GE SMOR-B GEK 105593C User manual

ÿ
GE Power Management
SMOR-B
Instructions
GEK 105593C
Protection, Monitoring, Analysis,
and Energy Management Numerical
System

GE Power Management
SMOR_B 1000/7000 QUICK REFERENCE GUIDE
Description
User
Limits
COMMON SETTINGS TO ALL TABLES
GeneralSettingsGroup
RELAYSTATUS
In/Outofservice
IDENTIFICACION
20ASCIIcharacters
RATEDVOLTAGE(PH-PH)
90-200
FREQUENCY
50/60Hz
CTPHASERATIO
1-4000
CTGROUDRATIO
1-4000
VTLINERATIO
1-4000
*
VTBUSBARRATIO
1-4000
DEMANDTIME
15/30/60min
PHASEROTATIONSELECTION
ABC/CBA
BreakerSettingsGroup
BREAKERNUMBER
4ASCIIcharacters
FAILTOOPENTIME
0.05
-1
sg
.
FAILTOCLOSETIME
0.05
-5
sg
.
ACCUMULABLEI2tLIMIT
1-999999kA
2
s
INTG.
I2t TIMESELECTOR
Fixed/Measured
I2tINTEGRATIONTIME
0.03
-0.25
sg
.
MAXIMUMTRIPSIN1HOUR
1-50
ActiveTableSettingsGroup
#OFACTIVESETTINGSTABLE
1-3
COLDPICK-UPPERMISSION
No/Yes
CHANGETOTABLE3TIME
Max.
Reclosetime/240
sg.
RETURNFROMTABLE3TIME
SafetyTime/1800
sg.
OscillographyMaskSettingsGroup
NUMBEROFPRE-FAULTCYCLES
2-10
PICK-UP51PT
Enabled/Disabled
PICK-UP51NT
Enabled/Disabled
PICK-UP50
PH
Enabled/Disabled
PICK-UP50PL
Enabled/Disabled
PICK-UP50NH
Enabled/Disabled
PICK-UP50NL
Enabled/Disabled
PICK-UP46PT
Enabled/Disabled
PICK-UP810
Enabled/Disabled
PICK-UP81U
Enabled/Disabled
PICK-UP27P
Enabled/Disabled
PICK-UP59P
Enabled/Disabled
PICK-UP59NH
Enabled/Disabled
PICK-UP59NL
Enabled/Disabled
EXTERNALTRIGGER
Enabled/Disabled
COMUNICATIONSTRIGGER
Enabled/Disabled
TRIP51PT
Enabled/Disabled
TRIP 51 NT
Enabled/Disabled
TRIP 50
PH
Enabled/Disabled
TRIP 50 PL
Enabled/Disabled
TRIP 50 NH
Enabled/Disabled
TRIP 50 NL
Enabled/Disabled
TRIP 46 PT
Enabled/Disabled
TRIP 81 0
Enabled/Disabled
TRIP 81 U
Enabled/Disabled
TRIP 27 P
Enabled/Disabled
TRIP 59 P
Enabled/Disabled
TRIP 59 NH
Enabled/Disabled
TRIP 59 NL
Enabled/Disabled
Function Permission Settings Group
51 PT FUNCTION PERMISSION
Not allowed/Allowed
51 NT FUNCTION PERMISSION
Not allowed/Allowed
50
PH FUNCTION PERMISSION
Not allowed/Allowed
50 PL FUNCTION PERMISSION
Not allowed/Allowed
50 NH FUNCTION PERMISSION
Not allowed/Allowed
* Disregard for SMOR7000
Description
User
Limits
50 NL FUNCTION PERMISSION
Not allowed/Allowed
46 PT FUNCTION PERMISSION
Not allowed/Allowed
81 O FUNCTION PERMISSION
Not allowed/Allowed
81 U FUNCTION PERMISSION
Not allowed/Allowed
27 P FUNCTION PERMISSION
Not allowed/Allowed
59 P FUNCTION PERMISSION
Not allowed/Allowed
59 NH FUNCTION PERMISSION
Not allowed/Allowed
59 NL FUNCTION PERMISSION
Not allowed/Allowed
51 PT TRIP PERMISSION
Enabled/Disabled
51 NT TRIP PERMISSION
Enabled/Disabled
50
PH TRIP PERMISSION
Enabled/Disabled
50 PL TRIP PERMISSION
Enabled/Disabled
50 NL TRIP PERMISSION
Enabled/Disabled
50 NH TRIP PERMISSION
Enabled/Disabled
46 PT TRIP PERMISSION
Enabled/Disabled
81 O TRIP PERMISSION
Enabled/Disabled
81 U TRIP PERMISSION
Enabled/Disabled
27 P TRIP PERMISSION
Enabled/Disabled
59 P TRIP PERMISSION
Enabled/Disabled
59 NH TRIP PERMISSION
Enabled/Disabled
59 NL TRIP PERMISSION
Enabled/Disabled
INDEPENDENT SETTINGS FOR EACH TABLE
51 PT Function Settings Group
51 / 67 P PICK-UP
1.00-12.00 A
CURVE
Inv./M Inv./E Inv./
Def. Time
TIME DIAL
0.05-1.00
DEFINITE TIME SETTING
0.00-100.00
sg
51 NT Function Settings Group
51 / 67 N PICK-UP
0.20-2.40 A
CURVE
Inv./M Inv./E Inv./
Def. Time
