The 8-zone Expansion Module (ZX8) is an interface between the control panels and any hardwired detection devices. The ZX8 connects to the control panel's combus
to provide eight additional hardwired inputs and one 50mA on-board PGM output.
Specifications
Installation
Connect the module as shown in Figure 1.
Table 1: Illustration
Table 2: Jumper Setting
Table 3: Options
Input voltage: Typically 12 to 16 Vdc No. of zones: 8 standard zone inputs
Current cons.: 28mA Oper. temperature: -20ºC to 50ºC (-4ºF to 122ºF)*
Max.# of ZX8: max.3: MG/SP Series Compatibility: Any Digiplex or Digiplex EVO series control panel
Any SP Series control panel (V2.0 or higher)
MG5000/MG5050 control panels (V2.0 or higher)
WinLoad Software V2.03 or higher
NOTE: For 1728/1738 compatibility, refer to the ZX8SP instruc-
tions.
No. of outputs: One 50mA PGM No. of inputs: 8 inputs
ADigiplex +Digiplex EVO
A “Locate” request coming from the control panel can be disabled by pressing the “Disable Locate”.
MG/SP Series
Press the “Disable Locate” for 3 seconds. Fast flash of the green LED occurs. Jumper settings can be changed.
BGreen “LOC” LED
Digiplex and Digiplex EVO
Remains Illuminated during power up
Flashes fast to indicate it is receiving a “Locate” request from the control panel.
To disable a “Locate” request, press the “Disable Locate” switch.
SP Series and MG5050
Flashes fast to indicate a change in jumper setting.
Red “WDG” LED
All panels flashes to indicate proper operation
If both “LOC” and the “WDG” LED are flashing alternately, the module is experiencing a communication failure with the control panel.
CConnect the detection devices to the ZX8 input terminals exactly as shown in the appropriate control panel’s Programming Guide.
DDigiplex and Digiplex EVO
Z8: Input terminal Z8 can be used as an anti-tamper switch input. Enable section [001] option [1]
MG/SP Series
Z1: Input terminal Z1 can be used as an anti-tamper switch input. Enable section [706] option [4] for panel+1,
option [5] for panel+9 and option [6] for panel+17
MG5000
(2 on-board zones)
MG5050
(5 on-board zones)
SP4000
(4 on-board zones)
SP5500
(5 on-board zones)
SP6000
(8 on-board zones)
SP65
(9 on-board zones)
SP7000
(16 on-board zones)
No/
ATZ
With/
ATZ
No/
ATZ
With/
ATZ
No/
ATZ
With/
ATZ
No/
ATZ
With/
ATZ
No/
ATZ
With/
ATZ
No/
ATZ
With/
ATZ
No/
ATZ
With/
ATZ
zones/ zones/ zones/ zones/ zones/ zones/ zones/z
A / Panel+1*
3-10 5-12 6-13 11-18 5-12 9-16 6-13 11-18 9-16 17-24 10-17 19-26 17-24 -
B / Panel+9* 11-18 13-20 14-21 19-26 13-20 17-24 14-21 19-26 17-24 25-32 18-25 27-32 25-32 -
C / Panel+17* 19-26 21-28 22-29 27-32 21-28 25-32 22-29 27-32 25-32 - 26-32 - - -
*Press “Disable Locate” for 3 seconds to change jumper setting
Programming Method
1. Hold [0] key+ [INSTALLER CODE]
2. Enter section [953] (DGP-848) [4003] (EVO)
3. Enter module’s 8-digit [SERIAL NUMBER]
4. Enter [SECTION] and turn desired option ON/OFF or enter the required data
Sections
[001]
Options
[1] Tamper Recognition OFF† = Disabled ON = Enabled (Z8)
[2] PGM Deactivation OFF† = Deact. Event ON = PGM timer
[3] PGM Normal State OFF† = N.O. ON = N.C.
[4] PGM Base time OFF† = 1 sec. ON = 1 min.
[002]-[016]
Even Numbered
Input Speed (Base Time Selection)
(Default = all inputs @ 600ms)
Even numbered sections represent inputs terminals Z1 to Z8. Using [q] and [p] keys. Select a Base Time value from 000 to 002. Press [ENTER].
000= Input Speed is X by 15 milliseconds.
001= Input Speed is X by 1 second.
