFF
16-9X Diagnosis Readouts
16-90 Alarm Word
0 - 0XFFFFFFFF
16-92 Warning Word
0 - 0XFFFFFFFF
16-94 Ext. Status Word
0 - 0XFFFFFFFF18-XX Extended Motor Data
18-8X Motor Resistors
18-80 Stator Resistance (High resolution)
0.000 - 99.990 ohm * 0.000 ohm
18-81 Stator Leakage Reactance(High resolution)
0.000 - 99.990 ohm * 0.000 ohm
AF-60 LPറMicro Drive
14
DEH-41264A
1

No. Description Warning Alarm Trip
Lock
Error Cause of Problem
2Live zero error X X Signal on terminal 53 or 60 is less than 50% of value set in par. 6-10,
6-12 and 6-22.
4Mains phase loss
1)
X X X Missing phase on supply side, or too high voltage imbalance. Check
supply voltage.
7DC over voltage
1)
X X Intermediate circuit voltage exceeds limit.
8DC under voltage
1)
X X Intermediate circuit voltage drops below “voltage warning low” limit.
9Driveoverloaded X X More than 100% load for too long.
10 Motor Electronic Overload over
temperature
X X Motor is too hot due to more than 100% load for too long.
11 Motor thermistor over tempera-
ture
X X Thermistor or thermistor connection is disconnected.
12 Torque limit X Torque exceeds value set in either par. 4-16 or 4-17.
13 Over Current X X X Drive current limit is exceeded.
14 Earth fault X X Discharge from output phases to ground.
16 Short Circuit X X Short-circuit in motor or on motor terminals.
17 Control word timeout X X No communication to frequency converter.
25 Brake resistor short-circuited X X Brake resistor is short-circuited, thus brake function is disconnected.
27 Brake chopper short-circuited X X Brake transistor is short-circuited, thus brake function is disconnec-
ted.
28 Brake check X Brake resistor is not connected/working
29 Power board over temp X X X Heat-sink cut-out temperature has been reached.
30 Motor phase U missing X X Motor phase U is missing. Check the phase.
31 Motor phase V missing X X Motor phase V is missing. Check the phase.
32 Motor phase W missing X X Motor phase W is missing. Check the phase.
38 Internal fault X X Contact local GE supplier.
44 Earth fault X X Discharge from output phases to ground.
47 Control Voltage Fault X X 24 V DC may be overloaded.
51 Auto Tune check U
nom
and I
nom
X Wrong setting for motor voltage and/or motor current.
52 Auto Tune low I
nom
X Motor current is too low. Check settings.
59 Current limit X Drive overload.
63 Mechanical Brake Low X Actual motor current has not exceeded “release brake” current
within “start delay” time window.
80 Drive restored to Factory Settings X All parameter settings are restored to factory default settings.
84 The connection between drive
and Keypad is lost
X No communication between Keypad and frequency converter
85 Button disabled X See parameter group 0-4* Keypad
86 Copy fail X An error occurred while copying from frequency converter to
Keypad or vice versa.
87 Keypad data invalid X Occurs when copying from Keypad if the Keypad contains errone-
ous data - or if no data was uploaded to the Keypad.
88 Keypad data not compatible X Occurs when copying from Keypad if data are moved between fre-
quency converters with major differences in software versions.
89 Parameter read only X Occurs when trying to write to a read-only parameter.
90 Parameter database busy X Keypad and RS485 connection are trying to update parameters si-
multaneously.
91 Parameter value is not valid in this
mode
X Occurs when trying to write an illegal value to a parameter.
92 Parameter value exceeds the
min/max limits
X Occurs when trying to set a value outside the range.
nw
run
Not While RUNning X Parameter can only be changed when the motor is stopped.
Err. A wrong password was entered X Occurs when using a wrong password for changing a password-
protected parameter.
1)
These faults may be caused by mains distortions. Installing GE Line Filter may rectify this problem.
Table 1.5: Warnings and AlarmsCode list
AF-60 LPറMicro Drive
DEH-41264A
15
1

