Copyright HK Instruments 2022 www.hkinstruments. Installaon version 7.0 2022
INSTALLATION
INSTRUCTIONS
AIR FLOW AND VELOCITY TRANSMITTERS
AVT Series
Thank you for choosing an HK Instruments AVT series air velocity
transmier. The AVT series is intended for use in commercial environ-
ments. It is designed with a duct mount probe and adjustable collar
suitable for round or rectangular ducts. The AVT series provides sepa-
rate readings for air velocity and temperature.
The AVT series comes with three measurement ranges in a single de-
vice (0–2 m/s, 0–10 m/s, 0–20 m/s). The AVT series is available with
oponal display and relay.
• READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING
TO INSTALL, OPERATE OR SERVICE THIS DEVICE.
• Failure to observe safety informaon and comply with instrucons
can result in PERSONAL INJURY, DEATH AND/OR PROPERTY
DAMAGE.
• To avoid electrical shock or damage to equipment, disconnect
power before installing or servicing and use only wiring with
insulaon rated for full device operang voltage.
• To avoid potenal re and/or explosion do not use in potenally
ammable or explosive atmospheres.
• Retain these instrucons for future reference.
• This product, when installed, will be part of an engineered system
whose specicaons and performance characteriscs are not
designed or controlled by HK Instruments. Review applicaons
and naonal and local codes to assure that the installaon will
be funconal and safe. Use only experienced and knowledgeable
technicians to install this device.
• Fuse at load supply (normally 6 A, 10 A, 16 A) does not always limit
the relay output load current to 6 A. Relay Maximum Load (250 V x
6 A res.)
• Add an external fuse to relay common connector. Use a me-lag
fuse (max 6 A) that is in accordance with the standard IEC 60127-2.
The product doesn’t have an internal fuse for the relay.
CAUTION: The product may only be connected to overvoltage
category II electricity network according to IEC 60664-1.
Performance
Measurement ranges:
Velocity:
Range: 0–2 m/s
Range: 0–10 m/s
Range: 0–20 m/s
Temperature: 0−50 °C
Accuracy:
Velocity:
Range: 0...2 m/s: <0.2 m/s + 5 % from reading
Range: 0...10 m/s: <0.5 m/s + 5 % from reading
Range: 0...20 m/s: <1.0 m/s + 5 % from reading
Thermal shi: ±0.8 % FS / °C
Units calibrated at 22 °C. Rapid thermal shi
stabilisaon me 10 min.
Temperature: <0.5 ºC typical @25ºC (velocity > 0.5 m/s)
Technical Specicaons
Media compability:
Dry air or non-aggressive gases
Measuring units:
m/s and °C
Measuring element:
Temperature: ntc10k
Velocity: Pt1000
Environment:
Operang temperature: 0...50 °C
Storage temperature: -20...70 °C
Humidity: 0 to 95 % rH, non-condensing
Physical
Dimensions:
Case : 86.0 x 95.0 x 36.0 mm
Probe: OD 10 mm, length 210 mm from boom of the
cover
Immersion Length with Flange: Adjustable 50–180 mm
Weight:
220 g
Mounng:
Mounng ange, ø 4.0 mm
Materials:
Case: ABS
Lid: PC
Probe: Stainless steel 304
Mounng ange: LLPDP
Protecon standard:
IP54
Display
3 1/2 digit LCD backlit display
Size: 45.7 x 12.7 mm
Electrical connecons:
Power supply & signal out: 4-screw terminal block
16–24 AWG (0.2–1.5 mm2)
Relay Out: 3-screw terminal block
16-24 AWG (0.2–1.5 mm2)
Cable entry:
M16
Electrical
Input: 24 VDC / 24 VAC ± 10 %
Current consumpon 35 mA (50 mA with relay)
+ 40 mA with mA-outs
Output signal 1: (T out)
0–10 V (linear to temperature)
L min 1 kΩ
4–20 mA (linear to temperature)
L max 400 Ω
Output signal 2: (v out)
0–10 V (linear to m/s)
L min 1 kΩ
4–20 mA (linear to m/s)
L max 400 Ω
Relay Out: 3-screw terminal block
(NC, COM, NO)
Potenal free SPDT
250 VAC, 6A / 30 VDC, 6 A adjustable switching point
and hysteresis
Conformance
Meets the requirements for:
CE: UKCA:
EMC: 2014/30/EU S.I. 2016/1091
RoHS: 2011/65/EU S.I. 2012/3032
LVD/EESR: 2014/35/EU S.I. 2016/1101
WEEE: 2012/19/EU S.I. 2013/3113
SPECIFICATIONS
INTRODUCTION
AVT series devices are commonly used in HVAC/R systems for:
• in-duct air ow and velocity monitoring
• in-duct temperature monitoring
• VAV applicaons
APPLICATIONS
WARNING
RoHS
COMPLIANT