manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Malmbergs
  6. •
  7. Accessories
  8. •
  9. Malmbergs Dual sense DALI 99 190 23 Quick guide

Malmbergs Dual sense DALI 99 190 23 Quick guide

1. Technical Specifications
Product type Dual sense DALI sensor (HF and PIR, daylight harvest)
Operating voltage 120~277VAC 50/60Hz
Switched power Maximum 20pcs devices, maximum 40mA
Power consumption < 1W
Detection angle 360o
Detection area (DxH) 12 x 6m (Maximum)
Mounting height 6m (Maximum)
Detection range 10% / 50% / 75% / 100%
Hold time 2s / 30s / 1min / 5min / 10min / 15min / 20min / 30min
Stand-by time 0s / 10s / 1min / 5min / 10min / 30min / 1h / +∞
Stand-by dimming level 10% / 20% / 30% / 50%
Daylight threshold 50 ~ 500Lux, Disable
Warmming up time 30s
Operating temperature -20oC ~ +55oC
Sensor mode PIR, HF, PIR+HF, PIR / HF
3. Rotary Switch Settings
A rotary switch is built inside the sensor for
scene selection / fast programming. Total
16 channels available:
Note: settings can also be changed by remote control 99 190 27. The last action controls.
Rotary switch preset (Please
see the location in 2. Installation)
Detection
range
Channel
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
5s
1min
5min
5min
5min
5min
10min
10min
10min
10min
20min
20min
30min
30min
30min
5s
10s
5min
10min
+∞
+∞
+∞
30min
+∞
+∞
+∞
1h
+∞
+∞
+∞
+∞
10s
10%
10%
10%
10%
10%
30%
10%
10%
10%
30%
10%
30%
10%
30%
50%
10%
Disable
50Lux
50Lux
75Lux
100Lux
200Lux
50Lux
75Lux
100Lux
200Lux
100Lux
200Lux
100Lux
200Lux
400Lux
100Lux
Hold
time
Stand-by
time
Stand-by
dimming level
Daylight
threshold
Switch the power supply to the sensor two times within 2 seconds, the ambient lux level is sampled and set
as the new daylight threshold / target lux level. This feature enables the daylight sensor to be commissioned
to the environment in which it is installed. Both the settings on rotary switch and the ambient lux level
sampled can overwrite each other. The last adjustment remains in memory. This may also easily be carried
out using the 99 190 27 remote control handset, please see next page (button ) for details.
5.3 Ambient Daylight Threshold
By connecting the “SYNC” terminals in parallel (see wiring diagram), no matter which sensor detects
motion, all 99 190 23 in the group will turn on the lights when surrounding natural light is below the
daylight threshold. The sensor module is shared and the detection area could be widely enlarged in
this way.
5.4 Synchronization Function
Turn off/on the power supply three times within 3 seconds, the light will be turned on for 8 hours,
even there is no motion detected, then go back to sensor mode automatically.
Note: this 8H manual on mode can be cancelled by turning off/on the power supply one time within
1 second.
5.7 8H Manual ON Mode For LED Lamp
5. Functions
The built-in daylight sensor can measure ambient natural light, and calculate how much electrical light is
needed to reach the target lux level. The demand is given to the LED driver by DALI signal, so as to deliver
the needed amount of electric light. The target lux level can be adjusted by remote control or long press on
the push switch.
5.1 Daylight Harvest (Daylight Regulating)
420
Light level
Time (hrs)
Normal Electric Light
Daylight controlled light
Energy Saving Zone
Natural light
Hold time
Stand-by time
With the help of push-switch, this sensor maybe over-ridden by the end-users to switch on/off the
lights manually, or adjust the target lux level. This makes the product more user-friendly and offers
more options to fit for extra-ordinary demands.
* Short push (<1s): on/off function;
ON → OFF: the light turns off immediately and cannot be lighten for a certain time (equals to hold
time preset) even movement is detected. After this period, the sensor goes back to
auto sensor mode.