002= Input Speed is X by 1 minute.
8-Zone Expansion Modules
ZX8
V6.0
Figure 1: ZX8 Connections
PARADOX.COM
Printed in Canada- 06/14
ZX8-EI04
Warranty
For complete warranty information on this product please refer to the Limited Warranty Statement found on the website www.parad ox.com/terms. Your use of the Paradox product signifies your acceptance of all warranty terms and conditions.
Magellan, Spectra SP, Digiplex and Digiplex EVO are trademarks or registered trademarks of Paradox Security Systems Ltd. or itsaffiliates in Canada, the United States and/or other countries. For the latest information on products approvals, such as UL a nd CE, please visit www.paradox.com. © 2014
Paradox Security Systems Ltd. All rights reserved. Specifications may change without prior notice. One or more of the following US patents may apply: 7046142, 6215399, 6111256, 6104319, 5920259, 5886632, 5721542, 5287111, 5119069, 5077549 and RE39406 and other pending patents may apply.
Canadian and international patents may also apply.
[003]-[017]
Odd Numbered
Input Speed (Time Value)
Odd numbered sections represent inputs Z1 to Z8. Enter a 3-digit decimal time value (000 to 255). Multiply by the Input Speed.
[018] PGM Timer
Enter a 3-digit decimal value (001-255). Multiply by the PGM Base Time Selection.
[019]
[020]
[021]
[022]
Activation Event*
__/__/__ Event Group
__/__/__ Feature Group
__/__/__ Start# Set the range within the Feature Group
__/__/__ End# Set the range within the Feature Group
[023]
[024]
[025]
[026]
Deactivation Event*
__/__/__ Event Group
__/__/__ Feature Group
__/__/__ Start# Set the range within the Feature Group
__/__/__ End# Set the range within the Feature Group
[030] PGM Test Mode
Activate PGM for 8 seconds to verify if the PGM is functioning properly.
[401] EOL/ATZ Options per Zone Input
By default, all options are configured as “0”. This means that all zone inputs will follow the global setting at panel section
[3033], options 7 and 8. However, if you change the value from 1 to 4, the inputs will follow the desired settings as shown below.:
Zone Input Option Individual Settings
[402] Selectable Input ResistorforEOLand Contact
Zone Input Option Individual Settings
Default Setting / *Only Event Groups 000 to 055 can be used. See PGM Table in the panel’s Programming Guide.
Programming Method
1. [ENTER] + [INSTALLER CODE]
2. Enter [SECTION]and turn desired option ON/OFF or enter the required data
[650] Tamper Recognition
[1] EOL Zones OFF= No EOLON = With EOL
[2] Tamper Recognition OFF= Disabled ON = Enabled (Z1)
[3] PGM Follows Global PGMOFF= Disabled ON = Enabled
[651] Zone Assignment
Enable zone inputs. Options [1] to [8], represent inputs Z1 to Z8.
[655] PGM Timer
__/__/__ 000 - 255 sec. 000 = Follow Deactivation Event.
[656] PGM Activation Event
__/__ Event Group [60]Tamper zone opened
[61]Tamper zone closed
__/__ Sub-Group [1]to [8] Zone input Z1 to Z8
retnE:desUtoNnoititraP__/__ [00]
[657] PGM Deactivation Event
__/__ Event Group [60]Tamper zone opened
[61]Tamper zone closed
__/__ Sub-Group [1]to [8] Zone input Z1 to Z8
retnE:desUtoNnoititraP__/__ [00]
Option Description
0 System default, zone will follow global panel settings for EOL and ATZ set in section [3033]. options 7 & 8.
1 No EOL, No ATZ
2 EOL enabled, No ATZ
3 No EOL, ATZ enabled
4 EOL enabled, ATZ enabled
Option EOL Value ZoneA Value Zone B Value(ATZ)
2K2K1K10
A/N5K12K21
A/N3K33K32
A/N7K47K43
A/N8K67K44
A/N7K42K25
A/N2K82K86

