Classification
Sprinkler
Rating
Maximum Ambient
Temperature Frame
Color
°F °C °F °C
Ordinary
Intermediate
High
165
212
286
74
100
141
100
150
225
38
66
107
Uncolored
White
Blue
Temperature Ratings
Design Criteria
cULus Listing Requirements
The Reliable Standard Response J168 Upright Sprinkler is
cULus Listed for use in occupancy classifications up to and
including Extra-Hazard, for hydraulically calculated wet or dry
systems per NFPA 13, with a minimum operating pressure of
7 psi (48,3 kPa) in wet or dry systems. Use the standard
sprinkler positioning requirements and density/area sprinkler
protection criteria provided in NFPA 13.
Also:
The J168 Sprinkler is cULus Listed for use in High-Piled
storage Occupancies as defined in NFPA 13. This sprinkler
may be used for the protection of solid piled, palletized, rack
storage (single, double, multiple-row and portable), bin box,
and shelf storage including, but not limited to: encapsuled or
unencapsulated Class I-IV and Group A or B plastics,
cartoned, expanded or unexpanded, as well as exposed
unexpanded. For hydraulically calculated wet or dry systems
per NFPA 13 with a minimum operating pressure of 7 psi (0,5
bar). Use the standard sprinkler positioning requirements and
density/area sprinkler protection criteria provided in NFPA 13
for High-Piled Storage Occupancies.
FM Approval Requirements
The Reliable Standard Response J168, K-16.8 Upright
Sprinkler is approved to be installed as an area/density in
accordance with FM guidelines. (FM guidelines may be
different from UL and C-UL Listing criteria).
Examples of High-Piled Storage without in rack sprinklers:
1. NFPA 13 provides ceiling-only protection (no in-rack
sprinklers) criteria using open frame (no solid shelves)
single, double, multiple-row, or portable rack storage
(without the need for in-rack sprinkler protection) of
cartoned or uncartoned unexpanded Group A or B
plastics, or, cartoned expanded Group A or B plastics,
with:
•Astorageheightofupto20ft(6,1m)
•A maximum ceiling height of 27 ft (8,2 m)
•A minimum deflector to top of storage clearance of 18"
(457 mm)
•A minimum design density of .60 gpm/ft2(24,4
mm/min)
•A minimum operating pressure of 7 psi (0,5 bar)
•A minimum design area of 2,000 ft2(186 m2)forwet
systems or 2,600 ft2(242 m2) for dry systems
Note: The J168 Sprinkler can be used in any
application or building height as allowed by NFPA13
or FM guidelines. The J168 is a standard response
standard spray sprinkler with a larger K factor to
provide greater water flows at lower pressures.
2. NFPA 13 provides ceiling-only protection (no in-rack
sprinklers) criteria using open frame (no solid shelves)
single, double, multiple-row, or portable rack storage
(without the need for in-rack sprinkler protection) of
cartoned or uncartoned unexpanded Group A or B
plastics, with:
•Astorageheightofupto25ft(7,6m)
•A maximum ceiling height of 30 ft (9,1 m)
•A minimum deflector to top of storage clearance of 18"
(457 mm)
•A minimum design density of .80 gpm/ft2(32,6
mm/min)
•A minimum operating pressure of 7 psi (0,5 bar)
•A minimum design area of 2,000 ft2(186 m2)forwet
systems or 4,500 ft2(418 m2) for dry systems
Refer to NFPA 13 for specific requirements for various
combinations of building heights, storage heights,
sprinkler- to-commodity clearance, storage arrangements,
commodity classifications, and lesser or greater required
design densities.
Note: This sprinkler is a Control Mode Sprinkler.
Special Application Finishes
Lead Plated 165°F(74°C), 212°F (100°C) and 286°F (141°C)
Temp. Ratings
Wax-Coated (1)(2) 165°F(74°C) Clear Wax, 212°F (100°C) Brown Wax.
Wax-Coated Over
Lead Plated (1)(2) 165°F(74°C) Clear Wax, 212°F (100°C) Brown Wax.
(1) 212°F (100°C) brown wax may be used on 286°F (141°C)
sprinklers when maximum ambient temperatures do not exceed
150°F (66°C).
(2) Not FM Approved.
2.
Caution: The Reliable Standard Response J168 Upright
Sprinkler must be installed and maintained per the
application NFPA standards, as well as the standards of
other authorities having jurisdiction.