  9. MULTISPAN TC-221P User manual

MULTISPAN TC-221P User manual

Page 1
TC-221P
INPUT SPECIFICATION:
PV = Process Value
SV = Set Value
TEMPERATURE CONTROLLER
DISPLAY AND KEYS:
CONTROL METHOD:
DIMENSION:
OUTPUT SPECIFICATION:
POWER SUPPLY:
ENVIRONMENT CONDITION:
Display
Heating
Size
Keys
Panel Cutout
Power
Consuption
(VA Rating)
Relative Humidity
Protection Level
(As per request)
Relay
Output Signal
Supply
Voltage
Operating Temp.
Relay Type
Rating
Upper: 3 digit, 7 segment, 0.80”
1) PID control with Auto-Tuning
Lower: 3 digit, 7 segment, 0.40”
2) ON-OFF control
72 (H) x 72 (W) x 45 (D) mm
100 to 270V AC, 50-60Hz
0°C to 55°C
UP to 95% RH
(non-condensing)
IP-65 (Front side) As per IS/IEC
60529 : 2001
1 Nos
12V DC, 30mA DC
(On-Off condition)
1C/O (NO-C-NC)
10A, 230V AC / 28V DC
SET, INC, DEC, ENT
68 (H) x 68 (W) mm
4VA @ 230V AC MAX
Relay Output
SSR Drive Output
TECHNICAL SPECIFICATION
68
68
MECHANICAL INSTALLATION
TERMINAL CONNECTION
Outline Dimension (mm) Panel Cutout
Dimension (mm)
8
9
Thermocouple
+
Sensor Input
72
72
Display Color:
Upper : RED/WHITE
Lower: Green
SV
PV
SET ENT
TC 221P
°
OUT
17
8
2345
10
11
12
13
14
6
9
NCCNO
Relay
LN
!
-
+
Control Action: ON-OFF, PID
Sensor:
Range:
J Type
0 to 400°C
-
+
S.S.R
O/P
100
270V AC
~
50/60 Hz
4VA
Made in India
www.multispanindia.com
T/C
Input Type
Resolution
Indication
Accuracy
Input Range
0 to 400°C, J
1°C
±1% of FSD ± 1°C
(FSD:-Full Scale Deflection)
3
45
Page 2
Read complete instructions prior to installation
and operation of the unit.
WARNING : Risk of electric shock.
SAFETY PRECAUTION
!
All safety related codifications, symbols and instructions that
appear in this operating manual or on the equipment must be
strictly followed to ensure the safety of the operating personnel
as well as the instrument.
If all the equipment is not handled in a manner specified by
the manufacturer, it might impair the protection provided by the
equipment.
STATUS LED DESCRIPTION
KEY OPERATION
To enter in parameter setting
For start/stop PID auto tuning Press
6 sec
Press 3 sec
+
To go in factory setting mode
PRESS KEY
FUNCTION
OPERATOR MODE
PARAMETER SETTING MODE
To set parameter value
To increment parameter value.
To decrement parameter value.
Set parameter to be save & exit.
WARNING GUIDELINES
WARNING : Risk of electric shock.
1. To prevent the risk of electric shock, power supply to the
equipment must be kept OFF while doing the wiring
arrangement. Do not touch the terminals while power is
being supplied.
2. To reduce electro magnetic interference, use wire with
adequate rating and twists of the same of equal size shall
be made with shortest connection.
3. Cable used for connection to power source, must have a
cross section of 1mm or greater. These wires should have
insulations capacity made of at least 1.5kV.
4. When extending the thermocouple lead wires, always use
thermocouple compensation wires for wiring for the RTD
type, use a wiring material with a small lead resistance
(5 max per line) and no resistance differentials among
three wires should be present.
5. A better anti-noise effect can be expected by using
standard power supply cable for the instrument.
Ω
INSTALLATION GUIDELINES
1. This equipment, being built-in-type, normally becomes a
part of main control panel and in such case the terminals
do not remain accessible to the end user after installation
and internal wiring.
2. Do not allow pieces of metal, wire clippings, or fine metallic
fillings from installation to enter the product or else it may
lead to a safety hazard that may in turn endanger life or
cause electrical shock to the operator.
3. Circuit breaker or mains switch must be installed between
