INT-IORS • INT-ORS
DIN-RAIL EXPANDER
int-iors_en 08/19
The INT-IORS expander enables the system to be expanded by 8 programmable wired
zones and 8 programmable wired outputs. The INT-ORS expander enables the system to be
expanded by 8 programmable wired outputs. The modules are designed for mounting on 35
mm DIN rail, which facilitates installation process and integration with other automation
systems. The expanders are supported by INTEGRA / INTEGRA Plus / CA-64 alarm control
panels and ACCO-NT access control panel. Additionally, the INT-ORS expander is supported
by the VERSA / PERFECTA alarm control panels. This manual applies to the expanders with
electronics version 2.1 and firmware version 2.04 (or newer).
1. Features
8 programmable hardwired zones only INT-IORS:
support for NO and NC type detectors, as well as roller shutter and vibration detectors,
support for Single EOL, Double EOL and Triple EOL configuration (Triple EOL when
working with INTEGRA Plus control panels),
programming end-of-line resistor values.
8 programmable relay outputs for control of the electrical devices supplied with 230 V AC.
Capable of being integrated with dedicated power supply unit (operation in "expander with
power supply" mode).
Connectable to RS-485 bus (firmware update through the bus).
35 mm DIN rail mountable.
2. Specifications
Supply voltage ................................................................................................... 12 V DC ±15%
Standby current consumption INT-IORS .....................................................35 mA
INT-ORS ......................................................35 mA
Maximum current consumption INT-IORS ...................................................350 mA
INT-ORS ....................................................310 mA
Relay output rating (resistive load) .................................................................. 16 A / 230 V AC
+12V output rating ............................................................................................ 2,5 A / 12 V DC
Environmental class according to EN50130-5 ......................................................................... II
Operating temperature range.............................................................................-10 °C...+55 °C
Maximum humidity..........................................................................................................93±3%
Dimensions ....................................................................................................122 x 93 x 58 mm
Weight INT-IORS ...................................................... 300 g
INT-ORS ....................................................... 285 g
The declaration of conformity may be consulted at www.satel.eu/ce