1.1.18 Mains Supply 1 x 200 - 240 VAC
Normal overload 150% for 1 minute
Frequency converter
Typical Shaft Output [kW] 0.18 0.37 0.75 1.5 2.2
Typical Shaft Output [HP] 0.25 0.5 1 2 3
IP 20
Unit Size
M1
Unit Size
M1
Unit Size
M1
Unit Size
M2
Unit Size
M3
Output current
Continuous (1 x 200-240 V ) [A] 1.2 2.2 4.2 6.8 9.6
Intermittent (1 x 200-240 V ) [A] 1.8 3.3 6.3 10.2 14.4
Max. cable size:
(mains, motor) [mm
2
/AWG] 4/10
Max. input current
Continuous (1 x 200-240 V ) [A] 3.3 6.1 11.6 18.7 26.4
Intermittent (1 x 200-240 V ) [A] 4.5 8.3 15.6 26.4 37.0
Max. mains fuses [A] See Section Fuses
Environment
Estimated power loss [W], Best case/
Typical
1)
12.5/
15.5
20.0/
25.0
36.5/
44.0
61.0/
67.0
81.0/
85.1
Weight enclosure IP20 [kg] 1.1 1.1 1.1 1.6 3.0
Efficiency [%], Best case/Typical
1)
95.6/
94.5
96.5/
95.6
96.6/
96.0
97.0/
96.7
96.9/
97.1
Table 1.6: Mains supply 1 x 200 - 240 VAC
1. At rated load conditions.
1.1.19 Mains Supply 3 x 200 - 240 VAC
Normal overload 150% for 1 minute
Frequency converter
Typical Shaft Output [kW] 0.25 0.37 0.75 1.5 2.2 3.7
Typical Shaft Output [HP] 0.33 0.5 1 2 3 5
IP 20
Unit Size
M1
Unit Size
M1
Unit Size
M1
Unit Size
M2
Unit Size
M3
Unit Size
M3
Output current
Continuous (3 x 200-240 V ) [A] 1.5 2.2 4.2 6.8 9.6 15.2
Intermittent (3 x 200-240 V ) [A] 2.3 3.3 6.3 10.2 14.4 22.8
Max. cable size:
(mains, motor) [mm
2
/AWG] 4/10
Max. input current
Continuous (3 x 200-240 V ) [A] 2.4 3.5 6.7 10.9 15.4 24.3
Intermittent (3 x 200-240 V ) [A] 3.2 4.6 8.3 14.4 23.4 35.3
Max.mains fuses [A] See Section Fuses
Environment
Estimated power loss [W], Best case/
Typical
1)
14.0/
20.0
19.0/
24.0
31.5/
39.5
51.0/
57.0
72.0/
77.1
115.0/
122.8
Weight enclosure IP20 [kg] 1.1 1.1 1.1 1.6 3.0 3.0
Efficiency [%], Best case/Typical
1)
96.4/
94.9
96.7/
95.8
97.1/
96.3
97.4/
97.2
97.2/
97.4
97.3/
97.4
Table 1.7: Mains supply 3 x 200 - 240 VAC
1. At rated load conditions.
AF-60 LPറMicro Drive
16
DEH-41264A
1