TIME DIAL
0.05-1.00
DEFINITE TIME SETTING
0.00-100.00
sg
50 PH Function Settings Group
50 / 67 P PICK-UP
1.00-160.00 A
TIME DELAY
0.00-60.00
sg
50 PL Function Settings Group
50 / 67 P PICK-UP
1.00-160.00 A
TIME DELAY
0.00-60.00
sg
50 NH Function Settings Group
50 / 67 N PICK-UP
0.20-32.00 A
TIME DELAY
0.00-60.00
sg
50 NL Function Settings Group
50 / 67 N PICK-UP
0.20-32.00 A
TIME DELAY
0.00-60.00
sg
46 PT Function Settings Group
51 / 67 N PICK-UP
0.10-4.00 A
CURVE
Inv./M Inv./E Inv./
Def. Time
TIME DIAL
0.05-1.00
DEFINITE TIME SETTING
0.00-100.00
sg
81 Function Settings Group
81 U PICK-UP
40.00-70.00 Hz
UNDERFREQUENCY TIME DELAY
0.00-100.00
sg
81 O PICK-UP
40.00-70.00 Hz
OVERFREQUENCY TIME DELAY
0.00-100.00
sg
UNDERVOLTAGE SUPERVISION
40-110 %
Voltage Settings Group
UNDERVOLTAGE PICK-UP (27 P)
10.00-260.00 V
27 P TIME DELAY
0.03-100.00
sg
OVERVOLTAGE PICK-UP (59 P)
10.00-260.00 V
59 P TIME DELAY
0.03-100.00
sg
Description
User
Range
OVERVOLTAGE PICK-UP (59 NH)
3.00-100.00 V
59 NH TIME DELAY
0.03-100.00
sg
OVERVOLTAGE PICK-UP (59 NL)
3.00-100.00 V
59 NL TIME DELAY
0.03-100.00
sg
Directionality Settings Group
51 PT DIRECTIONAL
Not allowed/Allowed
51 NT DIRECTIONAL
Not allowed/Allowed
50
PH DIRECTIONAL
Not allowed/Allowed
50 PL DIRECTIONAL
Not allowed/Allowed
50 NH DIRECTIONAL
Not allowed/Allowed
50 NL DIRECTIONAL
Not allowed/Allowed
CHARACTERISTIC ANGLE – PHASE
-90.00º - +90.00º
CHARACTERISTIC ANGLE – GROUND
-90.00º - +90.00º
LOSS VOLTAGE LOGIC
Block/Permission
Recloser Settings Group
RECLOSER PERMISSION
Not allowed/Allowed
NUMBER OF CYCLES
1-4
RESET TIME
0-600
sg
HOLD MODE SELECTION
NO/YES
HOLD MODE TIME
0-100
sg
1
ST
RECLOSE TIME
0.10-100.00
sg
2
ND
RECLOSE TIME
0.10-100.00
sg
3
RD
RECLOSE TIME
0.10-100.00
sg
4
TH
RECLOSE TIME
0.10-100.00
sg
RECLOSE CONDITIONS
0-4
0-No Condition
1-Inhib. Input
*
2-Voltage only on
*
3-Voltage on
busbar
*
4-Voltage on both sides
RECLOSE PERMISSION AFTER 51 PT
Enabled/Disabled
RECLOSE PERMISSION AFTER 51 NT
Enabled/Disabled
RECLOSE PERMISSION AFTER 50
PH
Enabled/Disabled
RECLOSE PERMISSION AFTER 50 PL
Enabled/Disabled
RECLOSE PERMISSION AFTER 50 NH
Enabled/Disabled
RECLOSE PERMISSION AFTER 50 NL
Enabled/Disabled
RECLOSE PERMISSION AFTER 46 PT
Enabled/Disabled
RECLOSE PERMISSION AFTER 81 U
Enabled/Disabled
RECLOSE PERMISSION AFTER 81 O
Enabled/Disabled
RECLOSE PERMISSION AFTER 27 P
Enabled/Disabled
RECLOSE PERMISSION AFTER 59 P
Enabled/Disabled
RECLOSE PERMISSION AFTER 59 NH
Enabled/Disabled
RECLOSE PERMISSION AFTER 59 NL
Enabled/Disabled
RECLOSE PERMISSION WITH AN INPUT
Enabled/Disabled
TRIP PERMISSION 51 PT AFTER 79
Enabled/Disabled
TRIP PERMISSION 51 NT AFTER 79
Enabled/Disabled
TRIP PERMISSION 50
PH AFTER 79
Enabled/Disabled
TRIP PERMISSION 50 PL AFTER 79
Enabled/Disabled
TRIP PERMISSION 50 NH AFTER 79
Enabled/Disabled
TRIP PERMISSION 50 NL AFTER 79
Enabled/Disabled
TRIP PERMISSION 46 PT AFTER 79
Enabled/Disabled
TRIP PERMISSION 81 U AFTER 79
Enabled/Disabled
TRIP PERMISSION 81 O AFTER 79
Enabled/Disabled
TRIP PERMISSION 27 P AFTER 79
Enabled/Disabled
TRIP PERMISSION 59 P AFTER 79
Enabled/Disabled
TRIP PERMISSION 59 NH AFTER 79
Enabled/Disabled
TRIP PERMISSION 59 NL AFTER 79
Enabled/Disabled
NOTE: Pick-up settings correspond to a range C relay:
1 - 12 A Phases
0.2 - 2.4 A Ground

