Lumel N100 User manual

1
POWER NETWORK ANALYSER
N100
USER’S MANUAL

2

3
Contensts
1 APPLICATION.................................................................................. 5
2 METER SET..................................................................................... 6
3 BASIC REQUIREMENTS, OPERATIONAL SAFETY ..................... 6
4 INSTALLATION................................................................................ 7
5 METER DESCRIPTION ................................................................... 8
5.1 Current inputs.............................................................................. 8
5.2 Voltage inputs .............................................................................. 8
5.3 External connection diagrams ................................................... 8
6 N100 PROGRAMMING.................................................................. 13
6.1 Front panel................................................................................. 13
6.2 Power-on message.................................................................... 15
6.3 Operating modes....................................................................... 16
6.4 MEASURING mode.................................................................... 19
6.4.1 Measurement of voltage and current harmonics ................ 20
6.5 Parameter settings .................................................................... 25
6.5.1 Setting of meter parameters PAr........................................... 27
6.5.2 Setting the input and output parameters InoUt................... 30
6.5.3 Alarm conguration ALn........................................................ 31
6.5.4 Analog outputs conguration Ao_n ..................................... 35
6.5.5 Pages conguration PAG ...................................................... 39
6.5.6 Archiving conguration Arch ................................................ 42
6.5.7 Ethernet settings conguration Ethr.................................... 45

4
7 MEASURING VALUES ARCHIVING ............................................. 48
7.1 INTERNAL MEMORY.................................................................. 48
7.2 COPYING ARCHIVE TO SD CARD............................................ 48
7.3 ARCHIVE FILES STRUCTURE .................................................. 49
7.4 DOWNLOADING ARCHIVE FROM SD CARD .......................... 50
8 SERIAL INTERFACES................................................................... 51
8.1 RS485 INTERFACE – list of parameters .................................. 51
8.2 Examples of registers’ readout and write ............................... 51
8.3 Ethernet interface 10/100-BASE-T ........................................... 56
8.3.1 Connecting 10/100-BASE-T interface ................................... 56
8.3.2 WWW Server ........................................................................... 58
8.3.3 FTP Server............................................................................... 61
8.3.4 Modbus TCP/IP ....................................................................... 63
8.4 Map of N100 meter registers .................................................... 63
9 SOFTWARE UPGRADE ................................................................ 91
10 ERROR CODES........................................................................... 93
11 TECHNICAL DATA....................................................................... 94
12 ORDERING CODE..................................................................... 100

5
1. APPLICATION
The N100 meter is a programmable digital instrument designed
for the measurement of 3-phase, 3 and 4-wire power network para-
meters in balanced or unbalanced systems. The measured values
are displayed on a two-color LED display. The meter enables control
and optimization of the power electronic devices, systems and industrial
installations.
The meter provides measurement of: RMS of voltage and current,
active, reactive and apparent power, active, reactive and apparent
energy, power factors, frequency, the harmonics of current and voltage
/up to 51st/, THD of voltage and current, averaged active
and apparent power P Demand, S Demand, averaged current I Demand
/15, 30 or 60 minutes/. Voltages and currents are multiplied by gi-
ven voltage and current ratios of the measuring transformers.
Power and energy indications take into account all programmed ratio
values. The value of each measured value can be transmitted
to the master system via the RS-485 or Ethernet interface. Three relay
outputs signal the overow of the chosen value, and the pulse output
can be used for the consumption check of 3-phase active energy.
The programmable analog outputs map the assigned parameter.
The pulse input can be used to check the counters with the pulse outputs.
There is a galvanic separation between following units of the meter:
–supply
–voltage inputs
–current inputs
–RS485 interface
–Ethernet interface
–pulse input
–pulse output OC
–alarm outputs
–analog outputs

6
2. METER SET
Complete set of the meter includes:
–N100 Meter 1 pc
–user’s manual 1 pc
–warranty card 1 pc
– screw clamp to x in the panel 4 pcs
–RS485 interface connector 1 pc
3. BASIC REQUIREMENTS,
OPERATIONAL SAFETY
In terms of operational safety the controller meets the requirements
of the EN 61010-1 standard.
Comments concerning safety:
• The meter should be installed and connected only by a qualied
personnel. All relevant safety measures should be observed during
installation.
• Always check the connections before turning the meter on.
• Prior to taking the meter housing off, always turn the supply off
and disconnect the measuring circuits.
• Removal of the meter housing during the warranty period voids
the warranty.
• This meter conforms to all requirements of the electromagnetic
compatibility in the industrial environment.
• A switch or a circuit-breaker should be installed in the building
or facility. It should be located near the device, easily accessible
by the operator, and suitably marked.