1.1.20 Mains Supply 3 x 380 - 480 VAC
Normal overload 150% for 1 minute
Frequency converter
Typical Shaft Output [kW] 0.37 0.75 1.5 2.2 3.0 4.0
Typical Shaft Output [HP] 0.5 1 2 3 4 5
IP 20
Unit Size
M1
Unit Size
M1
Unit Size
M2
Unit Size
M2
Unit Size
M3
Unit Size
M3
Output current
Continuous (3 x 380-440 V) [A] 1.2 2.2 3.7 5.3 7.2 9.0
Intermittent (3 x 380-440 V) [A] 1.8 3.3 5.6 8.0 10.8 13.7
Continuous (3 x 440-480 V) [A] 1.1 2.1 3.4 4.8 6.3 8.2
Intermittent (3 x 440-480 V) [A] 1.7 3.2 5.1 7.2 9.5 12.3
Max. cable size:
(mains, motor) [mm2/ AWG] 4/10
Max. input current
Continuous (3 x 380-440 V ) [A] 1.9 3.5 5.9 8.5 11.5 14.4
Intermittent (3 x 380-440 V ) [A] 2.6 4.7 8.7 12.6 16.8 20.2
Continuous (3 x 440-480 V ) [A] 1.7 3.0 5.1 7.3 9.9 12.4
Intermittent (3 x 440-480 V ) [A] 2.3 4.0 7.5 10.8 14.4 17.5
Max. mains fuses [A] See Section Fuses
Environment
Estimated power loss [W], Best case/
Typical1)
18.5/
25.5
28.5/
43.5
41.5/
56.5
57.5/
81.5
75.0/
101.6
98.5/
133.5
Weight enclosure IP20 [kg] 1.1 1.1 1.6 1.6 3.0 3.0
Efficiency [%], Best case/
Typical1)
96.8/
95.5
97.4/
96.0
98.0/
97.2
97.9/
97.1
98.0/
97.2
98.0/
97.3
Table 1.8: Mains supply 3 x 380 - 480 VAC
1. At rated load conditions.
Normal overload 150% for 1 minute
Frequency converter
Typical Shaft Output [kW] 5.5 7.5 11 15 18.5 22
Typical Shaft Output [HP] 7.5 10 15 20 25 30
IP 20
Unit Size
M3
Unit Size
M3
Output current
Continuous (3 x 380-440 V) [A] 12.0 15.5 23.0 31.0 37.0 43.0
Intermittent (3 x 380-440 V) [A] 18.0 23.5 34.5 46.5 55.5 64.5
Continuous (3 x 440-480 V) [A] 11.0 14.0 21.0 27.0 34.0 40.0
Intermittent (3 x 440-480 V) [A] 16.5 21.3 31.5 40.5 51.0 60.0
Max. cable size:
(mains, motor) [mm2/ AWG] 4/10 16/6
Max. input current
Continuous (3 x 380-440 V ) [A] 19.2 24.8 33.0 42.0 34.7 41.2
Intermittent (3 x 380-440 V ) [A] 27.4 36.3 47.5 60.0 49.0 57.6
Continuous (3 x 440-480 V ) [A] 16.6 21.4 29.0 36.0 31.5 37.5
Intermittent (3 x 440-480 V ) [A] 23.6 30.1 41.0 52.0 44.0 53.0
Max. mains fuses [A] See Section Fuses
Environment
Estimated power loss [W], Best case/
Typical1)
131.0/
166.8
175.0/
217.5
290.0/
342.0
387.0/
454.0
395.0/
428.0
467.0/
520.0
Weight enclosure IP20 [kg] 3.0 3.0
Efficiency [%], Best case/
Typical1)
98.0/
97.5
98.0/
97.5
97.8/
97.4
97.7/
97.4
98.1/
98.0
98.1/
97.9
Table 1.9: Mains supply 3 x 380 - 480 VAC
1. At rated load conditions.
AF-60 LPറMicro Drive
DEH-41264A
17
1

Protection and Features:
• Electronic thermal motor protection against overload.
• Temperature monitoring of the heatsink ensures that the frequency converter trips in case of overtemperature
• The frequency converter is protected against short-circuits between motor terminals U, V, W.
• If a motor phase is missing, the frequency trips and issues an alarm.
• If a mains phase is missing, the frequency converter trips or issues a warning (depending on the load).
• Monitoring of the intermediate circuit voltage ensures that the frequency converter trips if the intermediate circuit voltage is too low or too high.
• The frequency converter is protected against earth faults on motor terminals U, V, W.
Mains supply (L1/L, L2, L3/N):
Supply voltage 200-240 V ±10%
Supply voltage 380-480 V ±10%
Supply frequency 50/60 Hz
Max. imbalance temporary between mains phases 3.0 % of rated supply voltage
True Power Factor (ƃ)0.4 nominal at rated load
Displacement Power Factor (cosƎ) near unity (> 0.98)
Switching on input supply L1/L, L2, L3/N (power-ups) maximum 2 times/min.
Environment according to EN60664-1 overvoltage category III/pollution degree 2
The unit is suitable for use on a circuit capable of delivering not more than 100.000 RMS symmetrical Amperes, 240/480 V maximum.
Motor output (U, V, W):
Output voltage 0 - 100% of supply voltage
Output frequency 0-200 Hz (Adv Vector Control), 0-400 Hz (u/f)
Switching on output Unlimited
Ramp times 0.05 - 3600 sec.
Cable lengths and cross sections:
Max. motor cable length, screened/armoured (EMC correct installation) 15 m
Max. motor cable length, unscreened/unarmoured 50 m
Max. cross section to motor, mains*
Connection to load sharing/brake (M1, M2, M3) 6.3 mm insulated Faston Plugs
Max. cross section to load sharing/brake (M4, M5) 16 mm2/6AWG
Maximum cross section to control terminals, rigid wire 1.5 mm2/16 AWG (2 x 0.75 mm2)
Maximum cross section to control terminals, flexible cable 1 mm2/18 AWG
Maximum cross section to control terminals, cable with enclosed core 0.5 mm2/20 AWG
Minimum cross section to control terminals 0.25 mm2
* See tables for mains supply for more information!
Digital inputs (Pulse/enocder inputs):
Programmable digital inputs (Pulse/encoder) 5 (1)
Terminal number 18, 19, 27, 29, 33,
Logic PNP or NPN
Voltage level 0 - 24 V DC
Voltage level, logic'0' PNP < 5 V DC
Voltage level, logic'1' PNP > 10 V DC
Voltage level, logic '0' NPN > 19 V DC
Voltage level, logic '1' NPN < 14 V DC
Maximum voltage on input 28 V DC
Input resistance, Riapprox. 4 k
Max. pulse frequency at terminal 33 5000 Hz
Min. pulse frequency at terminal 33 20 Hz
Analog inputs:
Number of analog inputs 2
Terminal number 53, 60
Voltage mode (Terminal 53) Switch S200=OFF(U)
Current mode (Terminal 53 and 60) Switch S200=ON(I)
Voltage level 0 -10 V
Input resistance, Riapprox. 10 k
AF-60 LPറMicro Drive
18
DEH-41264A
1

