KMC Controls STE-8001 User manual

STE-8001 and STE-8201 sensors
Installation Guide
Section 1
Introduction to STE-8000 sensors
Specifications ...........................................................................................................................4
Safety considerations .............................................................................................................6
Section 2
Installing STE-8000 sensors
Planning for motion sensing .................................................................................................7
Rough-in preparation ............................................................................................................8
Installing the sensors ..............................................................................................................8
Maintenance ............................................................................................................................9
Section 3
User functions
Operating the STE-8000 .......................................................................................................11
Changing setpoints ...............................................................................................................12
Section 4
Commissioning functions
The commissioning sequence .............................................................................................14
Enter the commissioning mode ..........................................................................................14
Setting up network communications .................................................................................15
Box options ............................................................................................................................16
Setting commissioning setpoints ........................................................................................20
Setting the airflow setpoints ...............................................................................................23
Balancing airflow ..................................................................................................................27
Advanced options ................................................................................................................31
Set
Point
7O
12O2
RevisionA

KMC Controls
Revision A2
Important notices ©2012, KMC Controls, Inc.
WinControl XL Plus, NetSensor, and the KMC logo are registered trademarks of
KMC Controls, Inc.
BACstage and TotalControl are trademarks of KMC Controls, Inc.
All rights reserved. No part of this publication may be reproduced, transmitted,
transcribed, stored in a retrieval system, or translated into any language in any
form by any means without the written permission of KMC Controls, Inc.
Printed in U.S.A.
Disclaimer The material in this manual is for information purposes only. The contents and
the product it describes are subject to change without notice. KMC Controls, Inc.
makes no representations or warranties with respect to this manual. In no event
shall KMC Controls, Inc. be liable for any damages, direct or incidental, arising
out of or related to the use of this manual.
KMC Controls
P. O . B o x 4 9 7
19476 Industrial Drive
New Paris, IN 46553
U.S.A.
TEL: 1.574.831.5250
FAX: 1.574.831.5252
E-mail: [email protected]

Revision A 3
SECTION 1
Introduction to STE-8000 sensors
This section provides a description of the KMC Controls STE-8001
and STE-8201 wall sensors. It also introduces safety information.
Review this material before installing or operating the sensors.
Models STE-8001 and STE-8201 are wall-mounted, temperature sensor for use
with KMC BAC-8000 series VAV controllers. Key features include the following:
◆Integrated operator interface ready to use with BAC-8000 series VAV
controllers
◆Large LCD display
◆Simple three-button interface
◆Continuously displays temperature and time
◆Separate password protection for user and commissioning functions
◆Use as a service tool to set up BAC-8000 series VAV controllers
◆Optional motion sensor to detect space occupancy
Note
An STE-8000 series sensor will display time if the controller to which it is
attached has been synchronized with system time within the previous 24
hours.
Illustration 1-1 STE-8001 and STE-8201
Set
Point
7O
12O2
Set
Point
7O
12O2
STE-8001 STE-8201

KMC Controls
Revision A
Introduction to STE-8000 sensors
Specifications
4
Specifications
Display Multifunctional LCD
1.88 x 1.25 in. (48 x 32 mm)
Compatibility BAC-8000 series VAV controllers
Controller Connection
Connector type Eight-wire RJ-45 modular jack
Cable type and length Standard Ethernet cable up to 75 feet (22.9 meters)
Power Supplied by connected controller
Mounting Surface mount directly to any flat surface or to a
2x 4 inch or 4 x 4 inch handy-box. Mounting on a
4x 4 inch box requires a mounting backplate.
Weight 2.8 ounces (80 grams)
Material Flame retardant plastic
Accessories
Mounting backplate HMO-1161W
Gasket HPO-116
Replacement Allen screwsHPO-0044 (package of 10)
Environmental Limits
Operating Temperature 34° to 125° F (1.1 to 51.6° C)
Shipping –40° to 140° F (–40°C to 60° C)
Humidity 0 to 95% relative humidity
non-condensing