7
4. INSTALLATION
The meter is adapted to be xed to the panel with moun-
ting brackets as presented on Fig. 1. The meter housing is made
of a self-extinguishing plastics.
Housing overall dimensions 144 x 144 x 77 mm, dimensions
of the assembly hole 138 x 138 mm. There are screw terminal strips on
the outer side of the meter which enable the connection of external wires
of diameter up to 2.5 mm2.
max 10
138 +0,5
144
144
77,3
10
137,6
Fig 1. Overall
dimensions
and mounting
of the N100 meter
the hole in the mounting plate

8
5. METER DESCRIPTION
5.1 Current inputs
All current inputs are galvanically isolated (internal current transformers).
The meter is adapted to work with external measuring current transfor-
mers / 1 A or 5 A /. Displayed current values and derivative values are
automatically converted in relation to the introduced external current
transformer ratio.
5.2 Voltage inputs
All voltage inputs are galvanically isolated (internal transformers).
Values on voltage inputs are automatically converted according
to the introduced ratio of the external voltage transformer. Voltage inputs
are specied in the order as 3x57.7/100V, 3x230/400V or 3x400/690V.
5.3 External connection diagrams
External connections are shown in Figures 2 and 3.
Version: 3 relays, 1 analog output, 1 pulse input, 1 pulse output
Pulse In.Out.1 Pulse Out. AL1 AL2 AL3
RJ45 socket
(Ethernet)
Interface RS-485
Version with 3 relay outputs,
1 analog output
Uaux

9
Fig. 2. Connections of output signals
Version: 3 analog outputs, 1 relay
Direct measurement in 4-wire network
Interface RS-485
Uaux Out.A1 Out.A2 Out.A3 AL3
RJ45 socket
(Ethernet)
Version with 3 analog outputs,
1 relay output

10
Semi-indirect measurement in 4-wire network
Fig. 3. Meter connections of input signals
in a 3-phase 4-wire network
Semi-indirect measurement in 4-wire network

11
Direct measurement in a 3-wire network
Semi-indirect measurement using 2 current transformers
in a 3-wire network

12
Indirect measurement using 2 current transformers
and 2 or 3 voltage transformers in a 3-wire network
Fig. 4. Meter connections of input signals in a 3-phase 3-wire network

13
6. N100 PROGRAMMING
6.1 Front panel
Fig.5. Front panel
indication
of displayed
phase
elds of the displays
f1, f2, f3, f4
units
of the
displayed
values
alarm
signaling
f1
f2
f3
f4
ESC
resignation
or back
button
left
displacement
button
decrease
value
button
increase
value
button
right
displacement
button
ENTER
acceptance
button

14
The N100 meter has 6 buttons, 4 4½-digit display sections, illuminated
symbols and unit parameters. The values of the measured parame-
ters are shown on the active pages selected by subsequent pressing
the button (next page) or (previous page).
The page consists any 4 values selected from the Table 1 and displayed
simultaneously on the meter. The page denition is described
in the conguration mode P.
Front panel description:
ENTER acceptance
button
f1,f2,f3,f4 4 4 ½ -digit display
sections for readout
and settings
right displacement
button
Var Wh
PF tg
units of the displayed
values
increase value button L1 L2 L3 indication of
displayed phase
decrease value button A1A2A3 symbols of alarms
activation
left displacement
button
DM Averaged value
indicator (Demand)
ESC resignation
or back button
k, M kilo = 103,
Mega = 106
RxTx Indicators
of receiving
and transmitting data
on the RS485 link
SD indicator of writing
on SD/SDHC card

15
The assignment of individual buttons is as follows:
The button allows to enter the procedure SEt (pressed for more
than 3 seconds) when programming is used to accept the entered value.
The buttons when programming are used to change
the value of the digit in the decimal position. They enable to display
the minimum and maximum values respectively in the measurement mode.
The buttons enable to change the pages
in the measurement mode, when programming enable a cursor displa-
cement to successive decimal positions, in the procedure SEt enable to
change the displays luminosity.
The button enables in anytime the resignation of carried out
operations or return to a higher level in the procedure SEt.
It cancels the alarms in measurement mode.
6.2 Power-on message
Fig. 6. Message after starting the meter

16
After switching the supply on, the meter performs a display test
and displays the N100 meter name, version and current software version
where:
N100 – meter type,
230V 5A – version
r1.00 – revision, version of the program
6.3 Operating modes
The N100 meter has 8 modes listed below:
Mode Call out
Name Call out
symbol
Input Output
measurement default by entering a
different mode
meter parameters par
in SETUP
procedure
, or
after last parameter
inputs and outputs
parameters
binary and RS485
interface
1noUt
alarm conguration al1
al2
al3
analog outputs
conguration
ao1
ao2
ao3
pages
conguration
pag