GE Power Management
SMOR_B 1000/7000 QUICK REFERENCE GUIDE
* MODEL LIST
SMOR ___1_2 1 _ _ 00B DESCRIPTION
FAMILY
03xIph + Ig (without voltage functions)
13xIph + Ig + 3xV
43xIph + Ig + 3xV (ungrounded system)
63xIph + Ig + Ig2 + 3xV
73xIph + Ig + 3xV + Vo (dedicated)
COMMUNICATIONS INTERFACE
0RS232
1Plastic F.O. + RS232
2Glass F.O. + RS232
3RS232+RS485
RANGES
** Ranges (see table)
MMI LAGUAGE
MSpanish
DEnglish
EXPANSION
0Without expansion board
1With expansion board
AUXILIARY VOLTAGE
A48Vdc
H110 / 250 Vdc
* RANGES
MODELS A B CDEFG H
1/7 Phase 1-12 0.2-2.4 1-12 1-12 1-12 0.5-6 0.5-6 2-16
Ground 1-12 0.2-2.4 0.2-2.4 0.5-6 0.1-1.2 0.2-2.4 0.1-1.2 0.2-2.4
4 Phase 0.2-2.4 1-12
Ground 0.005-0.1 0.005-0.1
6 Phase 1-12 1-12
Ground 0.2-2.4 0.2-2.4
Ground 2 0.025-0.3 0.5-6
* INPUTS / OUTPUTS
- Without expansion board:
•6 digital inputs (two groups of 3 inputs with one common in each group).
•2 groups of 4 configurable outputs with one common in each group.
•2 trip contacts.
•2 close contacts.
•1 alarm contact
- With expansion board:
•12 digital inputs (4 groups of 3 inputs with one common in each group).
•2 groups of 4 configurable outputs with one common in each group.
•4 configurable outputs electrically isolated.
•2 trip contacts.
•2 close contacts.
•1 alarm contact.
•2 coil supervision circuits.
* COEFFICIENTS FOR INVERSE CURVES
−
=1
α
MK
TDtime
CURVE Kα
Inverse 0.13 0.02
Very Inverse 16 1
Extremely Inverse 96 2
* DEFAULT LEDSCONFIGURATION (STANDARD MODEL)
LED CONFIGURATION NMEMONIC MEMORY MODE
1Phase A Trip φΑ TRIP YES FIXED
2Phase B Trip φB TRIP YES FIXED
3Phase C Trip φC TRIP YES FIXED
4Ground Trip GRN TRIP YES FIXED
5Function 51/67 Trip 51/67 TRIP YES FIXED
6Function 50/67 Trip 50/67 TRIP YES FIXED
7Function 46 PT Trip 46 TRIP YES FIXED
8Voltage Functions Trip 27/59/59N TRIP YES FIXED
9Frequency Functions Trip 81 TRIP YES FIXED
10 Recloser Out of Service 79 OUT OF SERVICE NO FIXED
11 Reclose in progress 79 IN PROGRESS NO FIXED
12 Recloser LockOut 79 LOCKOUT NO FIXED
13 52 Open 52 OPEN NO FIXED
14 Coil Supervision Alarm COIL SUPERV. NO FIXED
15 Critical Alarm CRITICAL ALARM NO FIXED
16 Remote Mode REMOTE MODE NO BLINK.
* DEFAULT INPUTSCONFIGURATION (STANDARDMODEL)
INPUT CONFIGURATION CONTACT COMMON
CC1 Breaker input 52/b C9 D10
CC2 Recloser Block D9 D10
CC3 Recloser UnBlock C10 D10
CC4 50 P Block C11 D12
CC5 50 N Block D11 D12
CC6 Recloser Inhibit C12 D12
CC7 Reclose Initiate E9 F10
CC8 Phase Directional Blocking F9 F10
CC9 Ground Directional Blocking E10 F10
CC10 Oscillography Trigger E11 F12
CC11 Active Table Select 0 F11 F12
CC12 Active Table Select 1 E12 F12
* CONFIGURABLEINPUTSOPTIONS:
• Recloser Block (L) • Recloser Block (P)
• Recloser Unblock (P) •Reclose Initiate (P)
•Reclose Inhibition (L) • Oscillography External Trigger (P)
• PT Secondary MCB Tripping (L) • Fail To Open Pickup (P)
• Active Table Select 0 (L) • Active Table Select 1 (L)
• Open Command (P) • Close Command (P)
• Phase Directional Blocking (L) • Ground Directional Blocking (L)
• Phase Instantaneous Blocking (L) • Ground Instantaneous Blocking (L)
• Phase Units Blocking (L) • Ground Units Blocking (L)
• Voltage Uniis Blocking (L) • 81U/81O Units Blocking (L)
• 46 PT Unit Blocking (L) • General Blocking (L)
NOTE: (L) indicates Level input.
(P)indicates Pulse input.
* DEFAULT OUTPUTSCONFIGURATION(STANDARD MODEL)
OUTPUT CONFIGURATION CONTACT COMMON
S1 51/67 P Pick-Up C4 C6
S2 51/67 N Pick-Up D4 C6
S3 46 PT Trip C5 C6
S4 81 Trip D5 C6
S5 27 / 59 Trip C7 D6
S6 Last Trip D7 D6
S7 Reclose In Progress C8 D6
S8 Recloser Out of Service D8 D6
S9 51/67 P Trip E1 F1
S10 50/67 P Trip E2 F2
S11 51/67 N Trip E3 F3
S12 50/67 N Trip E4 F4
* CONFIGURABLEOUTPUTSOPTIONS:
Program Initiates 81O Pickup 51 Phase A Trip Trips not allowed
Settings Change 27P Pickup 51 Phase B Trip I with 52 open
Write Counters 59P Pickup 51 Phase C Trip 52 maintenance Al.
Cnfg. Change 59NH Pickup 50H Phase A Trip Coil 1 Cont. Failure
External Trigger 59NL Pickup 50H Phase B Trip Coil 1 DCsupply Fail.
Communic. Trigger 50H Phase C Trip Coil 2 Cont. Failure
50L Phase A Trip Coil 2 DC supply Fail.
50L Phase B Trip Closed Trip
Contacts
Reclose Command 51 Phase A Pickup 50L Phase C Trip Active Table 1
79 Block Command. 51 Phase B Pickup 27P AB Trip Active Table 2
79 Unblock Comma. 51 Phase C Pickup 27P BC Trip Active Table 3
Open Command 50H Phase A Pickup 27P CA Trip
Close Command 50H Phase B Pickup 59P AB Trip
50H Phase C Pickup 59P BC Trip New Events
50L Phase A Pickup 59P CA Trip
50L Phase B Pickup 52 Status
Activation Input 1 50L Phase C Pickup 79 Out of Service
Activation Input 2 27P AB Pickup Reclose in progress 52 Failed to Open
Activation Input 3 27P BC Pickup Reclose initiate 52 Failed to Close
Activation Input 4 27P CA Pickup Ext. Reclose Initiate. Directional A
Activation Input 5 59P AB Pickup Reclose Inhibit. Directional B
Activation Input 6 59P BC Pickup Directional C
59P CA Pickup Last Trip Directional N
79 Ready
Activation Input 7 51 PT Trip Lockout: Fail to open AND 1
Activation Input 8 51 NT Trip Lockout: Repet. Trip AND 2
Activation Input 9 50 PH Trip Lockout: No cond. AND 3
Activation Input 10 50 PL Trip Lockout: Faulty 79 AND 4
Activation Input 11 50 NH Trip Global Lockout AND 5
Activation Input 12 50 NL Trip AND 6
46 PT Trip AND 7
81 U Trip Recloser Block AND 8
51PT Pickup 81 O Trip AND 9
51NT Pickup 27 P Trip Parallel E2PROM Al. AND 10
50PH Pickup 59 P Trip Serial E2PROM Al. AND 11
50PL Pickup 59 NH Trip In/Out of Service AND 12
50NH Pickup 59 NL Trip Default general
Sett. AND 13
50NL Pickup Default Table 1 Sett. AND 14
46PT Pickup Default Table 2 Sett. AND 15
81U Pickup Default Table 3 Sett. AND 16
NOTE: By using the INF key on the MMI you can see the status of the shadowed signals.
Measurements and communication estates are also available.
* CONFIGURATION SETTINGS (7169)
SETTING RANGE DEFAULT
REMOTE PORT BAUD RATE 1200-115200 bauds 19200 bauds
REMOTE – STOP BITS 1-2 1
LOCAL PORT BAUD RATE 1200-19200 bauds 19200 bauds
LOCAL – STOP BITS 1-2 1
LOCAL SETTINGS No Per/Per Per
REMOTE SETTINGS No Per/Per Per
LOCAL OPERATIONS No Per/Per Per
REMOTE OPERATIONS No Per/Per Per
UNIT NUMBER 1 – 255 1
PASSWORD 0-99999 1
t TIMEOUT 0-86400 0
* SMOR_B SOFTWARE
GE_INTRO: RelayConfiguration .
GE_LOCAL: Settings, Events, Status.
GE_OSC: Oscillography analysis.
* COMMUNICATIONS
SMOR_B PC DB 9 MODEM
3 2 3
2 3 2
1 4 4*
5 5 5
* Join 6 and 7 points too.