STE-8001 and STE-8201 sensors
Revision A
Introduction to STE-8000 sensors
Specifications
5
Motion sensor range Model STE-8201 only
Detector type Passive infrared
Range 33 feet (10 meters). See diagrams
Dimensions
ABCDE F
3.25 in. 5.16 in. 2.58 in. 3.25 in. 0.87 in. 1.07 in.
83 mm 116 mm 66 mm 83 mm 22 mm 27 mm
55°
10 m
32.8 ft
10 m
32.8 ft
X
0°
10 m
32.8 ft
10 m
32.8 ft
0°
46.5°
Y
Top view Side view
7O
12O2
C
B
A
D
E
F

KMC Controls
Revision A
Introduction to STE-8000 sensors
Safety considerations
6
Models
Temperature sensor only STE-8001
Temperature and motion STE-8201
Safety
considerations KMC Controls assumes the responsibility for providing you a safe product and
safety guidelines during its use. Safety means protection to all individuals who
install, operate, and service the equipment as well as protection of the
equipment itself. To promote safety, we use hazard alert labeling in this manual.
Follow the associated guidelines to avoid hazards.
Danger
Danger represents the most severe hazard alert. Bodily harm or death will
occur if danger guidelines are not followed.
Warning
Warning represents hazards that could result in severe injury or death.
Caution
Caution indicates potential personal injury or equipment or property damage
if instructions are not followed.
Note
Notes provide additional information that is important.
Detail
Provides programing tips and shortcuts that may save time.

Revision A 7
SECTION 2
Installing STE-8000 sensors
This section provides important instructions and guidelines for
installing the STE-8000 series sensors. Carefully review this
information before installing the controllers.
Installing the sensors includes the following topics that are covered in this
section.
◆Planning for motion sensing on page 7
◆Rough-in preparation on page 8
◆Installing the sensors on page 8
◆Maintenance on page 9
Planning for
motion sensing For STE-8201 only—Mount the STE-8201 sensor on a wall that will have an
unobstructed view of the typical traffic in the coverage area. When choosing a
location, do not install the sensor in the following areas.
◆Behind curtains or other obstructions
◆In locations that will expose it to sunlight or heat sources
◆Near a heating/cooling duct.
For details on the coverage pattern, see Specifications on page 4.
The effective detection range is approximately 10 meters or 33 feet. Factors that
may reduce the range include:
◆The difference between the surface temperature of the object and the
background temperature of the room is too small.
◆Object movement in a direct line toward the sensor.
◆Very slow or very fast object movement.
◆Obstructions as shown in the illustration Typical motion sensing coverage area
on page 7.
Illustration 2-1 Typical motion sensing coverage area

KMC Controls
Revision A
Installing STE-8000 sensors
Rough-in preparation
8
False detections may be triggered by:
◆The temperature inside the detection range suddenly changes because of
the entry of cold or warm air from an air-conditioning or heating unit.
◆The sensor being directly exposed to sunlight, an incandescent light, or
other source of far-infrared rays.
◆Small animal movement.
Rough-in
preparation Complete rough-in wiring at each sensor location prior to sensor installation.
This includes the following.
◆Routing the connecting cable from the sensor to a controller.
◆If required, install the appropriate backplate. See Accessories on page 4 for
model numbers.
Connect the STE-8000 series sensor to a controller with a standard Ethernet cable
with RJ-45 connectors on each end. Maximum cable length is 75 feet (22.9
meters). Plenum-rated preassembled cables are recommended.
Installing the
sensors To install the sensor on a backplate, do the following:
1. Turn the Allen screws in the base of the NetSensor clockwise until they
clear the cover. Swing the sensor away from the mounting base to remove
it.
2. Route the Ethernet cable through the mounting base.
3. Fasten the mounting base directly to a 2 x 4 inch outlet box or a backplate
with the Allen screws toward the floor.
Illustration 2-2 Sensor mounting details
Connecting cable
Maximum 75 feet
or 22.9 meters
Allen
screws
Mounting
base
Illustration 2-3 Mounting screws
Turn clockwise to
remove from base.

