MC16-PAC-4-KIT Installation Manual 2023-01-17
1/2
Roger Access Control System
MC16-PAC-3-KIT and MC16-PAC-4-KIT Installation Manual
Controller Firmware version: 1.7.4 or newer
Product version: 2.0
Document version: Rev. D
This document contains minimum information that is necessary for initial setup
and installation of the kit. The detailed description of configuration parameters
and functionalities of all components is specified in respective Operating
manuals available at www.roger.pl.
INTRODUCTION
MC16-PAC-3-KIT is designed to control three doors while MC16-PAC-4-KIT is
designed to control four doors in RACS 5 system. All doors can be read-in or
read-in/out type when equipped with MCT series readers or OSDP-RS485
interface readers including OSR series readers. The kit includes respectively
MC16-PAC-3 or MC16-PAC-4 access controller, MCX4D expander and ME-16
metal box with PS4D power supply unit. The box is adapted to installation of
17Ah battery for emergency supply. All elements of controlled door including
readers and door locks can be supplied from the kit.
CONFIGURATION WITH ROGERVDM PROGRAM
Low level configuration with RogerVDM software enables to define basic
parameters of MC16 controller i.e. IP address and communication key.
MC16 programming procedure (RogerVDM):
1. Connect the controller to Ethernet network and define the IP address of your
computer in the same subnetwork as the controller with 192.168.0.213
default IP address.
2. Start RogerVDM program, select MC16 v1.x device, the latest firmware
version and Ethernet communication channel.
3. Select from the list or enter manually the IP address of controller, enter 1234
communication key and start the connection with the controller.
4. In the top menu select Tools and then Set communication key to define your
own password for the controller.
5. In the main window specify your own IP address of the controller.
6. Optionally enter comments for controller and its object to facilitate their
identification during further configuration of the system.
7. Optionally backup settings clicking Send to File…
8. Click Send to Device to update the configuration of controller and disconnect
by selection of Device in the top menu and then Disconnect.
Note: Initial low level configuration of MC16 controller in RACS 5 v2 system
should be made with RogerVDM program, but further modification of low level
configuration for MC16 controller and connected MCT/MCX peripheral devices
can be made with VISO v2 program.
CONFIGURATION WITH VISO PROGRAM
High level configuration with VISO software enables to define the logic of
controller. More information is given in MC16 Operating manual and AN006
application note.
MEMORY RESET
Memory reset procedure resets all settings to default ones and results in
192.168.0.213 IP address and empty communication key.
MC16 memory reset procedure:
1. Disconnect power supply
2. Short CLK and IN4 lines.
3. Restore power supply, all LEDs will flash and wait min. 6s.
4. Remove connection between CLK and IN4 lines, LEDs will stop pulsating and
LED2 will be on.
5. Wait approx. 1.5 min till LED5+LED6+LED7+LED8 are pulsating.
6. Restart the controller (switch power supply off and on)
7. Start RogerVDM and make low level configuration.
FIRMWARE UPDATE
New firmware can be uploaded to the controller with RogerVDM software or
VISO v2 software. The latest firmware file is available at www.roger.pl.
MC16 firmware update procedure (RogerVDM):
1. Connect with the controller using RogerVDM software.
2. Backup settings by clicking Send to File…
3. In the top menu select Tools and then Update firmware.
4. Select firmware file and then click Update.
5. After firmware update wait till LED8 is pulsating.
6. Make or restore low level configuration in RogerVDM software.
Note: During the firmware update process, it is necessary to ensure continuous
and stable power supply for the device. If interrupted, the device may require
repair by Roger.
POWER SUPPLY
The kit is supplied from PS4D power supply unit. The metal box offers space for
installation of typical 17Ah backup battery which can be connected to BAT+ and
BAT- terminals of MCX4D expander.
Fig. 1 MC16-PAC-3-KIT or MC16-PAC-4-KIT
The installation can be done only by qualified person with all
necessary certificates concerning connection and maintenance
of 230VAC and low voltage networks.
Prior to starting the installation it is necessary to ensure that
230 VAC circuit is disconnected. All works inside the box must
be carried out with 230VAC supply voltage disconnected.
It is forbidden to use the kit without properly executed and
operational earthing system.
TAMPER DETECTOR
