M-system Mini-M M2PA User manual

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-5038 Rev.8 P. 1 / 3
INSTRUCTION MANUAL
Mini-M™
PT TRANSMITTER MODEL
M2PA/M2PE
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.
■PACKAGE INCLUDES:
Signal conditioner (body + base socket).............................(1)
■MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
POINTS OF CAUTION
■NONINCENDIVE APPROVAL OPTION
• This equipment is suitable for use in Class I, Div. 2,
Groups A, B, C and D or Non-Hazardous Locations only.
• WARNING! Before You Remove the Unit from Its Base
Socket or Mount It, Turn Off the Power Supply and Input
Signal for Safety.
• WARNING! – Explosion Hazard –
Substitution of Components May Impair Suitability for
Class I, Div. 2.
• WARNING! – Explosion Hazard –
Do Not Disconnect Equipment Unless Power Has Been
Switched Off or The Area is Known To Be Non-Hazardous.
• The equipment was evaluated for use in the ambient tem-
perature and relative humidity as mentioned in ‘ENVI-
RONMENT’ section.
• The input and output wiring must be in accordance with
Class I, Div. 2 wiring methods and in accordance with the
authority having jurisdiction for use in these hazardous
locations.
■CONFORMITY WITH EU DIRECTIVES OR UL
• This equipment is suitable for Pollution Degree 2, Meas-
urement Category (input, transient voltage 2500V) and
Installation Category II (transient voltage 2500V). Rein-
forced insulation (signal input or output to power input:
300V) and basic insulation (signal input to output: 300V)
are maintained. Prior to installation, check that the insu-
lation class of this unit satisfies the system requirements.
• Altitude up to 2000 meters.
• The equipment must be mounted inside a panel.
• The equipment must be installed such that appropriate
clearance and creepage distances are maintained to con-
form to CE/UL requirements. Failure to observe these
requirements may invalidate the CE/UL conformance.
• The actual installation environments such as panel con-
figurations, connected devices, connected wires, may affect
the protection level of this unit when it is integrated in
a panel system. The user may have to review the CE re-
quirements in regard to the whole system and employ ad-
ditional protective measures to ensure the CE conformity.
• Install lightning surge protectors for those wires connect-
ed to remote locations.
■POWER INPUT RATING & OPERATIONAL RANGE
• Locate the power input rating marked on the product and
confirm its operational range as indicated below:
100 – 240V and 85 – 264V AC rating: 85 – 264V
(90 – 264V for UL), 47 – 66 Hz, approx. 3 – 5VA
24V DC rating: 24V ±10%, approx. 3W
11 – 27V DC rating: 11 – 27V, approx. 3W
110V DC rating: 85 – 150V (110V ±10% for UL), approx. 3W
■GENERAL PRECAUTIONS
• Before you remove the unit from its base socket or mount
it, turn off the power supply and input signal for safety.
■ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -5 to +55°C
(23 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
• Be sure that the ventilation slits are not covered with ca-
bles, etc.
■WIRING
• Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■AND ....
• The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
• With voltage output, do not leave the output terminals
shortcircuited for a long time. The unit is designed to
endure it without breakdown, however, it may shorten ap-
propriate life duration.
COMPONENT IDENTIFICATION
Model
SPAN
ZERO
Zero Adj.
Span Adj.
Body Base Socket
Connection
Diagram
Specifications
Fixing Screw
M2PA / M2PE
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-5038 Rev.8 P. 2 / 3
INSTALLATION
Loosen the fixing screw at the front of the unit in order to
separate the body from the base socket.
DIN Rail
35mm wide
Spring Loaded
DIN Rail Adaptor
■DIN RAIL MOUNTING
Set the base socket so that
its DIN rail adaptor is at
the bottom. Position the
upper hook at the rear side
of base socket on the DIN
rail and push in the lower.
When removing the socket,
push down the DIN rail
adaptor utilizing a minus
screwdriver and pull.
■WALL MOUNTING
Refer to “EXTERNAL DIMENSIONS.”
TERMINAL CONNECTIONS
Connect the unit as in the diagram below or refer to the connection diagram on the side of the unit.
■EXTERNAL DIMENSIONS unit: mm (inch)
5
9
21.5 (.85)
70.5 (2.78)
84 (3.31)10 (.39) 15 (.59)
6 (.23)
59 (2.32)
DIN RAIL
35mm wide
[4 (.16)]
8–M3
SCREW
72 (2.83)
23 (.91)
2–4.2x5
(.17x.20)
MTG HOLE
6 (.24) deep
114 (4.49)
• When mounting, no extra space is needed between units.
4
8
12
14 13
1
4 (.16)
■CONNECTION DIAGRAM
V
U
v
u
FUSE VT
LOAD
SOURCE
1
4
+
–
OUTPUT
9
12
U(+)
V(–)
POWER
13
14
WIRING INSTRUCTIONS
■SCREW TERMINAL
Torque: 0.8 N·m
■SOLDERLESS TERMINAL
Refer to the drawing below for recommended ring tongue
terminal size. Spade tongue type is also applicable.
Applicable wire size: 0.25 to 1.65 mm2(AWG 22 to 16)
Recommended manufacturer: Japan Solderless Terminal
MFG.Co.Ltd, Nichifu Co.,ltd
6 (.24) max
3.3 (.13) max
mm (inch)
M2PA / M2PE
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-5038 Rev.8 P. 3 / 3
CHECKING
1) Terminal wiring: Check that all cables are correctly con-
nected according to the connection diagram.
2) Power input voltage: Check voltage across the terminal
13 – 14 with a multimeter.
3) Input: Check that the input signal is within 0 – 100% of
the full-scale.
Be sure that the input waveform is sinusoidal to obtain
proper accuracy for model M2PA.
4) Output: Check that the load resistance meets the de-
scribed specifications.
ADJUSTMENT PROCEDURE
This unit is calibrated at the factory to meet the ordered
specifications, therefore you usually do not need any cali-
bration.
For matching the signal to a receiving instrument or in case
of regular calibration, adjust the output as explained in the
following.
■HOW TO CALIBRATE THE OUTPUT SIGNAL
Use a signal source and measuring instruments of sufficient
accuracy level. Turn the power supply on and warm up for
more than 10 minutes.
1) ZERO: Apply 0% input and adjust output to 0%.
2) SPAN: Apply 100% input and adjust output to 100%.
3) Check ZERO adjustment again with 0% input.
4) When ZERO value is changed, repeat the above proce-
dure 1) – 3).
MAINTENANCE
Regular calibration procedure is explained below:
■CALIBRATION
Warm up the unit for at least 10 minutes. Apply 0%, 25%,
50%, 75% and 100% input signal. Check that the output
signal for the respective input signal remains within accu-
racy described in the data sheet. When the output is out of
tolerance, recalibrate the unit according to the “ADJUST-
MENT PROCEDURE” explained earlier.
LIGHTNING SURGE PROTECTION
M-System offers a series of lightning surge protector for
protection against induced lightning surges. Please contact
M-System to choose appropriate models.