*(3RZHU0DQDJHPHQW
$Q\WKLQJ\RXFDQ·WILQG"
$Q\WKLQJQRWFOHDUHQRXJK"
,) <28 +$9( $1< &200(17 21 7+( &217(176 2) 7+(
35(6(17 0$18$/ .,1'/< )$; 86 $ &23< 2) 7+,6 3$*(
72*(7+(5 :,7+ $ &23< 2) 7+( 3$*( :+(5( <28 +$9(
)281' 7+( 352%/(0 72 7+( )$; 180%(5
),//,1*,17+(48(67,21$,5(%(/2::(:,//%(+$33<72
62/9( <285 '28%76 $1' :( 7+$1. <28 )25 +(/3,1* 86
,03529(7+,60$18$/
&RPSDQ\
1DPH
$GGUHVV
3KRQH
)D[
(PDLO
'HVFULSWLRQRI\RXUTXHVWLRQRUVXJJHVWLRQ
0DQXDO*(.FRGH


GEK-105593C
1
TABLE OF CONTENTS
TABLE OF CONTENTSTABLE OF CONTENTS
TABLE OF CONTENTS
1. GENERAL DESCRIPTION AND APPLICATION ........................................................................................ 5
1.1. GENERAL DESCRIPTION................................................................................................................................. 5
2. OPERATING PRINCIPLES.......................................................................................................................... 7
2.1. PROTECTION FUNCTIONS............................................................................................................................... 7
2.1.1. Overcurrent Units ................................................................................................................................. 7
2.1.2. Directional Supervision Setting ............................................................................................................ 7
2.1.3. Voltage Units........................................................................................................................................ 8
2.1.4. Frequency Units. .................................................................................................................................. 8
2.2. MONITORING AND REGISTERING FUNCTIONS. ................................................................................................. 9
2.2.1. Measurement....................................................................................................................................... 9
2.2.2. Associated Breaker Status................................................................................................................... 9
2.2.3. LED Indicators...................................................................................................................................... 9
2.2.4. Supervision of Trip and Closing Circuits ............................................................................................ 10
2.2.5. Breaker Health Monitoring.................................................................................................................. 11
2.2.6. Phase Rotation Sequence Selection.................................................................................................. 12
2.2.7. Self-checking functions. ..................................................................................................................... 12
2.3. ANALYSIS FUNCTIONS. ................................................................................................................................ 13
2.3.1. Event Recorder................................................................................................................................... 13
2.3.2. Oscillography Register ....................................................................................................................... 15
2.4. CONTROL.................................................................................................................................................... 17
2.4.1. Associated Breaker Command.......................................................................................................... 17
2.4.2. Operation Failure Detection ............................................................................................................... 17
2.4.3. Recloser ............................................................................................................................................. 18
2.4.4. Tables of Settings............................................................................................................................... 21
2.4.5. Cold Load Pick-up.............................................................................................................................. 21
2.4.6. Time Synchronization......................................................................................................................... 22
2.4.7. Configurable Inputs and 0utputs ........................................................................................................ 22
2.4.7.1. Digital Inputs................................................................................................................................ 22
2.4.7.2. Outputs ........................................................................................................................................ 23
2.5. MAN-MACHINE INTERFACE (MMI)................................................................................................................. 24
2.6. REMOTE COMMUNICATIONS......................................................................................................................... 24
3. SETTINGS .................................................................................................................................................. 29
4. TECHNICAL CHARACTERISTICS............................................................................................................ 39
4.1. MODEL LIST................................................................................................................................................ 39
4.2. TECHNICAL CHARACTERISTICS.................................................................................................................... 40
5. HARDWARE DESCRIPTION..................................................................................................................... 43
5.1. PHYSICAL DESCRIPTION .............................................................................................................................. 43
5.1.1. Case ................................................................................................................................................... 43
5.1.2. Electrical Connections........................................................................................................................ 43
5.1.3. Internal Construction .......................................................................................................................... 43
5.2. OPERATING THEORY ................................................................................................................................... 44
5.2.1. Magnetic Module................................................................................................................................ 44
5.2.2. CPU Board ......................................................................................................................................... 44
5.2.3. Power Supply ..................................................................................................................................... 45
5.2.4. Keyboard and Display ........................................................................................................................ 45
6. ACCEPTANCE TESTS .............................................................................................................................. 47
6.1. CONNECTIONS AND NECESSARY EQUIPMENT................................................................................................ 47
6.2. VISUAL INSPECTION..................................................................................................................................... 48
6.3. INSULATION TESTS...................................................................................................................................... 48
6.4. INDICATORS ............................................................................................................................................... 49
6.5. POWER SUPPLY.......................................................................................................................................... 49
6.6. COMMUNICATIONS....................................................................................................................................... 50

