
vi
────────────────────────────────────────────────────
Notes on Use
────────────────────────────────────────────────────
DANGER Logic Probe Connection
The logic input and 8841/42 Unit share a common ground. Therefore, if
power is supplied to the measurement object of the logic probe and to
the 8841/42 from different sources, an electric shock or damage to the
equipment may result. Even if power is supplied from the same system,
if the wiring is such that a potential difference is present between the
grounds, current will flow through the logic probe so that the
measurement object and 8841/42 could be damaged. We therefore
recommend the following connection method to avoid this kind of
result. Refer to Section 2.5, "Logic Probe Connection" for details.
(1) Before connecting the logic probe to the measurement object, be sure
that power is supplied from the same outlet box to the measurement
object and the 8841/42 using the supplied power cord.
(2) Before connecting the logic probe to the measurement object,
connect the ground of the measurement object to the 8841/42
ground terminal. Also in this case, power should be supplied from
the same source. Refer to Section 2.2, "Power Supply and Ground
Connections" for grounding terminal details.
Replacing the Input Units
In order to avoid accidents from electric shock, before removing or
replacing an input unit, check that the connector cables and
thermocouple are disconnected, turn off the power, and remove the
power cable.
Normally keep all input units installed permanently. If a unit is not
fitted, it must be replaced by a blanking panel. If the unit is
operated with an input unit not in place it poses a shock hazard.
Differential Probe Connection
When using grabber clips, the 9322's maximum rated voltage to
earth is 1500 VAC/DC; when using alligator clips, it is 1000 VAC/DC.
To avoid electrical shock and possible damage to the unit, never
apply voltages greater than these limits between the input channel
terminals and chassis, or across the inputs of two 9322s.
Maximum input voltage is 1000 VAC/2000 VDC. Do not measure
voltage in excess of these limitations, as doing so may damage the
unit or cause an accident that might result in injury or death.
Input/output terminal Maximum input voltage Maximum rated voltage to earth
9322
2000 VDC, 1000 VAC (CAT II)
600 VAC/DC (CAT III)
When using grabber clips
1500 VAC/DC (CAT II), 600 VAC/DC (CAT III)
When using alligator clips
1000 VAC/DC (CAT II), 600 VAC/DC (CAT III)
EXT TRIG/ START・STOP/
PRINT/ EXT SMPL -5 to +10 VDC
Not insulated
TRIG OUT/ GO/ NG -20 V to +30 VDC
500 mA max./ 200 mW max.