STE-8001 and STE-8201 sensors
Revision A
Installing STE-8000 sensors
Maintenance
9
4. Insert the Ethernet cable coming from the base into the sensor.
5. Place the top of the sensor over the top of the mounting base and swing it
down over the Allen screw brackets. Be careful not to pinch any wiring.
6. Back the Allen screws out of the brackets until they engage the sensor cover
and hold it in place.
Maintenance Remove dust as necessary from holes in top and bottom. Clean the display with
soft, damp cloth and mild soap.

KMC Controls
Revision A
Installing STE-8000 sensors
Maintenance
10

Revision A 11
SECTION 3
User functions
This section covers topics for the end user in a facility.
User functions are limited to changing the occupied temperature setpoints from
the STE-8000.
Operating the
STE-8000 The functions are accessible through an STE-8000 series sensor. The functions are
entered or changed using the buttons and display on the front of the STE-8000.
◆Pressing either the up button or down button changes a selection,
setting, or value.
◆Pressing the setpoint button saves the setting or value. Typically saving
an entry also advances to the next display.
Note
An STE-8000 series sensor will display time if the controller to which it is
attached has been synchronized with system time within the previous 24
hours.
Illustration 3-1 The STE-8000 series display and buttons
Set
Point
Set
Point
7O
12O2
LCD display with
temperature and time
UP and down
buttons
Setpoint button
Motion sensor
(STE-8201 only)

KMC Controls
Revision A
User functions
Changing setpoints
12
Changing
setpoints To enter or change the occupied setpoints you will need a Level 1 password.
Enter occupied setpoints
Procedure Steps STE display
Starting display Start from the temperature display.
Enter the level one
password
1. Press the button.
2. Press the or buttons to change
the first digit.
3. Press the button to select the next
digit. Repeat for all four digits.
4.
Note: If a Level 1 password has not
previously been entered, the display
will change to the occupied cooling
setpoint display after Step 1.
Set the occupied
cooling setpoint 1. Press the or buttons to change
the cooling setpoint temperature. The
setpoint changes in increments of 0.5
degrees.
2. Press the button to save the value.
The display advances to set the
heating setpoint.
Set the occupied
heating setpoint 1. Press the or buttons to change
the heating setpoint temperature.
The setpoint changes in increments
of 0.5 degrees.
2. Press the button to save the value.
The display returns to the
temperature display.
72
12S1
Set
Point
Set
Point
PSW1
OOOO
Set
Point
7SO
COOLING
Set
Point
68O
HEATING

Revision A 13
SECTION 4
Commissioning functions
This topics in this section are advanced topics for control technicians
and engineers.
The commissioning functions that are accessible through an STE-8000 series
sensor are values and settings that are entered during the installation and
commissioning of a VAV terminal unit. Typically these functions do not change
after the installation and commissioning process.
To set up the commissioning functions, you will need the following:
◆Information about the VAV terminal unit including the configuration for
fans and reheat
◆The installation and operation manual supplied with the controller to
which the STE-8000 series sensor is connected.
◆The building automation system plans.
Users may change the occupied heating and cooling setpoints without accessing
the commissioning functions. This procedure is covered in User functions on
page 11.
Note
The instructions for commissioning functions cover all of the functions that an
STE-8000 sensor can set up in the BAC-8000 series of controllers. Not all
functions are available on every model of controller. Consult the installation
and operation manual supplied with the controller to verify the functions and
options that are available.