GEK-105593C
2
6.7. RELAY SETTING .......................................................................................................................................... 50
6.8. INPUTS ....................................................................................................................................................... 50
6.8.1. Digital Inputs....................................................................................................................................... 50
6.8.2. Synchronization Input IRIG-B............................................................................................................. 50
6.9. OUTPUTS.................................................................................................................................................... 50
6.10. CHECKING RELAY MEASUREMENTS............................................................................................................ 51
6.10.1. Current and Voltage Measurement.................................................................................................. 51
6.10.2. Frequency Measurement ................................................................................................................. 52
6.11. RECLOSER................................................................................................................................................ 52
6.11.1. Checking Recloser Cycle ................................................................................................................. 53
6.11.2. Checking the Recloser Block ........................................................................................................... 53
6.11.3. Checking Recloser Inhibition............................................................................................................ 53
6.11.4. Checking Reclose Initiation.............................................................................................................. 53
6.12. INSTANTANEOUS PHASE OVERCURRENT UNIT,HIGH LEVEL (50PH)............................................................ 53
6.13. INSTANTANEOUS PHASE OVERCURRENT UNIT,LOW LEVEL (50PL).............................................................. 53
6.14. INSTANTANEOUS GROUND OVERCURRENT UNIT,HIGH LEVEL (50NH)......................................................... 54
6.15. INSTANTANEOUS GROUND OVERCURRENT UNIT,LOW LEVEL (50NL)......................................................... 54
6.16. PHASE TIME OVERCURRENT UNIT (51PT)................................................................................................. 54
6.17. GROUND TIME OVERCURRENT UNIT (51NT)............................................................................................... 55
6.18. PHASE DIRECTIONAL UNIT (67PL) ............................................................................................................. 56
6.19. GROUND DIRECTIONAL UNIT (67NL).......................................................................................................... 57
6.20. UNDERFREQUENCY UNIT (81U) ................................................................................................................. 58
6.21. OVERFREQUENCY UNIT (81O)................................................................................................................... 58
6.22. UNDERVOLTAGE UNIT (27) ........................................................................................................................ 59
6.23. OVERVOLTAGE UNIT (59) .......................................................................................................................... 59
6.24. ZERO SEQUENCE OVERVOLTAGE UNIT,HIGH LEVEL (59 NH) ..................................................................... 59
6.25. ZERO SEQUENCE OVERVOLTAGE UNIT,LOW LEVEL (59 NL)....................................................................... 60
6.26. BREAKER MAINTENANCE ........................................................................................................................... 60
6.27. COMMANDS............................................................................................................................................... 61
6.28. PHASE ROTATION ABC - CBA................................................................................................................... 61
6.29. MONITORING TRIP CIRCUITS : UNDERVOLTAGE ..................................................................................... 61
6.30. MONITORING TRIP CIRCUITS : COIL FAILURE........................................................................................... 62
7. INSTALLATION AND MAINTENANCE..................................................................................................... 67
7.1. INSTALLATION ............................................................................................................................................. 67
7.2. CONNECTION TO GROUND AND SUPPRESSION OF DISTURBANCES................................................................. 67
7.3. MAINTENANCE............................................................................................................................................. 67
8. KEYBOARD AND DISPLAY...................................................................................................................... 69
8.1. MENU TREE................................................................................................................................................ 70
8.2. SETTINGS GROUP ....................................................................................................................................... 72
8.3. INFORMATION GROUP.................................................................................................................................. 78
8.4. OPERATIONS GROUP................................................................................................................................... 80
8.5. SINGLE KEY OPERATION.............................................................................................................................. 81
8.6. CONFIGURATION MENU. .............................................................................................................................. 82

GEK-105593C
3
LIST OF FIGURES
LIST OF FIGURESLIST OF FIGURES
LIST OF FIGURES
Figure 1. Panel drilling dimensions for 19’’ rack models........................................................................84
Figure 2. Panel drilling dimensions for 1/2 rack models........................................................................85
Figure 3. INVERSE Characteristic Operating Curve .............................................................................86
Figure 4. VERY INVERSE Characteristic Operating Curve...................................................................87
Figure 5. EXTREMELY INVERSE Characteristic Operating Curve ......................................................88
Figure 6. Recloser Program Flowchart..................................................................................................89
Figure 7. Front View for 19’’ rack models ..............................................................................................90
Figure 8. Front View for 1/2 rack models...............................................................................................91
Figure 9. External Connections for 19’’ rack models.............................................................................92
Figure 10. External Connections for 1/2 rack models............................................................................93
Figure 11. Connection to computer (with PC)........................................................................................94
Figure 12. Connection to computer (with MODEM)...............................................................................94
Figure 13. Rear View for 19’’ rack models ............................................................................................95
Figure 14. Rear View for 1/2 rack models .............................................................................................96
Figure 15. Dimensions diagram for 19’’ rack models.............................................................................97
Figure 16. Dimensions diagram for 1/2 rack models.............................................................................98