power source and supply terminal to facilitate power ‘ON’
or ‘OFF’ function. However this mains switch or circuit
breaker must be installed at convenient place normally
accessible to the operator.
4. Use and store the instrument within the specified ambient
temperature and humidity ranges as mentioned in this
manual.
MECHANICAL INSTALLATION GUIDELINES
1. Prepare the panel cutout with proper dimensions as shown
above.
2. Fit the unit into the panel with the help of clamp given.
3. The equipment in its installed state must not come in close
proximity to any heating source, caustic vapors, oil steam,
or other unwanted process Byproducts.
4. Use the specified size of crimp terminal (M3.5 screws) to
wire the terminal block. Tightening the screws on the
terminal block using the tightening torque of the range of
1.2 N.m.
5. Do not connect anything to unused terminals.
MAINTENANCE
1. The equipment should be cleaned regularly to avoid blockage
of ventilating parts.
2. Clean the equipment with a clean soft cloth. Do not use
isopropyl alcohol or any other cleaning agent.
3. Fusible resistor must not be replaced by operator.
1
2
Tun
OUT
260
1 - Control output indication
2 - Auto tuning “ON” indication
Page 3
ERROR MEANING
When an error has occurred the display indicates error codes
as given below.
Check the sensor and the input wiring. If problem still exists,
replace the sensor. And still if problem is not solved yet by the
user, then please contact company person
Sensor is not connected or
Sensor connection is reversed
ERROR DISPLAY
FACTORY SETTING
PARAMETER RANGE
FACTORY SETTING
PARAMETER
IT
CT
Offset
PB
DT
MR
Hysteresis
VALUES
300
15 Sec
20.0°C
75
0°C
0°C
3°C
SR.
2
4
6
1
3
5
7
CORRECTIVE ACTION:
Over range condition or
sensor break
ENT
To ENTER BASIC
CONFIGURATION
SETTING, ENTER “73”
Message
Password
Output
Set Low Limit
Hysteresis
Set High Limit
Offset
Press key to save & exit
ENT
SET
Set Point Setting
Process Value
Press key for 3 sec to
enter password
Set Value
Set Point
Press key
Password Message
Basic Configuration
(S.S.R/Relay/Both)
SET
Control Action
(PID/ON-OFF)
Press + key
for 3 sec
yes
: Press key to apply factory set
values as shown in table.
: Press key to escape
from factory setting.
ENT
ENT
no
no
PB
IT
DT
CT
MR
OffSet
Hysteresis
0.0 to 999
0 to 999
0 to 999
SSR :1 to 99 Sec
-9°C to +9°C
-19°C to +19°C
1°C to 100°C
Parameter Range for J, K, PT100
Relay/Both :4 to 99 Sec Relay/Both :4 to 99 Sec
0.0 to 999
0 to 999
0 to 999
-9.0°C to +9.0°C
-19.0°C to +19.0°C
0.1°C to 100 °C
Range for PT.1
SSR :1 to 99 Sec
SET
Press key
PARAMETER SETTING
PARAMETER SETTING
Page 4
Specifications are subject to change, since development is a continuous process,
So for more updated operating information and Support,
Please contact our Helpline: 9978991476/9978991482/9978991474 or
Email at Ver:200206[email protected]
PARAMETER SETTING
CONTROL FUNCTION
RLY-OFF
RLY-ON
RLY-ON
RLY-ON
RLY-OFF
RLY-OFF
Temp.
S.V
HYST
Time
OFF OFF
ON - OFF control (Heating)
ON ON
ENT
Integral
time
Derivative
time
Cycle time
Manual Reset
SET
Password
Message
Proportional
Band
PID
Parameters
To ENTER CONTROL
PARAMETER
SETTING, ENTER “37”
Press key to save & exit
Control Parameter
SET
Press key
Auto Tuning:-
The Auto-tuning function automatically computes
and sets the Proportional band (Pb) , Integral time (It),
Derivative time (dt), and cycle time as per process
characteristics.
Tuning LED will turn “ON” during Auto-Tuning
If the power goes off before auto-tuning is completed,
auto-tuning will be restarted at next power ON.
PID AUTO-TUNING
Press key for 6 sec to start/stop
PID auto-tuning
Tun
.

