2EOL/NO type 2EOL/NO input can be in normal, triggered, tamper (sabotage) or
malfunction state. In normal state CAcontacts are opened, while
CTamp contacts are closed. Input triggering is caused by CA
contacts closing. CTamp contacts opening is recognized as the
tamper (sabotage) state. Input shorting to the ground is recognized
as the malfunction state.
Fig. 8 2EOL/NO input type
2EOL/NC type 2EOL/NC input can be in normal, triggered, tamper (sabotage) or
malfunction state. In normal state CAand CTamp contacts are
closed. Input triggering is caused by CA contacts opening. CTamp
contacts opening is recognized as the tamper (sabotage) state.
Input shorting to the ground is recognized as the malfunction state.
Fig. 9 2EOL/NC input type
3EOL/NO type 3EOL/NO input can be in normal, triggered, masking, triggered with
masking, tamper (sabotage) or malfunction state. In normal state
CAand CBcontacts are opened while CTamp contacts are closed.
Input triggering is caused by CA contacts closing. CBcontacts
closing is recognized as the masking state. Simultaneous closing of
CAand CBcontacts is recognized as the triggered with masking
state. CTamp contacts opening is recognized as the tamper
(sabotage) state. Input shorting to the ground is recognized as the
malfunction state.
Fig.10 3EOL/NO input type
3EOL/NC type 3EOL/NC input can be in normal, triggered, masking, triggered with
masking, tamper (sabotage) or malfunction state. In normal state
CA, CBand CTamp contacts are closed. Input triggering is caused by
CA contacts opening. CBcontacts opening is recognized as the
masking state. Simultaneous opening of CAand CBcontacts is
recognized as the triggered with masking state. CTamp contacts
opening is recognized as the tamper (sabotage) state. Input
shorting to the ground is recognized as the malfunction state.
Fig. 11 3EOL/NC input type