manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. HK Instruments
  6. •
  7. Transmitter
  8. •
  9. HK Instruments DPT-Dual-MOD Series User manual

HK Instruments DPT-Dual-MOD Series User manual

Copyright HK Instruments 2017 www.hkinstruments. Installaon version 6.0 2017
INSTALLATION
INSTRUCTIONS
DIFFERENTIAL PRESSURE TRANSMITTERS
DPT-Dual-MOD Series
• READ THESE INSTRUCTIONS CAREFULLY BEFORE
ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS
DEVICE.
• Failuretoobservesafetyinformaonandcomplywith
instruconscanresultinPERSONALINJURY,DEATHAND/OR
PROPERTY DAMAGE.
• Toavoidelectricalshockordamagetoequipment,disconnect
powerbeforeinstallingorservicinganduseonlywiringwith
insulaonratedforfulldeviceoperangvoltage.
• Toavoidpotenalreand/orexplosiondonotuseinpotenally
ammableorexplosiveatmospheres.
• Retaintheseinstruconsforfuturereference.
• Thisproduct,wheninstalled,willbepartofanengineered
systemwhosespecicaonsandperformancecharacteriscs
arenotdesignedorcontrolledbyHKInstruments.Review
applicaonsandnaonalandlocalcodestoassurethatthe
installaonwillbefunconalandsafe.Useonlyexperiencedand
knowledgeabletechnicianstoinstallthisdevice.
SPECIFICATIONS
ThankyouforchoosinganHKInstrumentsDPT-Dual-MODseries
dierenalpressuretransmier.DPT-Dual-MODcombinestwodif-
ferenalpressuretransmiersintoonedevice.Itoersapossibility
tomeasurepressurefromtwodierentpoints.IthasaModbusin-
terfaceandanInputterminal.
TheInputterminalenablesreadingofmulpleothersignalssuchas
temperatureorcontrolrelaysoverModbus.TheInputterminalhas
two input channels designed to accept 0−10 V, NTC10k, Pt1000,
Ni1000/(-LG),andBININ(potenalfreecontact)signals.Forexam-
ple,DPT-Dual-MODcanreadvaluesfromonedierenalpressure
measurementpointandtwotemperaturemeasurementpoints.
DPT-Dual-MODseriesdevicesarecommonlyusedinHVAC/R
systems for:
•fan,blowerandltermonitoring
•pressureandowmonitoring
•valveanddampercontrol
•pressuremonitoringincleanrooms
DPT-Dual-MOD-AHUcanalsobeusedfor:
•airowmonitoringacrosscentrifugalfansandblowers
•in-ductairowmonitoring
•VAVapplicaons
SPECIFICATIONS
Performance
Accuracy (from applied pressure):
Model2500:
Pressure<125Pa=1%+±2Pa
Pressure>125Pa=1%+±1Pa
Model7000:
Pressure<125Pa=1.5%+±2Pa
Pressure>125Pa=1.5%+±1Pa
(Including:generalaccuracy,temperaturedri,linearity,
hysteresis,longtermstabilityandrepeonerror)
Response me:
1...20sselectableviamenu
Overpressure:
Proofpressure:25kPa
Burstpressure:30kPa
Communicaon
Protocol:MODBUSoverSerialLine
TransmissionMode:RTU
Interface:RS485
Byteformat(11bits)inRTUmode:
 CodingSystem:8-bitbinary
 BitsperByte:
  1startbit
  8databits,leastsignicantbitsent
  rst
  1bitforparity
  1stopbit
Baudrate:selectableinconguraon
Modbusaddress:1−247addressesselectablein
conguraonmenu
Zeropointcalibraonopons:
•Manualpushbuonautozero
•ViaModbuswritecoil
Technical Specicaons
Media compability:
Dryairornon-aggressivegases
Measuring units on display (Selectable via menu):
Pressure:Pa,kPa,mbar,inchWC,mmWC,psi
Flow(AHUmodel):m3/s,m3/hr,cfm,l/s,m/s,/min
Measuring element:
MEMS
Environment:
Operangtemperature:-10...+50°C