KMC Controls
Revision A
Commissioning functions
The commissioning sequence
14
The
commissioning
sequence Set the commission functions in the following sequence.
1. Enter the commissioning mode on page 14
2. Setting up network communications on page 15
3. Box options on page 16
4. Setting commissioning setpoints on page 20
5. Setting the airflow setpoints on page 23
6. Balancing airflow on page 27
Enter the
commissioning
mode For access to the commissioning functions you will need a Level 2 password.
◆If the controller has not been previously set up, no password is required.
◆A new Level 2 password can be entered in the advanced commissioning
functions. See the topic Advanced options on page 31.
Enter the commissioning mode
Procedure Steps STE display
Starting display Start from the temperature display.
Enter the
commissioning
password
1. Press the and buttons together
and hold them down until the
display changes to PSW2.
2. Press the or button to change
the first digit.
3. Press the button to select the next
digit. Repeat for all four digits.
4. When the button is pushed for the
fourth correct digit, the display
changes to COMM.
Note: If a Level 2 password has not
previously been entered the display
will change to the COMM display after
Step 1.
Select a
commissioning
function
Access to the commissioning
functions always start at the COMM
display.
72
12S1
Set
Point
Set
Point
PSW2
OOOO
COMM

STE-8001 and STE-8201 sensors
Revision A
Commissioning functions
Setting up network communications
15
Setting up
network
communications Set the network communication settings before placing a controller on the
network. Setting network settings requires entering the Level 2 password which
is described in the topic Enter the commissioning mode on page 14.
Procedure to set up network communications
Procedure Steps STE display
Starting display 1. Start at the temperature display.
2. Enter the Level 2 password. The
display changes to the COMM.
Select the COMM
display
Press the button. The display changes
to DI D.
Enter the device
instance.
1. Press the or buttons to change
the first digit.
2. Press the button to select the next
digit. Repeat for all seven digits.
3. When the button is pressed for the
last digit, the display changes to MAC.
Enter the MAC
address.
1. Press the or buttons to change
the MAC address.
2. Press the button to save the
selected MAC address.
The display changes to BAUD.
Enter the baud 1. Press the or buttons to select a
new baud.
2. Press the button is save the
selected baud.
The display returns to COMM.
Advance or exit 1. Press the or buttons to select
one of the following:
•BLNC or CNFG options
•EXIT to return to the temperature
display.
2. Press the button to select the next
function.
72
12S1
PSW2
OOOO
Set
Point
COMM
Set
Point
Set
Point
D ID
OO72O69
Set
Point
MAC
11
Set
Point
BAUD
384OO
Set
Point
COMM

KMC Controls
Revision A
Commissioning functions
Box options
16
Box options The box options set up the controller for the specific mechanical installation of
the VAV terminal unit. Setting the box options requires entering the Level 2
password which is described in the topic Enter the commissioning mode on
page 14.
Procedure to set the box functions
Procedure Steps STE display
Starting display 1. Start at the temperature display.
2. Enter the Level 2 password. The
display changes to the COMM.
Select the box
settings display.
1. From the COMM display, press the
or buttons to show the CNFG
display.
2. Press the button to select the CNFG
options. The display changes to
STPT.
3. Press the or buttons to change
the display to BOX.
4. Press the button to select BOX.
Set the primary
VAV terminal unit
K-factor.
1. Press the or buttons to set the
primary K-factor.
2. Press the button to save the entry
and advance to the next function.
Set the secondary
VAV terminal unit
K-factor.
1. Press the or buttons to set the
secondary K-factor.
2. Press the button to save the entry
and advance to the next function.
72
12S1
PSW2
OOOO
Set
Point
Set
Point
COMM
CNFG
STPT
BOX
Set
Point
9O4
PKFT
Set
Point
9O4
SKFT

STE-8001 and STE-8201 sensors
Revision A
Commissioning functions
Box options
17
Set the mode of
reheat for the
terminal unit
1. Press the or buttons to choose
one of the following reheat options.
None—Reheat is not enabled.
Staged—Enables two or three stage
reheat. If lighting is enabled the
staged reheat is set to two stages. If
lighting is not enabled, three reheat
stages are available.
Modulating—The reheat output
varies from 0-10 volts.
Floating—The reheat outputs control
a tristate actuator.
Time proportional—Controls a
thermal wax valve with a 24-volt
triac output.
2. Press the button to save the reheat
option and advance to the next
function.
Set the fan option 1. Press the or buttons to choose
one of the following fan options.
None—No fan is connected to the
controller.
Series—The VAV unit includes a
series fan.
Parallel—The VAV unit includes a
parallel fan.
2. Press the button to save the fan
option and advance to the next
function.
Procedure to set the box functions (Continued)
Procedure Steps STE display
Set
Point
NONE
REHT
Set
Point
NONE
FAN

