Copyright HK Instruments 2019 www.hkinstruments. Installaon version 6.0 2019
INSTALLATION
INSTRUCTIONS
CARBON DIOXIDE TRANSMITTERS
CDT-MOD-2000 Duct Series
• READ THESE INSTRUCTIONS CAREFULLY BEFORE
ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS
DEVICE.
• Failuretoobservesafetyinformaonandcomplywith
instruconscanresultinPERSONALINJURY,DEATHAND/OR
PROPERTY DAMAGE.
• Toavoidelectricalshockordamagetoequipment,disconnect
powerbeforeinstallingorservicinganduseonlywiringwith
insulaonratedforfulldeviceoperangvoltage.
• Toavoidpotenalreand/orexplosiondonotuseinpotenally
ammableorexplosiveatmospheres.
• Retaintheseinstruconsforfuturereference.
• Thisproduct,wheninstalled,willbepartofanengineered
systemwhosespecicaonsandperformancecharacteriscs
arenotdesignedorcontrolledbyHKInstruments.Review
applicaonsandnaonalandlocalcodestoassurethatthe
installaonwillbefunconalandsafe.Useonlyexperiencedand
knowledgeabletechnicianstoinstallthisdevice.
SPECIFICATIONS
ThankyouforchoosinganHKInstrumentsCDT-MOD-2000Duct
seriescarbondioxidetransmierwithModbusinterface.TheCDT-
MOD-2000Ductseriesisintendedforuseincommercialenviron-
mentsinHVAC/Rapplicaons.
CDT-MOD-2000 Duct is a carbon dioxide transmier with tem-
peratureoutputinstalledinairvenlaonduct.Illuminateddisplay
ensureseasyreadabilityalsofromadistance.TheCDT-MOD-2000
Duct has a screwless lid and an easily adjustable mounng ange
thatmaketheinstallaonofthedeviceeasy.
TheCDT-MOD-2000Ductseriestransmierscalibratethemselves
automacallyusingABCTMlogic.TheABCTMlogicrequiresthatthe
space in which the transmier is used needs to to be unoccupied
forfourhoursperdaysothattheindoorCO2concentraondrops
to the outside level. CDT-MOD-2000-DC Duct is a dual channel
modelwithameasuringchannelandareferencechannelthatmakes
aconnuouscomparisonandthenecessaryadjustmentaccordingly.
CDT-MOD-2000-DCDuctisalsosuitableforbuildingsthatarecon-
nuouslyoccupied.
CDT-MOD-2000Ductseriesdevicesarecommonlyusedtomonitor:
• CO2andtemperaturelevelsofincomingandreturnairinvenlaon
systems
•CDT-MOD-2000-DCDuctseriesdevicescanalsobeusedin
applicaonswherethereisaconstantsourceofcarbondioxide
present(forexamplehospitalsandgreenhouses)
SPECIFICATIONS
Performance
Measurement ranges:
CO2:400–2000ppm
Temperature:0...50°C
Accuracy:
CO2:±40ppm+2%ofreading,DCmodel:75ppmor
10%ofreading(whicheverisgreater)
Temperature:<0.5ºC
Technical Specicaons
Media compability:
Dryairornon-aggressivegases
Measuring units:
ppmand°C
Measuring element:
CO2:Non-dispersiveinfrared(NDIR)
Temperature:NTC10K
Calibraon:
Automacself-calibraonABCLogicTMorconnuous
comparison(DC)
Environment:
Operangtemperature:0...50°C
Storagetemperature:-20...70°C
Humidity:0to95%rH,noncondensing
Physical
Dimensions:
Case:119x100x44.7mm
Probe:L=188mm,d=12mm
Mounng:
Withange,adjustable0...188mm
Weight:
150g
Materials:
Case:ABS
Cover:PC
Probe:ABS
Protecon standard:
IP54
Electrical connecons:
4springloadedterminals
Powersupply:
(24VandGND)
0.2–1.5mm2(12–24AWG)
ModbusRTU:
AandBline
0.2–1.5mm2(12–24AWG)
Electrical
Supplyvoltage:24VACorVDC±10%
Currentconsumpon:max230mA(at24V)+10mA
foreachvoltageoutput
Communicaon
Protocol:MODBUSoverSerialLine
TransmissionMode:RTU
Interface:RS485
Byteformat(11bits)inRTUmode:
CodingSystem:8-bitbinary
BitsperByte:
1 start bit
8databits,leastsignicantbitsent
rst
1bitforparity
1stopbit
Baudrate:selectableinconguraon
Modbusaddress:1−247addressesselectablein
conguraonmenu
Conformance
MeetsrequirementsforCEmarking:
EMCDirecve:2014/30/EU
RoHSDirecve:2011/65/EU
WEEEDirecve:2012/19/EU
INTRODUCTION WARNING
APPLICATIONS
COMPANY WITH
MANAGEMENT SYSTEM
CERTIFIED BY DNV GL
RoHS 2
2011/65/EU