GEK-105593C
4

GEK-105593C
5
1.
1.1.
1. GENERAL DESCRIPTION AND
GENERAL DESCRIPTION ANDGENERAL DESCRIPTION AND
GENERAL DESCRIPTION AND
APP
APPAPP
APPLICATION
LICATIONLICATION
LICATION
1.1. GENERAL DESCRIPTION
The SMOR system is a microprocessor based multifunction protection, control and measurement unit. The
SMOR uses a set of algorithms to create a general purpose protection and monitoring unit for power
systems.
The SMOR system is supplied in a 19’’ rack case 2 units high. Figure 1 shows a diagram for panel drilling
installation.
All the information and settings of the unit are accessible by means of a computer connected to the serial
port (RS232 or fiber-optic) or using the man-machine interface (MMI), which includes a 20 character keypad
and a two line liquid crystal display (LCD) with 16 character on each line, located on the front of the relay.
This protection system includes the following functions:
a) Protection:
• 6 overcurrent units arranged in the following way:
- 3 phase units:
- 51PT, Instantaneous, Inverse or definite time.
- 50PH, Instantaneous or definite time.
- 50PL, Instantaneous or definite time.
- 3 ground units:
- 51NT, Instantaneous, Inverse or definite time.
- 50NH, Instantaneous or definite time.
- 50NL, Instantaneous or definite time.
• Independent directional supervision adjustment for each overcurrent functions.
• Negative sequence overcurrent
• Three-phase over and undervoltage
• Ground overvoltage (2 levels). NOTE: Only for the SMOR7000 model an open delta input is available.
• Over and under frequency
b) Monitoring and Register
• Current measurement for each phase and ground.
• Negative sequence current measurement.
• Measurement of line to line voltages.
• Measurement of active and reactive power along with power factor.
• Frequency measurement.
• Breaker status.
• LED indicators - 17 LED display (16 of which can be configured by the user).
• Breaker supervision for failure-to-open or failure-to-close (optional, mounted in the additional board).
• Breaker health monitoring (ΣI2t) per phase.
• Phase rotation sequence selection (ABC or CBA).
• Maximeter for current and active power.
• Built in self-checking unit.

GEK-105593C
6
c) Analysis:
•Load profile recorder.
•Event recorder.
•Oscillography recorder.
d) Control:
• Command of associated breaker.
• Operation failure detection (opening or closing).
• Automatic recloser that can be programmed for up to 4 shots.
• 3 setting tables.
• Coldloadpickuplogic.
• IRIG-B time synchronization.
• Configurable inputs and outputs.
• Internal logic that can be configured by the user (based on AND, NOT, OR gates).
e) Communication Interfaces
• Three communication ports, one on the front of the relay and two located on the rear.
• Man machine interface (MMI) consisting of a keyboard (20 key) and an alphanumerical display (2 lines x
16 char.).
• Windowsbased GE-INTRO configuration software and GE-LOCAL communication software. Both
programs are part of the GE-NESIS (General Electric NEtwork Substation Integrated System).

GEK-105593C
7
2.
2.2.
2. OPERATING PRINCIPLES
OPERATING PRINCIPLESOPERATING PRINCIPLES
OPERATING PRINCIPLES
2.1. PROTECTION FUNCTIONS
2.1.1. OVERCURRENT UNITS
SMOR system includes the following overcurrent units, all of which can be set and used independently:
•Phase overcurrent (for three phases):
Time delayed 51 PT (Instantaneous, definite or inverse time)
Instantaneous, High level 50 PH (Instantaneous or definite time delayed)
Instantaneous, Low level 50 PL (Instantaneous or definite time delayed)
•Ground overcurrent:
Time delayed 51 NT (Instantaneous, definite or inverse time)
Instantaneous, High level 50 NH (Instantaneous or definite time delayed)
Instantaneous, Low level 50 NL (Instantaneous or definite time delayed)
Any unit can be set to be directional or non-directional, independently.
•Negative sequence overcurrent:
Time delayed 46 PT (Instantaneous, definite or inverse time)
The timed units can be selected using Inverse, Very Inverse, Extremely Inverse curves, or definite time
characteristic. These inverse time curves are shown in Figures 2, 3 and 4 and follow the equation:
K
t=TD M
∝-1
in which:
t= Time in seconds
TD = Time Dial of the curve (0.05 for the lower curve of the family and 1 for the upper curve)
M= Multiples of the pickup value
K, αare coefficients which identify the selected curve and which correspond to the following table:
Curve Characteristic K α
αα
α
1 Inverse 0.13 0.02
2 Very inverse 16 1
3 Extremely inverse 96 2
2.1.2. DIRECTIONAL SUPERVISION SETTING
The SMOR system has three phase directional units and one ground directional unit. They are completely
independent on each other, being used to supervise (assuming they are adjusted to do so) the tripping of the
phase and ground overcurrent units, according to the direction of the detected fault (they do not affect the
trip of the negative sequence overcurrent unit). The directional supervision can be adjusted independently for
each of the overcurrent functions of the SMOR system, both for phases and ground.
The phase directional units are polarized by phase-to-phase voltages, while the ground directional unit is
polarized by zero sequence voltage. The characteristic angle of the unit can be independently set for the
phase and ground units.