Max. voltage 20 V
Current level 0/4 to 20 mA (scaleable)
Input resistance, Riapprox. 200
Max. current 30 mA
Analog output:
Number of programmable analog outputs 1
Terminal number 42
Current range at analog output 0/4 - 20 mA
Max. load to common at analog output 500 ű
Max. voltage at analog output 17 V
Accuracy on analog output Max. error: 0.8 % of full scale
Resolution on analog output 8 bit
Control card, RS-485 serial communication:
Terminal number 68 (P,TX+, RX+), 69 (N,TX-, RX-)
Terminal number 61 Common for terminals 68 and 69
Control card, 24 V DC output:
Terminal number 12
Max. load (M1 and M2) 160 mA
Max. load (M3) 30 mA
Max. load (M4 and M5) 200 mA
Relay output:
Programmable relay output 1
Relay 01 Terminal number 01-03 (break), 01-02(make)
Max. terminal load (AC-1)1) on 01-02 (NO) (Resistive load) 250 V AC, 2 A
Max. terminal load (AC-15)1) on 01-02 (NO) (Inductive load @ cosƎ0.4) 250 V AC, 0.2 A
Max. terminal load (DC-1)1) on 01-02 (NO) (Resistive load) 30 V DC, 2 A
Max. terminal load (DC-13)1) on 01-02 (NO) (Inductive load) 24 V DC, 0.1A
Max. terminal load (AC-1)1) on 01-03 (NC) (Resistive load) 250 V AC, 2 A
Max. terminal load (AC-15)1) on 01-03 (NC) (Inductive load @ cosƎ0.4) 250 V AC, 0.2A
Max. terminal load (DC-1)1) on 01-03 (NC) (Resistive load) 30 V DC, 2 A
Min. terminal load on 01-03 (NC), 01-02 (NO) 24 V DC 10 mA, 24 V AC 20 mA
Environment according to EN 60664-1 overvoltage category III/pollution degree 2
1) IEC 60947 part 4 and 5
Control card, 10 V DC output:
Terminal number 50
Output voltage 10.5 V ±0.5 V
Max. load 25 mA
NB!
All inputs, outputs, circuits, DC supplies and relay contacts are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
AF-60 LPറMicro Drive
DEH-41264A
19
1
Other manuals for AF-60 LP
1
Table of contents
Languages:
Other GE Controllers manuals

GE
GE EV100 LX User manual

GE
GE D.20 RIO Instructions for use

GE
GE PACSystems* RX3i User manual

GE
GE IC3645SR7A353T4 User manual

GE
GE VR-1 Owner's manual

GE
GE IC3645SH7R354D1 User manual

GE
GE KTD-400 User manual

GE
GE PACSystems IC695CPU3104 User manual

GE
GE IC3645SR4R404U2 User manual

GE
GE Logix 764 User manual
Popular Controllers manuals by other brands

Sacher Lasertechnik
Sacher Lasertechnik Pilot PC user manual

STAVIOR
STAVIOR Smart Sterilizer Series user manual

CASTLE
CASTLE EP Description and Operation Manual

Sherwood Scuba
Sherwood Scuba SR1 user manual

Whelen Engineering Company
Whelen Engineering Company 295SHA1 installation guide

Wise Controls
Wise Controls WisePack Simple Instructions