Storagetemperature:-20...+70°C
Humidity:0to95%rH
Physical
Dimensions:
Case:102.0x71.5x36.0mm
Weight:
150g,withaccessories290g
Mounng:
2each4.3mmscrewholes,onesloed
Materials:
Case: ABS
Lid:PC
Pressure inlets: Brass
Ductconnectors:ABS
Tubing:PVC
Protecon standard:
IP54
Display:
2-linedisplay(12characters/line)
Line1:acvemeasurement,inletA
Line2:acvemeasurement,inletB
Ifinputsareselected,thelinesshowalsoinput
informaon(forexampletemperature)
Electrical Connecons:
4+4springloadterminals,max1.5mm2
CableEntry:M20
Pressure connecons:
Male 5,0mmand6,3mm
Electrical
Supply voltage:
24VACorVDC±10%
Power consumpon:
<1.3W
Output signal:
viaModbus
Conformance
MeetsrequirementsforCEmarking:
EMCdirecve2014/30/EU
RoHSDirecve2011/65/EU
WEEEDirecve2012/19/EU
INTRODUCTION WARNING
APPLICATIONS
COMPANY WITH
MANAGEMENT SYSTEM
CERTIFIED BY DNV GL
= ISO 9001 = ISO 14001 =
RoHS 2
2011/65/EU
Copyright HK Instruments 2017 www.hkinstruments. Installaon version 6.0 2017
SCHEMATICS
DIMENSIONAL DRAWINGS
Figure 1a - Mounng orientaon
Figure 1b - Applicaon connecons
Display connecon
A
B
24 V
GND
LEDs
Joysck 1
Joysck 2
Joysck 3
Select
Up
Down
Menu buons
Terminal
blocks
Pressure
sensors
Input terminal
configuraon
jumpers
Input 1
Input 2
GND
GND
InputOutput
Pressure
inlet A Pressure
inlet B
YES NO NO
Stac pressure Filter/Damper
monitoring
Fan/Blower
monitoring
Not
connected
INSTALLATION
1)Mountthedeviceinthedesiredlocaon(seestep1).
2)Openthelidandroutethecablethroughthestrainreliefand
connectthewirestotheterminalblock(s)(seestep2).
3)Thedeviceisnowreadyforconguraon.
WARNING!Applypoweronlyaerthedeviceisproperlywired.
Pressure
Flow
Thepressuretubesareconnectedtoaowmeasurementprobe(i.e.FloXact),ortothe
measurementportsspeciedbythefanmanufacturer.PleaseseetheFloXactinstallaon
guideorthefanmanufacturer’stechnicalspecicaonsformoreinformaon.
STEP 1: MOUNTING THE DEVICE
1)Selectthemounnglocaon(duct,wall,panel).
2)Usethedeviceasatemplateandmarkthescrewholes.
3)Mountwithappropriatescrews.
MOUNTING THE DEVICE CONTINUED
STEP 2: WIRING DIAGRAMS
ForCEcompliance,aproperlygroundedshieldingcableisrequired.
1)Unscrewthestrainreliefandroutethecable(s).
2)Connectthewiresasshowningure2aand2b.
3)Tightenthestrainrelief.
Figure 2a - Wiring diagram
Figure 2b - Wiring diagram example for input signals
Input 1
Input 2
GND
GND
Pt1000
NTC10k
J1
J2
J3
IN1 IN2
Input 1 Pt1000 temperature:
Funcon 04 - Read input register 3x0005
Input 2 NTC10k temperature:
Funcon 04 - Read input register 3x0008
A
B
24 V
GND
+ Power Supply
24VDC / 24VAC
Input 1
Input 2
GND
GND
Modbus
Copyright HK Instruments 2017 www.hkinstruments. Installaon version 6.0 2017
NOTE! Always zero the device before use.
Supplyvoltagemustbeconnectedonehourbeforethezeropoint
adjustmentiscarriedout.AccessviaModbusorbypushbuon.
1)Loosebothtubesfromthepressureinlets+and-.
2)Regularmodel:Presstheselectbuonbriey.
AHUmodel:Presstheselectbuonfor3secto
enterthemenuandselectzero sensors.
3)WaitunltheLEDturnsoandtheninstalltubesagainforthe
pressureinlets.
CONFIGURATION CONTINUED
STEP 3: CONFIGURATION
