INSTRUCTIONS
FIELD-ADJUSTABLE TOMO™ INSTALLATION
RAB Lighting is committed to creating high-quality, aordable, well-designed and energy-ecient LED lighting and controls that make it easy for electricians to install
and end users to save energy
. W
e’
d love to hear your comments. Please call the Marketing Depar
tment at 888-RAB-1000 or email: mark
[email protected]WIRING OPERATION
MAINTENANCE
TROUBLESHOOTING
Note: These instructions do not cover all details or variations in equipment
nor do they provide for every possible situation during installation,
operation or maintenance.
LIGHT
FIXTURE
INSIDE FIXTURE
BATTERY
Pink/DIM–
Black/Switched Line
Green/Ground
White/Neutral
Black/Unswitched Line
Purple/DIM+
BACKUP
DRIVER
BATTERY
CONNECTOR:
CONNECT
ONLY AFTER
AC SUPPLY
POWER IS
CONNECTED
BATTERY BACKUP MODELS
TOMO - IN - 0823 RAB WARRANTY: RAB’s warranty is subject to all terms and conditions found at rablighting.com/warranty.
Easy Answers
rablighting.com
Visit our website for product info
Tech Help Line
Call our experts: 888 722-1000
e-mail
Answered promptly - sales@rablighting.com
Free Lighting Layouts
Answered online or by request
© 2022 RAB LIGHTING Inc.
Fig: 13
CAUTION: FOR BATTERY BACKUP FIXTURE (TOMO-4/TOMO-8)
Voltage could be present in BATTERY. To prevent high voltage
from being present on output leads, Inverter Connector must
be open. Do not join BATTERY connector until installation is
complete and AC power is supplied to the emergency driver
(Fig. 13).
NOTE: Make sure that the necessary branch circuit wiring is
available. An UNSWITCHED AC source of power is required. The
emergency driver must be fed from the same branch circuit as the
LED driver.
CAUTION: Do not use any supply voltage other than 120-277V
50/60 HZ.
1. Connect UNSWITCHED HOT HOT AC supply
line.
2. If using an UNSWITCHED circuit, connect UNSWITCHED
and SWITCHED lines together.
3. If using a SWITCHED circuit, connect SWITCHED HOT AC
xture lead to the external control.
4. For 0-10V dimming, connect DIMDIM
(-) pink lead to 0-10V dimmer connections.
5. Connect GROUND
ground. Do not connect GROUND to the output leads.
6. All unused leads must be capped and insulated.
7. After installation is complete, supply AC power to the
BATTERY (Fig. 13).
8.
Charging Indicator Light should illuminate to indicate the
battery is charging.
9. Once the BATTERY has charged for at least one hour, a
short duration test may be performed by pressing the test
button.
10. After the battery has charged for 24 hours, a long duration
1. When AC power is applied, the charging indicator light
is illuminated indicating that the BATTERY is being
charged.
2. When power fails, the standby power automatically
switches to backup mode at reduced power resulting in
lower illumination. The emergency driver supplies power
in standby mode for a minimum of 90 minutes.
3. When AC power is restored, the emergency driver
automatically returns to charging mode.
1.
2. If the charging indicator light does not illuminate after
pressing the Test Button (Fig. 14), check if battery is
connected properly.
Although no routine maintenance is required to keep the
emergency driver functional, it should be checked periodically
to ensure that it is working. The following schedule is
recommended:
1. Visually inspect the charging indicator light monthly. It
should be illuminated.
2.
intervals for a minimum of 30 seconds.
3. Conduct a 90-minute discharge test once a year. Fixture
would operate at reduced illumination for a minimum of
90 minutes.
P-100173
Fig: 14
Test Button