The metal box is equipped with door contact which can be connected to one of
the inputs (e.g. IN8) and GND terminal of the controller. The anti-sabotage
function can be assigned to the input with VISO program.
APPENDIX
Table 1. MC16 screw terminals
Name
Description
BAT+, BAT-
Not used in kit
AC, AC
Controller power supply
AUX-, AUX+
Controller power supply
TML-, TML+
Not used in kit
IN1-IN8
Input lines
GND
Ground
OUT1-OUT6
15VDC/150mA transistor output lines
A1,B1
RS485 bus
CLK, DTA
Not used in kit
A2,B2
Not used
NO1, COM1, NC1
30V/1.5A DC/AC (REL1) relay
NO2, COM2, NC2
30V/1.5A DC/AC (REL2) relay
Table 2. MCX4D screw terminals
Name
Description
BAT+, BAT-
Backup battery
VIN+, VIN-
13.8VDC input power supply
AUX+, AUX-
13.8VDC/0.2A output power supply (for general
purpose)
VOUT+, VOUT-
13.8VDC/0.2A output power supply (for controller)
A, B
RS485 bus (for controller)
MC16-PAC-4-KIT Installation Manual 2023-01-17
2/2
Ax, Bx
RS485 bus (for readers)
TMLx+, TMLx-
13.8VDC/0.2A output power supply (for readers)
VDRx+, VDRx-
13.8VDC/1.0A output power supply (for door lock)
LCKx
15VDC/1A transistor output line (door lock)
BELLx
15VDC/1A transistor output line (alarm signalling
device)
DCx
Input line (door contact)
DRx
Input line (exit button)
Table 3. MC16 LED indicators
Name
Description
LED1
Normal mode
LED2
ON: Service mode (low level configuration)
Pulsing: RAM or Flash SPI memory error
LED3
ON: High level configuration error
Pulsing: Low level configuration error
LED4
No memory card or memory card error
LED5
Event log error
LED6
Not used
LED7
Not used
LED8
Pulsating: Proper functioning of the controller
Table 4. Specification
Supply voltage
230VAC, 50/60Hz (-15%÷+10%)
Power supply
PS4D 13.8VDC/5.4A
Short circuit and
overload protection
Yes
Metal box
DC01 0.7mm metal sheet, grey anthracite colour
(RAL7016)
Tamper protection
NO/NC detector, 50VDC/50mA
Distances
RS485: up to 1200m
Power supply: according to AN022 application note
IP Code
IP20
Environmental class
(acc. to EN 50133-1)
Class I, indoor general conditions, temperature:
+5°C to +40°C, relative humidity: 10 to 95% (no
condensation)
Dimensions H x W x D
305 x 325 x 100 mm
Weight
3.2 kg
Certificates
CE
Fig. 2 Typical control of doors with MCT readers
Notes:
•MC16 power supply should be ensured as in fig. 2. If VOUT+ terminal of the
expander is connected incorrectly i.e. to the other AC terminal of MC16
controller then LED AC indicator on controller’s board will be switched off.
•All MCT readers connected to the MC16 controller via MCX4D expander must
have unique addresses on RS485 bus in range of 101-115 (assuming that
expander is operated with default ID=100 address). In RACS 5 v2 system, all
addressing of MCT/MCX devices can be made remotely from VISO v2
software during system start-up.
•In case of OSDP interface readers including OSR series readers it is
necessary to install MCI-3 interfaces on RS485 bus.
•In case of read-in door, single reader is connected to the controller within
particular door.
•Diagrams include doors with electric strikes. In case of electromagnetic lock,
the polarity of LCKx output must be changed within low level configuration of
MCX4D expander.
•Diagrams include exit buttons. In case of read-in/out doors they can be used
for emergency door opening.
•In case of 17Ah backup battery it is recommended to configure 600mA battery
charging current by means of jumper on MCX4D board.
•If MC16 controller is supplied from MCX4D expander which is typical in case of
MC16-PAC-3-KIT and MC16-PAC-4-KIT then it is recommended not to use
TML+ and AUX+ outputs of MC16 controller.
Note: The device has an Ethernet network communication interface. In principle,
the device can be used in both WAN and LAN, while the manufacturer's warranty
is covered only for operation in an isolated LAN reserved exclusively for the
access control system or other system in which the device is to be used.
This symbol placed on a product or packaging indicates that the
product should not be disposed of with other wastes as this may
have a negative impact on the environment and health. The user is
obliged to deliver equipment to the designated collection points of
electric and electronic waste. For detailed information on recycling,
contact your local authorities, waste disposal company or point of
purchase. Separate collection and recycling of this type of waste
contributes to the protection of the natural resources and is safe to
health and the environment. Weight of the equipment is specified in
the document.
Contact:
Roger Sp. z o. o. sp. k.
82-400 Sztum
Gościszewo 59
Tel.: +48 55 272 0132
Fax: +48 55 272 0133
Tech. support: +48 55 267 0126
E-mail: support@roger.pl
Web: www.roger.pl