OFF → ON: the light turns on and goes to auto sensor mode.
* Long push (>1s): adjust the target lux level by turning the light up or down. Both the adjustment by
remote control and push switch can overwrite each other, the last adjustment
remains in memory.
* If no end-user adjustment is desired, simply leave the “push” terminal disconnected.
5.5 Manual Override (Push Function)
The light dims to minimum level even switches off completelly if ambient daylight is sufficient (natural light
level exceeds target lux level), no matter it is during hold-time or stand-by time, with or without motion.
Note: if the stand-by time is preset at "+∞", the light never turns off even when natural light is sufficient.
5.2 Lux Off Function
Installation and Instruction Manual
TM
10
2. Installation
Warnings:
1. Installation must be carried out by a
qualified engineer in accordance with
local regulations.
2. Disconnect supply before installing.
3. Install to a solid surface - vibrations may
cause mis-triggering.
4. Ensure environmental conditions are
suitable for electronic equipment
29
50.2
55.2
Infrared receiver
HF Sensor module Photocell
PIR
LED indicator
Sensor mode selection
Rotary switch preset
Direct junction “J” box mounting
32.5
53.7
58.7
C - Surface box
B - Facia Cover
a. Separate control board (A) from facia (B)
& Surface box (C). C is not required.
b. Make electrical connections to control board
(A). See detailed wiring diagram on next page.
c. Secure control board (A) to junction box.
d. Set-up sensor modes as per sections 3 & 4
of this manual.
e. Clip facial plate (B) to control board (A).
Surface mount assembly
a. Separate control board (A) from facia (B) &
Surface box (C).
b. Securely mount surface box (C) to a flat and
solid surface.
c. Make electrical connections to control board
(A). See detailed wiring diagram on next page.
d. Set-up sensor modes as per sections 3 & 4 of
this manual.
e. Secure control board (A) to surface box (C).
f. Clip facial plate (B) to control board (A).
A - Control Board
4. Sensor Mode Selection
Sensor mode can be easily selected by choosing the correct combination of the DIP switches
(see table below):
HF
PIR
HF+PIR
HF/PIR
1 2
I
II
III
IV
HF+PIR: Light is on when both HF
and PIR sensors are activated.
HF/PIR: Light is on when HF or PIR
sensors are activated.
SURFACE MOUNT DUAL SENSE MOTION SENSOR 99 190 23
The motion sensor is employed, but only activated on the manual press of the push switch. With
presence, the light remains on and can interact with ambient natural light, then dims down in
absence, eventually switching off automatically after the stand-by time has expired.
Note: end-user can choose either function 5.5 or 5.6 for application. Default function is 5.5.
5.6 Semi-auto Function (Absence Detection)
Varning!
Stäng av strömmen, ta ut säkringen på elcentralen eller ställ automatsäkringen till läge ”AV”, innan
installationsarbetet påbörjas.
Skall installeras av behörig installatör och i enlighet med gällande föreskrifter.
www.malmbergs.com
2017.03.01Art.no: 99 190 23
7. Wiring Diagram
9. Trouble Shooting
YDEMERESUACYDEMER ESUAC NOITCNUFLAM
The fixture does not light up
The fixture is always on
Check detection area setting
The fixture is on when it should not
Incorrect daylight threshold setting
Continued movement in the detection zone
Sudden change in temperature due to weather (wind, rain, snow) or air
expelled from fans, open windows
Detection zone not targeted
Faulty fixture
No power supply
Adjust daylight threshold setting
Replace fixture
Check power to sensor
Check detection area setting
Adjust zone, change installation site
Description of the
Button Functions
(remote control 99 190 27)
8.
99 190 27
6
8
10
11
12
13
14
2
4
1
3
7
9
5
Permanent ON/OFF [ ]
Press button to select permanent ON or permanent OFF mode.