9)SelecttheaddressforModbus:1...247.
BAUD RATE
9600
SELECT
UP
DOWN
ADDRESS
99
SELECT
UP
DOWN
PARITY BIT
NONE
SELECT
UP
DOWN
10)Selectthebaudrate:9600/19200/38400.
11)Selecttheparitybit:None/Even/Odd.
12)Selectthepressureunitfordisplay:Pa/inchWC/mmWC/psi/mbar.
(Not for AHU model)
PRESS. UNIT
Pa
SELECT
UP
DOWN
13)Selecttheresponseme:1...20s.
RESPONSETIME
20 s
SELECT
UP
DOWN
14)Pushtheselectbuontoexitmenu.
SELECT
EXIT MENU SELECT
STEP 4: ZERO POINT ADJUSTMENT
SELECT
1)AcvatethedeviceMenubypushingthetheselectbuonfor2
seconds.
Points 2–8 for AHU model only:
3)If
commonprobe
selected:selectmeasurementunitsusedinthe
formula(akaFormulaunit)(i.e.l/s)
FORMULA UNIT
l/s
SELECT
UP
DOWN
4)SelectK-value
Each applicaon has a specic K-value. Select the K-value from the
manufacturer’sspecicaons.
AvailableK-valuerange:0.001...9999.000
K-VALUE
9000.000
SELECT
UP
DOWN
5)Selectpressureunitfordisplayandoutput:Pa,kPa,mbar,inWCor
mmWC
PRESS.UNIT
Pa
SELECT
UP
DOWN
6)Selectowunitfordisplayandoutput:
Flowvolume:m3/s,m3/h,cfm,l/s
Velocity:m/s,f/min
FLOW UNIT
m3/s
SELECT
UP
DOWN
2)Selectthefunconingmodeofthedevice:
-SelectManufacturerwhenconnecngDPT-Dual-MOD-AHUtoa
fanwithpressuremeasurementpoints
-SelectCommon probe whenusingDPT-Dual-MOD-AHUwitha
commonmeasurementprobethatfollowstheformula:
 q=k∙√∆P(i.e.FloXact)
7)Selectthethetypeofsensorforinput1:
NTC10k, Ni1000-LG, Ni1000, Pt1000, VINPUT (voltage 0–10 V),
none(sensor1willnotbeshownondisplay)
SENSOR 1
NTC10K
SELECT
UP
DOWN
7)Selectthethetypeofsensorforinput2:
NTC10k, Ni1000-LG, Ni1000, Pt1000, VINPUT (voltage 0–10 V),
none(sensor2willnotbeshownondisplay)
SENSOR 2
NONE
SELECT
UP
DOWN
MANUFACTURER
Common probe
SELECT
UP
DOWN
Common probe Flakt Woods
SELECT
UP
DOWN
Copyright HK Instruments 2017 www.hkinstruments. Installaon version 6.0 2017
Thesellerisobligatedtoprovideawarrantyofveyearsforthedeliv-
eredgoodsregardingmaterialandmanufacturing.Thewarrantyperiod
isconsideredtostartonthedeliverydateoftheproduct.Ifadefectin
rawmaterialsoraproduconawisfound,thesellerisobligated,when
theproductissenttothesellerwithoutdelayorbeforeexpiraonof
thewarranty,toamendthemistakeathis/herdiscreoneitherbyre-
pairingthedefecveproductorbydeliveringfreeofchargetothebuy-
eranewawlessproductandsendingittothebuyer.Deliverycosts
fortherepairunderwarrantywillbepaidbythebuyerandthereturn
costsbytheseller.Thewarrantydoesnotcomprisedamagescausedby
accident, lightning, ood orother natural phenomenon, normal wear
andtear,improperorcarelesshandling,abnormaluse,overloading,im-
properstorage,incorrectcareorreconstrucon,orchangesandinstal-
laonworknotdonebythesellerorhis/herauthorizedrepresentave.
Theseleconofmaterialsfordevicespronetocorrosionisthebuyer’s
responsibility,unlessotherwiseislegallyagreedupon.Shouldtheman-
ufactureralterthestructureofthedevice,thesellerisnotobligatedto
makecomparablechangestodevicesalreadypurchased.Appealingfor
warrantyrequiresthatthebuyerhascorrectlyfullledhis/herdues
arisenfromthedeliveryandstatedinthecontract.Thesellerwillgive
anewwarrantyforgoodsthathavebeenreplacedorrepairedwithin
