Satel INT-ADR User manual

INT-ADR
ADDRESSABLE ZONE EXPANDER
int-adr_en 05/14
The INT-ADR expander allows you to expand the system by adding up to 48 addressable
zones. It supports detectors in which the CA-64 ADR-MOD addressable module is installed.
The expander works with INTEGRA, INTEGRA Plus and CA-64 control panels.
If the expander is connected to the CA-64 alarm control panel, connecting any
other modules to the control panel to expand the system by additional zones is
impossible.
1. Features
Up to 48 addressable zones.
Support for NO and NC type detectors with CA-64 ADR-MOD module installed.
NC type tamper input.
Capable of being integrated with dedicated power supply unit (operation in "expander with
power supply" mode).
Connectable to RS-485 bus (firmware update through the bus).
2. Electronics board
Explanations to Fig. 1:
DIP-switches (see: DIP-
SWITCHES
).
connector for a dedicated power supply unit (e.g. APS-412).
STS LED indicating the status of power supply connected to the connector:
ON – power supply is working normally,
blinking – power supply is reporting a trouble.

2 INT-ADR SATEL
LED indicating the status of communication with the control panel:
ON – no communication with the control panel,
blinking – communication with the control panel OK.
Description of terminals:
POW - +12 V DC dedicated power supply output for CA-64 ADR-MOD addressable
modules and detectors.
COM - common ground.
INT - data input from CA-64 ADR-MOD addressable modules.
ZA, ZB - terminals for future applications.
TMP - tamper input (NC) – if not used, it should be shorted to the common ground.
CLK - clock (expander communication bus).
DAT - data (expander communication bus).
+12V - +12 V DC power input / output.
Do not connect power to the terminals, if the dedicated power supply unit is
connected to the connector on electronics board.
A, B - RS-485 bus.
3. DIP-switches
The DIP-switches 1-5 are used for address setting. A numerical value is assigned to each
switch. In OFF position, the value is 0. Numerical values assigned to individual switches in
ON position are shown in Table 1. The sum of numerical values assigned to switches 1-5
means the address set on the module. The address must be different from that on the other
modules connected to the communication bus of the control panel.
DIP-switch number 1 2 3 4 5
Numerical value 1 2 4 8 16
Table 1.
The switch 10 allows you to define how the expander will be identified by the control panel
(see: Table 2) and how many addresses it will take up in the system. If the switch is set to the
ON position, the expander will take up 6 addresses (the address set in the expander and 5
subsequent ones). At the same time, 48 zones will be reserved in the system for the
expander. If the switch is set to the OFF position, the expander can take up from 1 to 6
addresses and at the same time reserve from 8 to 48 zones (1 address = 8 zones). The
number of occupied addresses and reserved zones depends on the number of connected
addressable modules and addresses set in them (see: Table 3). Consecutive sequence of
addresses must be maintained and any gaps must be avoided, because one module with an
address out of a group of 8 addresses suffices to reserve 1 address and 8 zones.
Identification of device
expander w/o power supply expander with power supply
ON INT-ADRPS / CA-64 ADR
DIP-switch position OFF INT-ADR INT-ADRPS / CA-64 ADR
Table 2.

SATEL INT-ADR 3
Notes:
The expander will be identified as INT-ADR / INT-ADRPS by INTEGRA / INTEGRA Plus
control panels with firmware version 1.12 or newer.
The switch 10 must be set in ON position, if the expander is connected to the following
control panels:
CA-64,
INTEGRA / INTEGRA Plus with a firmware version older than 1.12, if the dedicated
power supply is not connected to the onboard connector.
If the switch is set in OFF position, the control panel will not be able to identify the
expander.
If the dedicated power supply is not connected to the onboard connector and the
expander has been identified as INT-ADRPS / CA-64 ADR, no power supply related
troubles will be reported.
Leave a suitable number of free addresses for the expander. If it turns out during
identification that the addresses required for the expander are already occupied, the
identification will fail (the control panel will inform you that two devices have the same
address).
Addresses of CA-64 ADR MOD modules Addresses for expander in the system
0-7 address set on DIP-switches
8-15 address set on DIP-switches +1
16-23 address set on DIP-switches + 2
24-31 address set on DIP-switches + 3
32-39 address set on DIP-switches + 4
40-48 address set on DIP-switches + 5
Table 3.
Fig. 2 shows some examples of DIP-switches settings.
4. Installation and start-up
Disconnect power before making any electrical connections.

4 INT-ADR SATEL
The expander is designed for indoor installation.
1. Fasten the expander electronics board in the enclosure.
2. Using the DIP-switches, set the suitable expander address and define how it is to be
identified.
3. Connect the CLK, DAT and COM terminals to the corresponding terminals of the control
panel communication bus (see: installer manual for alarm control panel). It is
recommended that an unshielded non-twisted cable be used to make the connection. If
you use the twisted-pair type of cable, remember that CLK (clock) and DAT (data) signals
must not be sent through one pair of twisted conductors. The conductors must be run in
one cable.
4. If the expander is to supervise the enclosure tamper contact, connect the wires of tamper
contact to the TMP and COM terminals. If the expander is not to supervise the enclosure
tamper contact, connect the TMP terminal to the expander COM terminal.
5. Connect the addressable detectors to the expander (see: C
ONNECTING ADDRESSABLE
DETECTORS
).
6. Depending on the selected method of expander powering, connect the dedicated power
supply unit to the connector on expander electronics board or connect the power leads to
the +12V and COM terminals (the expander may be powered directly from the control
panel, from an expander with power supply or from a power supply unit).
The expander must not be powered from both sources at the same time.
7. Power on the alarm system.
8. Start the identification function in the control panel. After the expander is identified, the
addressable zones will be given corresponding numbers in the alarm system (see:
N
UMBERING ADDRESSABLE ZONES
). The control panel monitors presence of the identified
modules. If the module is disconnected from communication bus, position of DIP-switches
is changed, or the device is replaced with another one with DIP-switches set in the same
way, a tamper alarm will be triggered.
Note: The status of addressable zones is read out by the expander every 200 ms. When
programming the zone sensitivity, do not enter any values lower than 200 ms.
5. Connecting addressable detectors
Addressable detector is a detector with the CA-64 ADR-MOD module installed. Dimensions
of the module enable it to be mounted inside the detector enclosure.
The maximum distance between the addressable detector and the expander may be up to
1000 m. Table 4 shows requirements for the common ground wires if 0.5 mm dia. conductors
are used.
Distance to expander Number of conductors connected in parallel
up to 200 m 1
200-400 m 2
400-600 m 3
600-1000 m 4
Table 4.
The addressable modules and detectors should be powered from the POW output of the
expander. Where the sum of currents drawn by the addressable modules and detectors
exceeds the output current of power supply unit connected to the expander, the detectors
may be powered from another source (but not the addressable modules).