* Press button / to resume automatic operation.
Semi-auto Mode [ button & ]
Power output [ button ]
Press button , the light output shifts between 80% and 100%.
Note: the function of “Sensor off” and “Twilight” are disabled.
Ambient daylight threshold [ button ]
Detection range [ zone ]
Press buttons in zone to set HF detection range at 100% / 75% /
50% / 10%.
Stand-by time [ zone ]
Press buttons in zone to set the stand-by time at 0s / 10s / 1min /
5min / 10min / 30min / 1h / +∞.
Note: “0s” means on/off control; “+∞” means bi-level control, 100%
on when motion detected, and remains at the stand-by
dimming level when no presence after hold-time.
Daylight threshold [ zone ]
Press buttons in zone to set the daylight sensor at 50Lux / 100Lux
/ 300Lux / 500Lux or Disable as threshold / target Lux level.
Note: 2Lux / 10Lux are disabled.
To set daylight sensor at 100Lux / 300 Lux / 500Lux, press
button Shift at first.
button
Auto Mode [ button ]
Brightness +/- [ button ]
Press button to adjust light brightness to reset the target lux level.
Scene prog. [ zone ] (One-key-commissioning)
1. Press button Shift, the red LED flashes for indication.
2. Press button , the ambient lux level is sampled and set as
daylight threshold / target Lux level.
Hold time [ zone ]
Press buttons in zone to set the hold time at 2s / 30s / 1min /
5min / 10min / 15min / 20min / 30min.
Note: 1.To set hold-time at 30s / 5min / 15min / 30min, press button
Shift at first.
2. 2s is for test purpose only, stand-by time and daylight
sensor settings are disabled in this mode.
* To exit from Test mode, press button or any button in zone .
Stand-by dimming level [ zone ]
Press buttons in zone to set the stand-by dimming level at 10% /
20% / 30% / 50%.
Dual tech & RF mode [ zone ]
1. Press buttons in zone to select sensor technology.
HF+PIR: Light is on when both HF and PIR sensors are activated.
HF/PIR: Light is on when HF or PIR sensors are activated.
2. Learn / Erase, Transmit, RX100% and RX STBY% are disabled.
Shift [ button ]
RESET [ button ]
Press button , all settings go back to the rotary switch settings.
Sensor mode return to DIP switch settings.
Press button to initiate automatic mode. The sensor starts working
and all settings remain as before the light was switched ON/OFF.
1. Press button “Start” to program.
2. Select the buttons in “Detection range”, / “Daylight threshold”,
“Hold time”, “Stand-by time”, “Stand-by dimming level” to
set all parameters.
3. Press button “Memory” to save all the settings programmed in the
remote control.
4. Press button “Apply” to set the settings to each sensor unit(s).
For example, to pre-set detection range 100%, daylight threshold
Disable, hold time 5min, stand-by time +∞, stand-by dimming level
30%, steps should be:
Press button Start, button 100%, Disable, Shift, 5min,
Shift, +∞ , 30%, Memory. By pointing to the sensor unit(s)
and pressing Apply, all settings are passed on the sensor(s).
Press button , the LED on the top left corner flashes for indication.
All values / settings in RED are in valid for 20 seconds.
1. Press button Shift (the red LED flashes for indication),
2. press button to initiate semi-auto mode. The fixture is manually on
by push-switch and automatically off in semi-auto mode.
18
3
3
2
9
10
11
12
13
14
14
13
12
11
11
10
9
8
2
2
3
3
3
3
4
4
4
5
6
7
7
7
7
3
3
8
8 9
10
10 11
1312
11 12 13
6
5
4
1
2 4
3
Detection Pattern7.
HF walking towards 10m
PIR walking across 8m
6. Wiring Diagram
SYNC P N L
DA+ DA- DA- DA+
- + L N
LED
99 190 23
SYNC P N L
L
N
DA+ DA-
99 190 23
LED driver
DA- DA+
- + L N
LED
LED driver
DA- DA+
- + L N
LED
LED driver
Max. 20pcs
Max. 20pcs
DA- DA+
- + L N
LED
LED driver
Malmbergs Elektriska AB
|
PO Box 144, SE-692 23 Kumla, SWEDEN
| Phone: +46 19 58 77 00 |
Fax: +46 19 57 11 77
| [email protected] | www.malmbergs.com
www.malmbergs.com