17
The meter enters the measurement mode and displays the page set befo-
re it was turned off after switching the supply on and performing the tests.
To enter the SETUP procedure, press the button
for approx. 3 seconds.
Use the buttons to select an appropriate mode.
Active mode par, 1noUt, aln, aon, pag, arch or ethr is indicated
by blinking of the appropriate symbol. Accept a selected mode by pres-
sing the button .
where: n – number of an alarm or analog output
Use the button to return to a measurement mode from other
modes .
Archive
parameters
arch
in SETUP
procedure
,or
after last parameter
Ethernet
parameters
ethr

18
Alarm reset Power
or
or
or
or or or or
or or
supply
pressed
released
pressed
released
andand
or
or
sec
MEASUREMENT
Mode
Display
of the minimum values
reset
Selection of harmonic
currents I1, I2, I3
harmonics Code Enter the code
Change
of displayed pages
Display
of the maximum values
reset
Selection of harmonic
currents U1, U2, U3
harmonics
Selection of SEt parameters
change the display luminosity
selection of the group parameters
Meter parameters
mode
Parameters acc. to Table 2 Parameters acc. to Table 4 Pages programming
acc. to Table 7 Parameters acc. to Table 8
Alarm parameters
mode
Pages conguration
mode
Ethernet parameters
mode
Change of quantity
of a selected parameterChange of quantity
of a selected parameterChange of quantity
of a selected parameterChange of quantity
of a selected parameter
or
RS485 parameters,
output and binary
intput mode
Parameters acc. to Table 3Parameters acc. to Table 5
Analog outputs
mode Archive parameters
mode
Parameters acc. to Table 7
Change of quantity
of a selected parameter
Change of quantity
of a selected parameterChange of quantity
of a selected parameter
return to a higher level without saving the changes
only preview of parameters, without the possibility of changes
Fig 7. N100 meter
operating modes

19
6.4 MEASURING mode
In the MEASURING mode the values are displayed according
to the pages that are preset at the factory or congured by the user
in Pages Programming PAG.
Changing the page is done by pressing the button
or . The sequence of displayed pages is according to a table
created in PAG mode.
Preview of the maximum or minimum values respectively is
done while the button or is pressed down.
Reset of maximum or minimum values is done by pressing the button
while viewing their values, i.e. rst the button or
and then must be pressed.
Alarms are active if they were allocated. Note that the alarms do not
need to be associated with the values displayed on the page because
the change of a page would result in action on two-state outputs.
The alarm switching on is signaled by the lighting of the ALn inscrip-
tion (n=1..3). The end of alarm duration at the alarm signalization latch
switched on, is indicated by the pulsation of the ALn inscription (n= 1..3).
Erasing alarm signalization latch / if it was set in the Alarm parameters
mode ALn / is done by pressing the button .
When displaying the reactive capacity power or energy, a marker indi-
cating the load character is displayed , there is no mark for inductive
load.
When displaying the active power, the sign „-” is displayed for active
energy export or no mark for active energy import.
Exceeding of the upper or lower indication range is signaled
on the display by upper or lower horizontal lines. For measurement
of the averaged values (P Demand, S Demand, I Demand) single
measurements are carried out with 0.25 second quantum.Averaging time
to choose from: 15, 30 or 60 minutes. Until all samples of the averaged
values are acquired, the values are calculated from already measured samples.
Current value in the neutral wire I(N) is calculated from phase current vectors.

20
6.4.1 Measurement of voltage and current harmonics
The choice of harmonics is done by pressing the buttons
forviewingthecurrentharmonicsor
for voltage harmonics.
Voltage harmonics U1, U2, U3 or current harmonics I1, I2, I3
are displayed simultaneously for 3-phases. The number of displayed
harmonic circled in the gure, is signaled by blinking and it can
be changed in the range 2..51 by pressing or buttons.
By pressing button, you can return to the measuring mode.
Other manuals for N100
1
Table of contents
Other Lumel Measuring Instrument manuals
Popular Measuring Instrument manuals by other brands

Elma Instruments
Elma Instruments Elma 9200BT manual

Hioki
Hioki CT9691 installation manual

Exotek Instruments
Exotek Instruments MC-60CPA user manual

PCE Americas
PCE Americas PCE-WM 1 manual

Dwyer Instruments
Dwyer Instruments RVM Specifications-installation and operating instructions

ELMETRON
ELMETRON CX-461 user manual

Airmar
Airmar WeatherStation 200WXRS Owner's guide & installation instructions

Qu-Bit Electronix
Qu-Bit Electronix EON manual

Velleman
Velleman DVM8080 user manual

KROHNE
KROHNE OPTIMASS 1000 Series Guidelines for use

Simpson
Simpson S664 Operation manual

Cleveland Controls
Cleveland Controls 6650 instruction manual