Other Paradox Control Unit manuals

Paradox APR3-HUB2 User manual

Paradox

Paradox APR3-HUB2 User manual

Paradox PGM82 User manual

Paradox

Paradox PGM82 User manual

Paradox VDMP3 User manual

Paradox

Paradox VDMP3 User manual

Paradox ZX22 User manual

Paradox

Paradox ZX22 User manual

Paradox ZX32D User manual

Paradox

Paradox ZX32D User manual

Paradox MG-RCV3 User manual

Paradox

Paradox MG-RCV3 User manual

Paradox IP150+ User manual

Paradox

Paradox IP150+ User manual

Paradox PCS300 User manual

Paradox

Paradox PCS300 User manual

Paradox IP150 User manual

Paradox

Paradox IP150 User manual

Paradox Spectra Digiplex NE APR3-HUB2 User manual

Paradox

Paradox Spectra Digiplex NE APR3-HUB2 User manual

Paradox IP150 User manual

Paradox

Paradox IP150 User manual

Paradox MAGELLAN RTX3 V1.5 User manual

Paradox

Paradox MAGELLAN RTX3 V1.5 User manual

Paradox Digiplex EVO PRT3 Installation manual

Paradox

Paradox Digiplex EVO PRT3 Installation manual

Paradox ZX16D User manual

Paradox

Paradox ZX16D User manual

Paradox MG-RCV3 User manual

Paradox

Paradox MG-RCV3 User manual

Paradox Digiplex APR-ADM2 User manual

Paradox

Paradox Digiplex APR-ADM2 User manual

Paradox Digiplex EVO PRT3 Installation manual

Paradox

Paradox Digiplex EVO PRT3 Installation manual

Paradox ZX82 User manual

Paradox

Paradox ZX82 User manual

Paradox IP150+ Operating instructions

Paradox

Paradox IP150+ Operating instructions

Paradox TM40 User manual

Paradox

Paradox TM40 User manual

Paradox IP180 User manual

Paradox

Paradox IP180 User manual

Paradox IMPERIAL DIGIPLEX EVO ACM24D User manual

Paradox

Paradox IMPERIAL DIGIPLEX EVO ACM24D User manual

Paradox VDMP3 User manual

Paradox

Paradox VDMP3 User manual

Paradox Digiplex EVO ZX8D User manual

Paradox

Paradox Digiplex EVO ZX8D User manual

Popular Control Unit manuals by other brands

BOC Edwards EXDC Series instruction manual

BOC Edwards

BOC Edwards EXDC Series instruction manual

Digilent ChipKIT PRO Reference manual

Digilent

Digilent ChipKIT PRO Reference manual

CMX VS-C203 Installation and operation manual

CMX

CMX VS-C203 Installation and operation manual

jbc MSE-A instruction manual

jbc

jbc MSE-A instruction manual

RTimes X501M product manual

RTimes

RTimes X501M product manual

Afag Compact Slide CS 8 Translation of the Original Montage Instructions

Afag

Afag Compact Slide CS 8 Translation of the Original Montage Instructions

tau D727M installation guide

tau

tau D727M installation guide

AVL DITEST VAS 6356 operating manual

AVL DITEST

AVL DITEST VAS 6356 operating manual

Leister DSE operating instructions

Leister

Leister DSE operating instructions

IBA ibaMS4xAI-380VAC manual

IBA

IBA ibaMS4xAI-380VAC manual

Vag GA INDUSTRIES Figures 251-D Installation, operation and maintenance manual

Vag

Vag GA INDUSTRIES Figures 251-D Installation, operation and maintenance manual

Mitsubishi Electric QD75P1N user manual

Mitsubishi Electric

Mitsubishi Electric QD75P1N user manual

Mod 30ML Demonstration Guide

Mod

Mod 30ML Demonstration Guide

Lawler 4000 Series Installation & maintenance manual

Lawler

Lawler 4000 Series Installation & maintenance manual

nvent ERICO Plus quick start guide

nvent

nvent ERICO Plus quick start guide

Espressif Systems ESP32-WROOM-32E user manual

Espressif Systems

Espressif Systems ESP32-WROOM-32E user manual

ICP DAS USA PROFIBUS PROFI-2510 quick start

ICP DAS USA

ICP DAS USA PROFIBUS PROFI-2510 quick start

Uniteck UNISUN Series manual

Uniteck

Uniteck UNISUN Series manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.