Other MULTISPAN Temperature Controllers manuals

MULTISPAN UTC-113P User manual

MULTISPAN

MULTISPAN UTC-113P User manual

MULTISPAN TC-19 User manual

MULTISPAN

MULTISPAN TC-19 User manual

MULTISPAN UTC-222 User manual

MULTISPAN

MULTISPAN UTC-222 User manual

MULTISPAN UTC-1202G User manual

MULTISPAN

MULTISPAN UTC-1202G User manual

MULTISPAN UTC-4203 User manual

MULTISPAN

MULTISPAN UTC-4203 User manual

MULTISPAN UTC-4201A User manual

MULTISPAN

MULTISPAN UTC-4201A User manual

MULTISPAN TC-442 User manual

MULTISPAN

MULTISPAN TC-442 User manual

MULTISPAN UTC-320 User manual

MULTISPAN

MULTISPAN UTC-320 User manual

MULTISPAN TC-49P User manual

MULTISPAN

MULTISPAN TC-49P User manual

MULTISPAN UTC-421P User manual

MULTISPAN

MULTISPAN UTC-421P User manual

MULTISPAN TC-49 User manual

MULTISPAN

MULTISPAN TC-49 User manual

MULTISPAN UTC-2202G Instruction sheet

MULTISPAN

MULTISPAN UTC-2202G Instruction sheet

MULTISPAN UTC-121P User manual

MULTISPAN

MULTISPAN UTC-121P User manual

MULTISPAN TC-49P User manual

MULTISPAN

MULTISPAN TC-49P User manual

MULTISPAN UTC-121P User manual

MULTISPAN

MULTISPAN UTC-121P User manual

MULTISPAN UTC-4202G User manual

MULTISPAN

MULTISPAN UTC-4202G User manual

MULTISPAN UTC-221G User manual

MULTISPAN

MULTISPAN UTC-221G User manual

MULTISPAN UTC-221P User manual

MULTISPAN

MULTISPAN UTC-221P User manual

MULTISPAN UTC-214 User manual

MULTISPAN

MULTISPAN UTC-214 User manual

MULTISPAN UTC-2202 User manual

MULTISPAN

MULTISPAN UTC-2202 User manual

MULTISPAN UTC-121G User manual

MULTISPAN

MULTISPAN UTC-121G User manual

MULTISPAN UTC-423 User manual

MULTISPAN

MULTISPAN UTC-423 User manual

MULTISPAN UTC-421G User manual

MULTISPAN

MULTISPAN UTC-421G User manual

MULTISPAN UTC-321P User manual

MULTISPAN

MULTISPAN UTC-321P User manual

Popular Temperature Controllers manuals by other brands

Aegis Pavilion Control 410 Data brochure

Aegis

Aegis Pavilion Control 410 Data brochure

TREND T/PI installation instructions

TREND

TREND T/PI installation instructions

Oregon Scientific THGR328NH user manual

Oregon Scientific

Oregon Scientific THGR328NH user manual

Automarion24 TC6702 operating instructions

Automarion24

Automarion24 TC6702 operating instructions

Ekinex 71 Series Applications manual

Ekinex

Ekinex 71 Series Applications manual

Kiwi Lora Alliance Member LAS-603V1 user manual

Kiwi

Kiwi Lora Alliance Member LAS-603V1 user manual

Danfoss ECL Comfort 310 installation guide

Danfoss

Danfoss ECL Comfort 310 installation guide

Franke ZAQUA020 Installation and operating instructions

Franke

Franke ZAQUA020 Installation and operating instructions

Data Harvest 1100 quick start guide

Data Harvest

Data Harvest 1100 quick start guide

RKC INSTRUMENT RB700 manual

RKC INSTRUMENT

RKC INSTRUMENT RB700 manual

Uponor Climate Control Zoning System installation guide

Uponor

Uponor Climate Control Zoning System installation guide

Linear Technology DC1792A manual

Linear Technology

Linear Technology DC1792A manual

ELKATHERM FTRFB-280 Series manual

ELKATHERM

ELKATHERM FTRFB-280 Series manual

Thermon TC 816 Operation manual

Thermon

Thermon TC 816 Operation manual

TCNet Boiler Controller User and service manual

TCNet

TCNet Boiler Controller User and service manual

BriskHeat LYNX Quick start instruction manual

BriskHeat

BriskHeat LYNX Quick start instruction manual

Auber Instruments SWA-2441B instruction manual

Auber Instruments

Auber Instruments SWA-2441B instruction manual

Alula RE605 quick start guide

Alula

Alula RE605 quick start guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.