3 Operation, settings
Use of the sensor and configuration in the system separate manual for the control unit used.
3.1 Setting the detection range for presence detection
In order to use the presence detection in a targeted way, the detection range of the sensor can/
must be set independently of the spatial conditions 7.
1. Remove/insert or rotate one or both shutters where necessary.
2. By changing the shutter position, you can influence the detection range of the sensor direc-
tionally in order to prevent undesired presence detection.
3.2 Sensor button 3a
This button (2) executes different functions depending on the duration of activation.
1. Press the sensor button (SP) to test the DALI connection 1 press LED on, another press
LED off.
2. Press the sensor button (VLP) to start the reset. The LED flashes for approx. 10 s.
The unit is set back to the factory settings and all addresses are deleted.
4 Technical data
Function description Light and presence sensor for use in OSRAM DALI PRO
and DALIeco control systems
Connection cable 2 x 0.2…0.5 mm2
Ambient temperature -20 °C to +50 °C (operation)
Working range, light sensor 20 - 800 lux (directly on the sensor)
Protection class IP20
Power supply The unit is supplied from DALI
Voltage as per DALI standard IEC 62386
Power consumption approx. 6 mA
Installation height max. 5.0 m
Detection range max. Ø 7.0 m
Detection angle 40° - 90°
Detection range adjustable via shutter (min. 40° - max. 90°)
Installation height 2.0 m
Installation height 2.5 m
Installation height 3.0 m
Installation height 3.5 m
Max. installation height 5.0 m
Detection range Ø 1.5 m - 4.0 m
Detection range Ø 1.8 m - 5.0 m
Detection range Ø 2.0 m - 6.0 m
Detection range Ø 2.5 m - 7.0 m
Max. detection range Ø 7.0 m