KMC Controls
Revision A
Commissioning functions
Box options
18
Set the damper
direction to close
1. Press the or buttons to which
direction to damper moves to close.
CCW—The actuator turns
counterclockwise to close the
damper.
CW—The actuator turns clockwise to
close the damper.
2. Press the button to save the
damper option and advance to the
next function.
Set the dual duct
mode
1. Press the or buttons to choose
the dual duct mode of operation.
VAV—The system maintains space
temperature with variable air volume
control.
CAC—The system maintains space
temperature with constant air
volume control.
Supply exhaust offset—The system
maintains space temperature with
the primary VAV controller. The
secondary controller controls the
exhaust unit. Supply/exhaust
tracking is controlled as an offset
percentage.
Supply exhaust differential—The
system mantains space temperature
with the primary VAV controller. The
secondary controller controls the
exhaust unit. Supply/exhaust
tracking controlled by differential
pressure.
Indoor air quality—Room
temperature is maintained with
primary VAV unit and CO2 levels
controlled by secondary VAV unit.
2. Press the button to save the dual
duct option and advance to the next
function.
Procedure to set the box functions (Continued)
Procedure Steps STE display
Set
Point
CCW
DDIR
Set
Point
A
DUAL

STE-8001 and STE-8201 sensors
Revision A
Commissioning functions
Box options
19
Advance or exit 1. Press the or buttons to select
one of the following:
•STPT, FLOW, or ADVC options
•BACK to choose another
commissioning function
•EXIT to return to the temperature
display.
2. Press the button to select the next
function.
Procedure to set the box functions (Continued)
Procedure Steps STE display
Set
Point
BOX

KMC Controls
Revision A
Commissioning functions
Setting commissioning setpoints
20
Setting
commissioning
setpoints The commissioning setpoints set the operational parameters and limits for the
VAV terminal unit. Setting configuration setpoints requires entering a Level 2
password which is described in the topic Enter the commissioning mode on
page 14.
Procedure to set the commissioning setpoints
Procedure Steps STE display
Starting display Enter the Level 2 password. The display
changes to the COMM.
Select the setpoint
display.
1. From the COMM display, press the
or buttons to show the CNFG
display.
2. Press the button to select the CNFG
options. The display changes to
STPT.
3. Press the button to select the STPT
options.
Set the minimum
cooling setpoint 1. Press the or buttons to set the
minimum cooling setpoint. The
setpoint will change in 0.5°
increments.
2. Press the button to save the
setpoint and advance to the next
function.
Set the maximum
heating setpoint 1. Press the or buttons to set the
maximum heating setpoint. The
setpoint will change in 0.5°
increments.
2. Press the button to save the
setpoint and advance to the next
function.
PSW2
OOOO
Set
Point
Set
Point
COMM
CNFG
STPT
Set
Point
MIN
68O
Set
Point
MAX
78O
This manual suits for next models
1
Table of contents
Other KMC Controls Accessories manuals

KMC Controls
KMC Controls STE-6010 User guide

KMC Controls
KMC Controls NetSensor KMD-1261 Operating instructions

KMC Controls
KMC Controls NetSensor KMD-1162 Operating instructions

KMC Controls
KMC Controls STW Series User manual

KMC Controls
KMC Controls STE-6014 User manual

KMC Controls
KMC Controls STE-6014 User guide

KMC Controls
KMC Controls Conquest STE-90 Series User manual

KMC Controls
KMC Controls KMD-1183 Operating instructions

KMC Controls
KMC Controls STW-6010 User manual

KMC Controls
KMC Controls THE-1105 User manual