4
European Economic Area certification mark
Environment Friendly Use Period
Intrinsically Safe - À Sécurité Intrinsèque
Cl. I, Div. 1, Grps. A,B,C,D, T4
Cl. I, Zn. 1, AEx ia IIC T4
Ex ia IIC T4
Ta -20°C to +50°C
IP66
Patent: www.hsmpats.com
WARNING/AVERTISSEMENT
Part NO.
Serial NO.
Mod State: 1 2 3 4 5 6 7 8 9 10
Honeywell Analytics Ltd., Poole, Dorset, BH17 0RZ Made in UK
465385
HAND HELD UNIT
TEST TOOL
2331B1000
XXXXXXXXX
Read and understand manual before installation, operation or servicing. Substitution of components may impair intrinsic safety. Do not open or replace battery when an explosive atmosphere is present.
Use only DURACELL MN2400 AAA batteries or equivalent (refer to Quick Start Guide for allowed battery types).
Lire et comprendre le manuel avant d’installer, d’utiliser ou de réparer l’équipement. La substitution des composants peut nuire à la sécurité intrinsèque. N’ouvrez pas l’équipement et ne remplace pas la betterie dans
des atmosphères contenant des explosifs.
Utilisez uniquement des piles AAA DURACELL MN2400 ou équivalentes (reportez-vous au Guide de démarrage rapide pour les types de piles autorisés).
II 2 G
HAND HELD UNIT - TEST TOOL
Ex ia IIC T4 Gb
Ta -20°C to +50°C
DEMKO20ATEX2247
IECEx UL20.0043
IP66
Patent: www.hsmpats.com
2813
Read and understand manual before installation, operation or servicing. Substitution of components may impair intrinsic safety.
Do not open or replace battery when an explosiveatmosphere is pre sent.
WARNING
Part NO.
Serial NO.
Mod State: 1 2 3 4 5 6 7 8 9 10
Honeywell Analytics Ltd., Poole, Dorset, BH17 0RZ Made in UK
Use only DURACELL MN2400 AAA batteries or equivalent (refer to Quick Start Guide for allowed battery types)
2331B1000
XXXXXXXXX
Example certification labels
Example warning label
Instructions
The Hand Held Test Tool is an ultrasound-generating device used for
functional verification of the Searchzone Sonik detector. It may be used in
combination with the Searchzone Sonik App running on a suitable mobile
device.
The Hand Held Test Tool generates two different test signals to check
detector’s functionality:
1) First test signal is recognized by the detector as a ‘bump test’ and is
used to perform the local test. It is reported through change in detector’s
LED ring status indicator, however the detector’s outputs will NOT be
activated. This local test is automatically logged.
2) Second test signal is used for END-toEND testing. It is reported as
Alarm through detector’s LED ring status indicator, relays and through
420mA loop.
WARNING
While operating the Hand Held Test Tool, do not under any circum-
stances aim the tool towards your head, or any other person.
NOTE: When using the Hand Held Test Tool, ensure that it is operated at
least 1m from the Searchzone Sonik detector.