thewarranty,howeveronlytotheexpiraonoftheoriginalproduct’s
warrantyme.Thewarrantyincludestherepairofadefecvepartor
device,orifneeded,a newpartordevice,butnotinstallaonorex-
changecosts. Under nocircumstance isthe seller liablefordamages
compensaonforindirectdamage.
Register Parameter descripon Data Type Value Range
3x0001 Programversion 16bit 0...1000 0,00...99,00
3x0002 PressurereadingA 16bit -250...2500/7000 -250...2500/7000(Pa)
3x0003 PressurereadingB 16bit -250...2500/7000 -250...2500/7000(Pa)
3x0004 Input1:0...10V 16bit 0...1000 0...100%
3x0005 Input1:Pt1000 16bit -500...500 -50...+50°C
3x0006 Input1:Ni1000 16bit -500...500 -50...+50°C
3x0007 Input1:Ni1000-LG 16bit -500...500 -50...+50°C
3x0008 Input1:NTC10k 16bit -500...500 -50...+50°C
3x0009 Input2:0...10V 16bit 0...1000 0...100%
3x0010 Input2:Pt1000 16bit -500...500 -50...+50°C
3x0011 Input2:Ni1000 16bit -500...500 -50...+50°C
3x0012 Input2:Ni1000-LG 16bit -500...500 -50...+50°C
3x0013 Input2:NTC10k 16bit -500...500 -50...+50°C
AHU model only:
3x0014 Flowm3/s 16bit 0...10000 0...100m3/s
3x0015 Flowm3/h 16bit 0...30000 0...30000m3/h
3x0016 Flowcfm 16bit 0...30000 0...30000cfm
3x0017 Flowl/s 16bit 0...3000 0...3000l/s
3x0018 Velocitym/s 16bit 0...1000 0...100m/s
3x0019 Velocityf/min 16bit 0...5000 0...5000f/min
Funcon04-Readinputregister
The parts le over from installaon should be
recycled according to your local instrucons.
Decommissioned devices should be taken to a
recyclingsitethatspecializesinelectronicwaste.
STEP 6: MODBUS REGISTERS
RECYCLING/DISPOSAL
WARRANTY POLICY
Funconcode03-Readinputholdingregister-AHU model only
Register Parameter descripon Data Type Value Range
4x0001 Manufacturer 16bit 0...7 0...7
4x0002
Formulaunit(Manufac-
turer=7)
16bit 0...5
0=m3/s,1=f/min,2=m/s,3=l/s,4=cfm,
5=m3/h
4x0003 K-FactorInteger 16bit 0...9999 0...9999
4x0004 K-FactorDecimal 16bit 0...999 0...999
4x0005 ResponseTime 16bit 0...20 0...20s
MODBUS REGISTERS CONTINUED
Funconcode02-Readinputstatus
Register Parameter descripon Data Type Value Range
1x0001 Input1:BININ Bit0 0...1 On-O
1x0002 Input2:BININ Bit0 0...1 On-O
Funcon05-Writesinglecoil
Register Parameter descripon Data Type Value Range
0x0001 Zeroingfuncon Bit0 0...1 On-O
Funconcode06-Writesingleregister-AHU model only
Register Parameter descripon Data Type Value Range
4x0001 Manufacturer 16bit 0...7 0...7
4x0002
Formulaunit(Manufac-
turer=7)
16bit 0...5
0=m3/s,1=f/min,2=m/s,3=l/s,4=cfm,
5=m3/h
4x0003 K-FactorInteger 16bit 0...9999 0...9999
4x0004 K-FactorDecimal 16bit 0...999 0...999
4x0005 ResponseTime 16bit 0...20 0...20s
STEP 5: INPUT SIGNAL CONFIGURATION
InputsignalscanbereadoverModbusviaDPT-MODRS485interface.
Signals Accuracy for measurement Resoluon
0...10V <0,5% 0,1%
NTC10k <0,5% 0,1%
Pt1000 <0,5% 0,1%
Ni1000/(-LG) <0,5% 0,1%
BININ(potenalfreecontact)
Thejumpersshouldbesetaccordingtotheinstruconsbelowandthe
valueshouldbereadfromtherightregister.Bothinputscanbecong-
uredindependently.
Figure 3 - Input signal conguraon
J1
J2
J3
IN1 IN2
J1
J1
J1
J2
J2
J2
J3
J3
J3
NTC10k / BIN IN
Pt1000 / Ni10007(-LG)
0...10 V