This manual suits for next models

1

Other M-system Transmitter manuals

M-system W2XT User manual

M-system

M-system W2XT User manual

M-system B5RS User manual

M-system

M-system B5RS User manual

M-system SENTRONIC M2SES User manual

M-system

M-system SENTRONIC M2SES User manual

M-system 10JPA User manual

M-system

M-system 10JPA User manual

M-system 10TS User manual

M-system

M-system 10TS User manual

M-system Mini-M M2XRP2 User manual

M-system

M-system Mini-M M2XRP2 User manual

M-system M2EXV User manual

M-system

M-system M2EXV User manual

M-system M5VSH User manual

M-system

M-system M5VSH User manual

M-system LC2 User manual

M-system

M-system LC2 User manual

M-system M2XPA2 User manual

M-system

M-system M2XPA2 User manual

M-system M5PT User manual

M-system

M-system M5PT User manual

M-system 10JFT User manual

M-system

M-system 10JFT User manual

M-system Mini-M M2RTS User manual

M-system

M-system Mini-M M2RTS User manual

M-system 10MS User manual

M-system

M-system 10MS User manual

M-system Mini-M M2DU User manual

M-system

M-system Mini-M M2DU User manual

M-system M3LV User manual

M-system

M-system M3LV User manual

M-system 15TS User manual

M-system

M-system 15TS User manual

M-system F2VS User manual

M-system

M-system F2VS User manual

M-system W2CA User manual

M-system

M-system W2CA User manual

M-system M5YV User manual

M-system

M-system M5YV User manual

M-system TM User manual

M-system

M-system TM User manual

M-system B5VS User manual

M-system

M-system B5VS User manual

M-system M80YS User manual

M-system

M-system M80YS User manual

M-system M3LR User manual

M-system

M-system M3LR User manual

Popular Transmitter manuals by other brands

ABB 2600T Series operating instructions

ABB

ABB 2600T Series operating instructions

Jung eNet FMHS2 operating instructions

Jung

Jung eNet FMHS2 operating instructions

Extron electronics TP T 15HD AV user manual

Extron electronics

Extron electronics TP T 15HD AV user manual

Tugicom TX25A user manual

Tugicom

Tugicom TX25A user manual

YOKOGAWA Dpharp EJA118N user manual

YOKOGAWA

YOKOGAWA Dpharp EJA118N user manual

CYP PU-515PLTX-1H Operation manual

CYP

CYP PU-515PLTX-1H Operation manual

Thinklogical Velocitykvm Series quick start guide

Thinklogical

Thinklogical Velocitykvm Series quick start guide

WisyCom MTH400 user manual

WisyCom

WisyCom MTH400 user manual

Anywave PA-U-2200-D-FB Marble quick start guide

Anywave

Anywave PA-U-2200-D-FB Marble quick start guide

JUMO dTRANS T02j operating instructions

JUMO

JUMO dTRANS T02j operating instructions

Lectrosonics SMV-941 Series quick start guide

Lectrosonics

Lectrosonics SMV-941 Series quick start guide

Walkera WK-2403 user manual

Walkera

Walkera WK-2403 user manual

RADEMACHER RP-SX5-HS-RF11 quick start guide

RADEMACHER

RADEMACHER RP-SX5-HS-RF11 quick start guide

Shure AD2 manual

Shure

Shure AD2 manual

Dragon-RC DTS-1 instructions

Dragon-RC

Dragon-RC DTS-1 instructions

JRC NJT5669 Series instruction manual

JRC

JRC NJT5669 Series instruction manual

Crestron DigitalMedia DM-TX-100F quick start guide

Crestron

Crestron DigitalMedia DM-TX-100F quick start guide

Moore Industries IPH user manual

Moore Industries

Moore Industries IPH user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.