SATEL INT-ADR 5
Use separate conductors to connect the power common for addressable modules and the
power common for detectors.
Connect to one of the detector alarm output terminals the same common ground which is
connected to the addressable module. Connect the other terminal of alarm output to the blue
wire of the addressable module.
The detector tamper contact can be connected to a separate tamper circuit (the addressable
zone should be programmed as NO or NC) or can be connected in series into the power
circuit of addressable module (the addressable zone should be programmed as 2EOL/NO or
2EOL/NC).
Figure 3 shows how the addressable modules and detectors should be connected to the
expander when the status of detector tamper contacts is to be monitored by the expander.
The wires of addressable module are marked in the figure as follows:
W – white wire (common ground),
B – black wire (data output),
A – blue wire (detector status supervision input),
R – red wire (power input).

6 INT-ADR SATEL
6. Numbering addressable zones
The number of addressable zone depends on the address set in the CA-64 ADR-MOD
module. To set the address, use the DIP-switches. A numerical value is assigned to each
switch. In the OFF position, the value is 0. Numerical values assigned to individual switches
in the ON position are shown in Table 5. The sum of numerical values assigned to switches
1-6 denotes the address set in the module. Addresses from the 0-47 range should be set.
Modules with higher addresses are not supported. A different address must be set in each
module. Setting the same address in two modules will result in two addressable detectors
being assigned to the same zone.
DIP-switch number 1 2 3 4 5 6
Numerical value 1 2 4 8 16 32
Table 5.
Notes:
The INTEGRA 24 control panel may be expanded by up to 16 addressable zones (set the
addresses within the 0-15 range).
The INTEGRA 32 control panel may be expanded by up to 24 addressable zones (set the
addresses within the 0-23 range).
Figure 4 shows examples of setting addresses in the CA-64 ADR-MOD modules.
Interfacing with the CA-64 control panel
To determine the number which will be assigned to an addressable zone in the system, add
the number 17 to the address set in the CA-64 ADR-MOD module.
Interfacing with the INTEGRA / INTEGRA Plus control panel
The INTEGRA control panels have different number of zones on their mainboard. To the
INTEGRA / INTEGRA Plus control panel, it is possible to connect other modules to expand
the number of zones, in addition to the INT-ADR expander. The zones in expanders with
lower addresses are given lower numbers than those in expanders with higher addresses.
The above mentioned factors have an effect on numbering of the addressable zones. For
example, if two INT-E zone expanders (2 x 8 zones) with lower addresses than the address
set in the INT-ADR expander are connected to the INTEGRA128 control panel (16 zones),
numbers from 33 up will be assigned to the addressable zones.
7. Updating the expander firmware
Using the RS-485 bus, connect the expander to the ACCO-USB converter, and then connect
the converter to the computer (see: ACCO-USB converter manual). You can find a program
for updating the expander firmware and a detailed description of the firmware update
procedure on the www.satel.eu website.

SATEL INT-ADR 7
8. Specifications
Supply voltage ................................................................................................... 12 V DC ±15%
Standby current consumption ..........................................................................................30 mA
Maximum current consumption........................................................................................35 mA
+12V output rating ............................................................................................ 2.5 A / 12 V DC
POW output rating ............................................................................................ 2.5 A / 12 V DC
Environmental class according to EN50130-5 ......................................................................... II
Operating temperature range.............................................................................-10 °C...+55 °C
Maximum humidity..........................................................................................................93±3%
Dimensions ............................................................................................................. 80 x 57 mm
Weight................................................................................................................................. 35 g
The declaration of conformity may be consulted at www.satel.eu/ce
SATEL sp. z o.o. • ul. Schuberta 79 • 80-172 Gdańsk • POLAND
tel. + 48 58 320 94 00
www.satel.eu
Table of contents
Other Satel Extender manuals

Satel
Satel CA-64 SR User manual

Satel
Satel CA-64 OPS-OC User manual

Satel
Satel ACX-201 User manual

Satel
Satel CA-64 PP User manual

Satel
Satel INT-IORS User manual

Satel
Satel CA-64 ADR User manual

Satel
Satel ACX-220 User manual

Satel
Satel INT-E User manual

Satel
Satel INT-R User manual

Satel
Satel ACX-200 User manual

Satel
Satel CA-64 O-OC User manual

Satel
Satel CA-64 DR User manual

Satel
Satel ACX-201 User manual

Satel
Satel CA-64 PP User manual

Satel
Satel INT-PP User manual

Satel
Satel CA-64 EPS User manual

Satel
Satel ACX-200 User manual

Satel
Satel CA-64 EPS User manual

Satel
Satel INT-R User manual

Satel
Satel ACX-210 User manual