Other HK Instruments Transmitter manuals

HK Instruments DPT-Priima Series User manual

HK Instruments

HK Instruments DPT-Priima Series User manual

HK Instruments RHT Series User manual

HK Instruments

HK Instruments RHT Series User manual

HK Instruments CDT2000 Series User manual

HK Instruments

HK Instruments CDT2000 Series User manual

HK Instruments CMT Series User manual

HK Instruments

HK Instruments CMT Series User manual

HK Instruments DPT-CR-MOD Series User manual

HK Instruments

HK Instruments DPT-CR-MOD Series User manual

HK Instruments CDT2000 Series User manual

HK Instruments

HK Instruments CDT2000 Series User manual

HK Instruments DPT-MOD Series User manual

HK Instruments

HK Instruments DPT-MOD Series User manual

HK Instruments SIRO Series User manual

HK Instruments

HK Instruments SIRO Series User manual

HK Instruments CDT-MOD-2000 Series User manual

HK Instruments

HK Instruments CDT-MOD-2000 Series User manual

HK Instruments DPT-MOD Series User manual

HK Instruments

HK Instruments DPT-MOD Series User manual

HK Instruments RHT-MOD Duct Series User manual

HK Instruments

HK Instruments RHT-MOD Duct Series User manual

HK Instruments DPT-Flow Series User manual

HK Instruments

HK Instruments DPT-Flow Series User manual

HK Instruments RHT Series User manual

HK Instruments

HK Instruments RHT Series User manual

HK Instruments DPT-Dual-MOD Series User manual

HK Instruments

HK Instruments DPT-Dual-MOD Series User manual

HK Instruments CDT-MOD-2000 Duct Series User manual

HK Instruments

HK Instruments CDT-MOD-2000 Duct Series User manual

HK Instruments RHT-MOD Duct Series User manual

HK Instruments

HK Instruments RHT-MOD Duct Series User manual

HK Instruments DPT-Flow-1000 Quick start guide

HK Instruments

HK Instruments DPT-Flow-1000 Quick start guide

HK Instruments KLU 100 User manual

HK Instruments

HK Instruments KLU 100 User manual

HK Instruments DPT-Ctrl-MOD Series User manual

HK Instruments

HK Instruments DPT-Ctrl-MOD Series User manual

HK Instruments DPT-Priima Series User manual

HK Instruments

HK Instruments DPT-Priima Series User manual

HK Instruments AVT Series User manual

HK Instruments

HK Instruments AVT Series User manual

HK Instruments DPT2500-R8 Series Instruction manual

HK Instruments

HK Instruments DPT2500-R8 Series Instruction manual

HK Instruments DPT-R8 Series User manual

HK Instruments

HK Instruments DPT-R8 Series User manual

HK Instruments RHT-MOD Duct Series User manual

HK Instruments

HK Instruments RHT-MOD Duct Series User manual

Popular Transmitter manuals by other brands

AMG AMG5803A966G-DF instruction manual

AMG

AMG AMG5803A966G-DF instruction manual

Lectrosonics HM instruction manual

Lectrosonics

Lectrosonics HM instruction manual

ASTEL TT 101 operating instructions

ASTEL

ASTEL TT 101 operating instructions

Micatrone Micaflex PFTT Installation & operation manual

Micatrone

Micatrone Micaflex PFTT Installation & operation manual

Williams Sound T1-216 Specification sheet

Williams Sound

Williams Sound T1-216 Specification sheet

Omnitronic TM-100 user manual

Omnitronic

Omnitronic TM-100 user manual

Tele Radio PN-T13-3 installation instructions

Tele Radio

Tele Radio PN-T13-3 installation instructions

BKM FTC1 user manual

BKM

BKM FTC1 user manual

SICK TRANSIC111LP operating instructions

SICK

SICK TRANSIC111LP operating instructions

Siemens SITRANS P series operating instructions

Siemens

Siemens SITRANS P series operating instructions

SGM LEKTRA PTU51 manual

SGM LEKTRA

SGM LEKTRA PTU51 manual

rojaflex RHST5-W Assembly and operating instructions

rojaflex

rojaflex RHST5-W Assembly and operating instructions

G-QRP Club Limerick Sudden manual

G-QRP Club

G-QRP Club Limerick Sudden manual

Minebea OPT-564 instruction manual

Minebea

Minebea OPT-564 instruction manual

Trust APIR-2150 user manual

Trust

Trust APIR-2150 user manual

SVS SHT-12 BS operating instructions

SVS

SVS SHT-12 BS operating instructions

iWantit iFMT11 quick start guide

iWantit

iWantit iFMT11 quick start guide

Invisible systems QC0150 installation manual

Invisible systems

Invisible systems QC0150 installation manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.