GEK-105593C
8
To protect against loss of polarization voltage, the system includes adjustable fuse-failure logic. This logic
allows to either block the operation of the units or to convert the directional units into non-directional. The
selection is done through a setting. The fuse failure function operates on two different conditions (OR logic):
- Operation of undervoltage detectors (adjusted at 3.5 volts)
- Activation of a digital input connected to the voltage MCB.
2.1.3. VOLTAGE UNITS
•Phase over and under voltage:
•Under voltage: 27P
•Over voltage: 59P
The three-phase under and overvoltage units operate under conditions of under or over voltage (depending
on the unit) in any of the three phases. Both units are adjusted and operate on phase-to-phase voltage
values, calculated from the phase-to-ground voltages applied to the unit.
• Ground overvoltage:
•High Setting: 59 NH
•Low Setting: 59 NL
There are two ground overvoltage units. The SMOR7000 model has a dedicated open-delta input. In all
other models the voltage is calculated from the phase to ground inputs.
2.1.4. FREQUENCY UNITS
• Underfrequency : 81U
• Overfrequency: 81O
The under and over frequency units are measured on one phase (phase B).

GEK-105593C
9
2.2. MONITORING AND REGISTERING FUNCTIONS.
2.2.1. MEASUREMENT
The SMOR system offers the following metering capabilities:
- Three-phase and ground current.
- Negative sequence current.
- Phase-to-phase voltages.
- Active and reactive power.
- Power factor.
- Frequency.
The RMS value for currents and voltages is calculated for each phase, and the phase-to-phase voltages are
calculated from the phase to ground voltages. The active and reactive power are also computed on these
values. The active and reactive power, and the power factor are only shown as three-phase values.
These measurements can be accessed locally on the liquid crystal display (LCD) on the front of the relay, or
via the GE-LOCAL communication software.
The SMOR unit has a demand register, as well as a maximeter register for current and active power. For the
demand register, the maximum and average RMS current are calculated over a selected period of 15, 30 or
60 minutes corresponding to the last 24, 48 or 96 hours respectively. The maximeter register computes the
maximum value for current and power for periods which are the same as those selected for the demand
register.
2.2.2. ASSOCIATED BREAKER STATUS
SMOR system monitors breaker status associated to the unit with a digital input (52/b). The breaker status
can be accessed using the local MMI or the communication software, which shows the breaker status in real
time through a visual simulation of the line.
2.2.3. LED INDICATORS.
An internal states matrix stores the digital information for all the units (inputs, pick-ups, alarms, etc). The
digital signals on this matrix are grouped in groups of 16 signals; there are 10 groups; It is a 10 x 16 matrix;
the final group corresponds to the 16 AND gates definable using the programmable logic of GE-INTRO
software.
The SMOR unit has a total of 17 LED indicators, one fixed bicolor assigned to the critical alarm function of
the unit and 16 red LED indicators, arranged in two columns of 8 LEDs. They can be configured using the
GE-INTRO configuration software to any of the user definable alarms (32 protection alarms and 16
communication alarms) assigned from among the protection and communication states. To define each
alarm, the user can use 16 inputs OR gates. All the inputs to an OR gate must belong to the same group in
the states matrix. Similarly, each LED can be configured to have memory in the absence of auxiliary power
supply (the status of the LED with memory is registered on the EEPROM memory). They can also be
configured to blink when turned on.
There is a test option for the LEDs, lighting them all up when the TARGET RESET button is pressed. When
this button is held down the LED indicators are reset.
The SMOR units are supplied from the manufacturer with the following default configuration of the LEDs:

GEK-105593C
10
COLUMN
LED Nº LEFT LED
Nº
RIGHT
1 Phase A trip 9 Frequency trip (81)
2 Phase B trip 10 Recloser out of service
3 Phase C trip 11 Reclose in progress
4 Ground trip 12 Recloser in lockout status
5 Timed Overcurrent trip 13 Circuit Breaker Open
6 Instantaneous Overcurrent trip 14 Coil supervision alarm
7 Negative sequence trip 15 Unit alarm
8 Voltage trip (27/59/59N) 16 Remote communication mode
2.2.4. SUPERVISION OF TRIP AND CLOSING CIRCUITS
On the optional expansion board there are two complete supervision circuits for the trip and/or closing coil of
the breaker (one input for each coil). These supervision inputs monitor both the battery voltage and the
continuity of the tripping or closing circuits, monitoring the flow of a small current injected into the circuit.
The unit independently identifies in the event recorder and states matrix the continuity of each coil ("coil
continuity alarm") and the loss of voltage to command the breaker ("coil DC supply alarm.")
Circuit supervision is carried out on a permanent basis, regardless of whether the breaker is in the open or
closed status, since the supervision circuit is connected both to contact 52/a and 52/b of the breaker. For the
supervision to be carried out correctly, the supervision circuits must be connected to the tripping or closing
coils as shown in the following diagrams:
TRIP CIRCUIT SUPERVISION

GEK-105593C
11
CLOSE CIRCUIT SUPERVISION
2.2.5. BREAKER HEALTH MONITORING
To supervise the breaker health, SMOR system calculates and stores, for each operation, the accumulated
values for the square of the current multiplied by the opening time of the breaker (ΣI2t) on each of the three
phases. If the nominal current is not exceeded, as is the case for a manual opening command with no fault
current, the relay uses the nominal current value instead of the measured value.
The value I2t is accumulated and stored independently for each phase. These values can be accessed
either by local MMI or by GE-LOCAL communication software.
The function has an "Integration Time Selector" setting which can be used to assign a fixed opening time
(given by another "Integration Time" setting). Otherwise it allows the unit to measure this time from the
moment the opening command is given until the moment when the breaker opens.
The "Accumulative Current Limit" setting establishes a threshold for the breaker's interruption capability (it is
advisable to set this to the limit supplied by the manufacturer). When this threshold is passed on any of the
three phases, the system gives an alarm. In addition, the system incorporates a counter for the number of
opening operations carried out.
The purpose of this function is to allow maintenance to be carried out in a more accurate method than using
fixed time periods. Once this maintenance operation has been carried out, the values for both the I2t and
number of opening operations, can be reset to zero.
In order to be able to take into account the history of the breaker, in the case where the breakers were
already in use before the installation of the relay, the system allows to set an initial value for the ΣI2tandthe
number of opening operations carried out. Similarly, these values can be adjusted to a given value in order
to take into account the operations carried out during the protection testing.

