Copyright HK Instruments 2017 www.hkinstruments. Installaon version 5.0 2017
STEP 3: CONFIGURATION
STEP 4: MODBUS REGISTERS
ForCEcomplianceaproperlygroundedshieldingcableis
required.
1)Unscrewthestrainreliefandroutethecable(s).
2)Connectthewiresasshowningure2a.
3)Tightenthestrainrelief.
A
24 V
GND
+ Power Supply
24VDC / 24VAC
Modbus A
Modbus B
B
WARRANTY POLICY
Thesellerisobligatedtoprovideawarrantyofveyearsforthedeliv-
eredgoodsregardingmaterialandmanufacturing.Thewarrantyperiod
isconsideredtostartonthedeliverydateoftheproduct.Ifadefectin
rawmaterialsoraproduconawisfound,thesellerisobligated,when
theproductissenttothesellerwithoutdelayorbeforeexpiraonof
thewarranty,toamendthemistakeathis/herdiscreoneitherbyre-
pairingthedefecveproductorbydeliveringfreeofchargetothebuy-
eranewawlessproductandsendingittothebuyer.Deliverycosts
fortherepairunderwarrantywillbepaidbythebuyerandthereturn
costsbytheseller.Thewarrantydoesnotcomprisedamagescausedby
accident, lightning, ood or other natural phenomenon, normal wear
andtear,improperorcarelesshandling,abnormaluse,overloading,im-
properstorage,incorrectcareorreconstrucon,orchangesandinstal-
laonworknotdonebythesellerorhis/herauthorizedrepresentave.
Theseleconofmaterialsfordevicespronetocorrosionisthebuyer’s
responsibility,unlessotherwiseislegallyagreedupon.Shouldtheman-
ufactureralterthestructureofthedevice,thesellerisnotobligatedto
makecomparablechangestodevicesalreadypurchased.Appealingfor
warrantyrequiresthatthebuyerhascorrectlyfullledhis/herdues
arisenfromthedeliveryandstatedinthecontract.Thesellerwillgive
anewwarrantyforgoodsthathavebeenreplacedorrepairedwithin
thewarranty,howeveronlytotheexpiraonoftheoriginalproduct’s
warrantyme.Thewarrantyincludestherepairofadefecvepartor
device, orifneeded,a new partordevice,butnotinstallaonorex-
change costs. Underno circumstanceisthe seller liable fordamages
compensaonforindirectdamage.
1)AcvatethedeviceMenubypushingthetheselectbuonfor2
seconds.
2)SelecttheaddressforModbus:1...247.
ADDRESS
99
SELECT
UP
DOWN
3)Selectthebaudrate:9600/19200/38400.
BAUD RATE
9600
SELECT
UP
DOWN
3)Selecttheparitybit:None/Even/Odd.
PARITY BIT
NONE
SELECT
UP
DOWN
4)Pushtheselectbuontoexitmenu.
SELECT
EXIT MENU SELECT
Funcon04-Readinputregister
Register Parameter descripon Data Type Value Range
3x0001 Programversion 16bit 0...1000 0.0...99.00
3x0003 rHreading 16bit 0...1000 0.0...100.0%
3x0004 Temperaturereading 16bit 0...500 0.0...50.0°C
STEP 2: WIRING DIAGRAMS
RECYCLING/DISPOSAL
The parts le over from installaon should be
recycled according to your local instrucons.
Decommissioned devices should be taken to a
recyclingsitethatspecializesinelectronicwaste.
Figure 2 - Wiring diagram