Other manuals for MC16-PAC-3-KIT

1

This manual suits for next models

1

Other Roger IP Access Controllers manuals

Roger MCT88M-IO User manual

Roger

Roger MCT88M-IO User manual

Roger PR402DR User manual

Roger

Roger PR402DR User manual

Roger MCT68ME-IO-I User manual

Roger

Roger MCT68ME-IO-I User manual

Roger RFT1000 Use and care manual

Roger

Roger RFT1000 Use and care manual

Roger PR102DR User manual

Roger

Roger PR102DR User manual

Roger PRT12MF-DES User manual

Roger

Roger PRT12MF-DES User manual

Roger MC16-PAC-EX/ST-2-KIT User manual

Roger

Roger MC16-PAC-EX/ST-2-KIT User manual

Roger MC16 User manual

Roger

Roger MC16 User manual

Roger PR611-VP User manual

Roger

Roger PR611-VP User manual

Roger MCT82M-IO-CH User manual

Roger

Roger MCT82M-IO-CH User manual

Roger MCT82M-IO-HR-F User manual

Roger

Roger MCT82M-IO-HR-F User manual

Roger PR201 Assembly instructions

Roger

Roger PR201 Assembly instructions

Roger MCT88M-IO User manual

Roger

Roger MCT88M-IO User manual

Roger MC16-PAC-16 User manual

Roger

Roger MC16-PAC-16 User manual

Roger MCT86M-IO-CH-HR User manual

Roger

Roger MCT86M-IO-CH-HR User manual

Roger PRT62MF User manual

Roger

Roger PRT62MF User manual

Roger PR402DR User manual

Roger

Roger PR402DR User manual

Roger RKD32 User manual

Roger

Roger RKD32 User manual

Roger RFT1000 User manual

Roger

Roger RFT1000 User manual

Roger EDGE1 Series Product manual

Roger

Roger EDGE1 Series Product manual

Roger PR402DR-BRD User manual

Roger

Roger PR402DR-BRD User manual

Roger MCT68ME User manual

Roger

Roger MCT68ME User manual

Roger RFT1000 User manual

Roger

Roger RFT1000 User manual

Roger PR622 User manual

Roger

Roger PR622 User manual

Popular IP Access Controllers manuals by other brands

Navkom Biohandle user manual

Navkom

Navkom Biohandle user manual

H3C WX5002 Compliance and Safety Manual

H3C

H3C WX5002 Compliance and Safety Manual

ACT PRO MIFARE CLASSIC READERS Operating and installation instructions

ACT

ACT PRO MIFARE CLASSIC READERS Operating and installation instructions

Siemens ADE5300 installation manual

Siemens

Siemens ADE5300 installation manual

TCS codelock12 Product information

TCS

TCS codelock12 Product information

ZKTeco LockerPad-7B user manual

ZKTeco

ZKTeco LockerPad-7B user manual

Alcad 969 Series manual

Alcad

Alcad 969 Series manual

Door-Gard LS2 Programming manual

Door-Gard

Door-Gard LS2 Programming manual

eKey home Series operating instructions

eKey

eKey home Series operating instructions

Holars AS H-TAG user manual

Holars AS

Holars AS H-TAG user manual

CDVI GALEOR installation manual

CDVI

CDVI GALEOR installation manual

xpr B100PROX-EH-SA v2 Installer manual

xpr

xpr B100PROX-EH-SA v2 Installer manual

ZKTeco ZKX5030A user manual

ZKTeco

ZKTeco ZKX5030A user manual

RBH Access Technologies Integra 32 UNC100 manual

RBH Access Technologies

RBH Access Technologies Integra 32 UNC100 manual

3MillID 3M Inline installation guide

3MillID

3MillID 3M Inline installation guide

Dahua DHI-ASI7213Y-V3-T1P user manual

Dahua

Dahua DHI-ASI7213Y-V3-T1P user manual

Paxton Access PROXIMITY P Series instructions

Paxton Access

Paxton Access PROXIMITY P Series instructions

ZKTeco F17 installation guide

ZKTeco

ZKTeco F17 installation guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.