GEK-105593C
12
2.2.6. PHASE ROTATION SEQUENCE SELECTION
The SMOR system works correctly with any phase sequence selection ABC or CBA without the need to
change the wiring of the external transformers, since there is a setting which allows the selection of the
phase rotation sequence.
2.2.7. SELF-CHECKING FUNCTIONS.
Thanks to its digital technology, the SMOR system incorporates self-checking functions which guarantee the
correct performance of the unit and will block the operation in case of internal errors.
These self monitoring checks are carried out both when the unit is started up and during normal operation.
The checks are carried out on the internal power supply, program memory (ROM), working memory (RAM),
oscillographic memory (RAM) and settings and calibration memory (EEPROM).
In addition there is a hardware test for the LED indicators, which light them all up when the button TARGET
RESET is pressed. If the button is kept pressed down for more than one second the memory for all the
indicators is reset.

GEK-105593C
13
2.3. ANALYSIS FUNCTIONS.
The SMOR system includes an event recorder and an oscillographic recorder with 1 msec. time tag
resolution. So as not to lose the date and time setting or the oscillographic recorder information, the unit uses
a capacitor as backup for the internal clock and register memory. This allows the information to be kept for at
least 24 hours from the moment the power supply is lost.
2.3.1. EVENT RECORDER
The SMOR system keeps a record of the last 144 events and stores the following information: date and time
(1 msec. resolution), the type of event, current and voltages measured at the time the event occurred, and
the internal states matrix of the unit.
This event recorder is stored in a non-volatile memory and can be maintained indefinitely, even with no
power supply.
The relay generates an event when any of the following signals changes its status:
Index State
0.0 Program initiates
0.1 Settings change
0.2 Write counters
0.3 Configuration change
0.4 External trigger
0.5 Communications Trigger
0.6
0.7
1.0 Reclose command
1.1 79 block command
1.2 79 unblock command
1.3 Open command
1.4 Close command
1.5
1.6
1.7
2.0 Activation input 1
2.1 Activation input 2
2.2 Activation input 3
2.3 Activation input 4
2.4 Activation input 5
2.5 Activation input 6
2.6
2.7
3.0 Activation input 7
3.1 Activation input 8
3.2 Activation input 9
3.3 Activation input 10
3.4 Activation input 11
3.5 Activation input 12
3.6
3.7
4.0 51PT Pick-up

GEK-105593C
14
Index State
4.1 51NT Pick-up
4.2 50PH Pick-up
4.3 50PL Pick-up
4.4 50NH Pick-up
4.5 50NL Pick-up
4.6 46PT Pick-up
4.7 81U Pick-up
5.0 81O Pick-up
5.1 27P Pick-up
5.2 59P Pick-up
5.3 59NH Pick-up
5.4 59NL Pick-up
5.5
5.6
5.7
8.0 51PT Trip
8.1 51NT Trip
8.2 50PH Trip
8.3 50PL Trip
8.4 50NH Trip
8.5 50NL Trip
8.6 46PT Trip
8.7 81U Trip
9.0 81O Trip
9.1 27P Trip
9.2 59P Trip
9.3 59NH Trip
9.4 59NL Trip
9.5
9.6
9.7
C.0 79 out of service
C.1
C.2 Reclose initiate
C.3 External reclose initiate
C.4 Reclose inhibit
C.5
C.6 Last trip
C.7 79 Ready
D.0 Lockout: Failed to open
D.1 Lockout:Repetitive tripping
D.2 Lockout:No conditions to reclose
D.3 Lockout:Faulty reclose
D.4 Global Lockout
D.5
D.6
D.7 Recloser block
E.0

GEK-105593C
15
Index State
E.1 Parallel EEPROM alarm
E.2 Serial EEPROM alarm
E.3 Out of service
E.4 Default General settings
E.5 Default Table 1 settings
E.6 Default Table 2 settings
E.7 Default Table 3 settings
F.0
F.1 Tripping not permitted
F.2 Current with open breaker
F.3 52 maintenance alarm
F.4 Coil 1 continuity failure
F.5 Coil 1 DC supply failure
F.6 Coil 2 continuity failure
F.7 Coil 2 DC supply failure
10.0
10.1 Active table 1
10.2 Active table 2
10.3 Active table 3
10.4
10.5
10.6
10.7
11.0 52 Status
11.1
11.2 52 failed to open
11.3 52failedtoclose
11.4 Directional A
11.5 Directional B
11.6 Directional C
11.7 Directional N
2.3.2. OSCILLOGRAPHY REGISTER
The SMOR unit stores 4 oscillography records, with a resolution of 16 samples per cycle. Each register has a
maximum capacity of 66 cycles. The number of pre-fault cycles can be selected from 2 to 10 cycles. Each of
the records includes the following information:
•Instantaneous values for voltage and current inputs (IA,I
B
,I
C
,I
N
,V
A
,V
B
,V
C
,V
busbar)
•Digital information:
- Status of protection functions
- Status of digital inputs.
- Recloser signals
•Date and time.
Table of contents
Other GE Power Supply manuals

GE
GE Digital Energy LP 33 Series User manual

GE
GE Infinity S User manual

GE
GE Digital Energy LP 31 Series Technical specifications

GE
GE Tetra GEPS12-60 User manual

GE
GE GEPS12-25U-NA User manual

GE
GE Tetra GEPS12-25U-EU User manual

GE
GE Tetra GEPS24W-80M Manual

GE
GE KTP-24C User manual

GE
GE SERIES B 480 User manual

GE
GE Tetra GEPS24-300U-GL User manual