Other Malmbergs Accessories manuals

Malmbergs E-2026 User manual

Malmbergs

Malmbergs E-2026 User manual

Malmbergs Neso LED User manual

Malmbergs

Malmbergs Neso LED User manual

Malmbergs Primo ST-1005B User manual

Malmbergs

Malmbergs Primo ST-1005B User manual

Malmbergs io-DS-BLE User manual

Malmbergs

Malmbergs io-DS-BLE User manual

Malmbergs B620 User manual

Malmbergs

Malmbergs B620 User manual

Malmbergs io-PIR-BLE User manual

Malmbergs

Malmbergs io-PIR-BLE User manual

Malmbergs TP001-ZA User manual

Malmbergs

Malmbergs TP001-ZA User manual

Malmbergs 70000(K) User manual

Malmbergs

Malmbergs 70000(K) User manual

Malmbergs 99 751 42 User manual

Malmbergs

Malmbergs 99 751 42 User manual

Malmbergs PAM21 User manual

Malmbergs

Malmbergs PAM21 User manual

Malmbergs Sense User manual

Malmbergs

Malmbergs Sense User manual

Malmbergs TM001-ZA User manual

Malmbergs

Malmbergs TM001-ZA User manual

Malmbergs 99 190 17-18 User manual

Malmbergs

Malmbergs 99 190 17-18 User manual

Malmbergs io-TH-BLE User manual

Malmbergs

Malmbergs io-TH-BLE User manual

Malmbergs HC009S User manual

Malmbergs

Malmbergs HC009S User manual

Malmbergs 99 190 21 Quick guide

Malmbergs

Malmbergs 99 190 21 Quick guide

Malmbergs 99 190 25 Quick guide

Malmbergs

Malmbergs 99 190 25 Quick guide

Malmbergs 9974125 User manual

Malmbergs

Malmbergs 9974125 User manual

Malmbergs B612Q User manual

Malmbergs

Malmbergs B612Q User manual

Malmbergs HC0025 User manual

Malmbergs

Malmbergs HC0025 User manual

Malmbergs 99 190 22 Quick guide

Malmbergs

Malmbergs 99 190 22 Quick guide

Malmbergs HC407VDS User manual

Malmbergs

Malmbergs HC407VDS User manual

Malmbergs Vinga User manual

Malmbergs

Malmbergs Vinga User manual

Malmbergs ST-1002G User manual

Malmbergs

Malmbergs ST-1002G User manual

Popular Accessories manuals by other brands

Ergon BA3 Evo Protect User instructions

Ergon

Ergon BA3 Evo Protect User instructions

MMC D-2615-11 Operating and maintenance instructions

MMC

MMC D-2615-11 Operating and maintenance instructions

Omron TL-T datasheet

Omron

Omron TL-T datasheet

Parrot Pot quick start guide

Parrot

Parrot Pot quick start guide

iPowerCase iPower6000 instruction manual

iPowerCase

iPowerCase iPower6000 instruction manual

View Sky Sensor installation guide

View

View Sky Sensor installation guide

Farm King 1266 Operator and parts manual

Farm King

Farm King 1266 Operator and parts manual

Axis FA3105-L installation guide

Axis

Axis FA3105-L installation guide

Fiamma Compass 220 Installation and usage instructions

Fiamma

Fiamma Compass 220 Installation and usage instructions

Cisco Catalyst 6500-E Series Installation and verification manual

Cisco

Cisco Catalyst 6500-E Series Installation and verification manual

ESI MAYA44 XTe user guide

ESI

ESI MAYA44 XTe user guide

Skoda OCTAVIA - ANNEXE 338 brochure

Skoda

Skoda OCTAVIA - ANNEXE 338 brochure

Halo ACDC BOLT 58830 operating instructions

Halo

Halo ACDC BOLT 58830 operating instructions

FlowLine EchoPod DL34 Series quick start

FlowLine

FlowLine EchoPod DL34 Series quick start

Hypersen HPS-FT025 manual

Hypersen

Hypersen HPS-FT025 manual

Autonics BTS Series product manual

Autonics

Autonics BTS Series product manual

ROSE DISPLAYS BUTTERFLY CLIPS WITH BALL CHAIN manual

ROSE DISPLAYS

ROSE DISPLAYS BUTTERFLY CLIPS WITH BALL CHAIN manual

Sony BKM-14L Operation manual

Sony

Sony BKM-14L Operation manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.