RDU20U, RDU50U and RDU50.2U Room Temperature Controllers Technical Instructions
with LCD for Heating and Cooling Systems Document Number 155-735
November 1, 2006
Siemens Industry, Inc. Page 7
Table 5. Control Parameters.
Setpoint of heating in energy saving mode
(operating mode changeover switch activated)
OFF
41°F to 64°F (5°C to 18C)
(in increments of 1.0°F [0.5°C])
Setpoint of cooling in energy saving mode
(operating mode changeover switch activated)
OFF
75°F to 95°F (24°C to 35C)
(in increments of 1.0°F [0.5°C])
Minimum setpoint limitation in normal mode
41°F to 68°F (5°C to 20C)
(in increments of 1.0°F [0.5°C])
Maximum setpoint limitation in normal mode
70°F to 95°F (21°C to 35C)
(in increments of 1.0°F [0.5°C])
Heat-cool changeover switching point cooling
50°F to 77°F (10°C to 25C)
(in increments of 1.0°F [0.5°C])
Heat-cool changeover switching point heating
81°F to 104°F (27°C to 40C)
(in increments of 1.0°F [0.5°C])
-3 K to 3 K (1 Kelvin = 2°F)
P-band in heating mode (RDU50U and
RDU50.2U)
0.5 K to 4 K (1 Kelvin = 2°F)
(in increments of 1°F [0.5 K])
P-band in heating mode/switching differential
when ON/OFF output is selected (RDU20U)
0.5 K to 4 K (1 Kelvin = 2°F)
(in increments of 1°F [0.5 K])
P-band in cooling mode (RDU20 when
ON/OFF output selected)
0.5 K to 4 K (1 Kelvin = 2°F)
(in increments of 1°F [0.5 K])
1 to 10 min. (in increments of 1 min.)
Minimum output limitation in cooling mode
(normal operation) (RDU50U and RDU50.2U)
0 to 100% (in increments of 10%)
Actuator running time (RDU20U)
50 to 150 s (in increments of 10 s)
Active temperature sensor (no setting, display
only)
01 = room temperature sensor active
02 = return air temperature sensor active
Current room temperature reading (no setting,
display only)
32°F to 120°F (0°C to 49C) = current
temperature value
Current heat-cool changeover
temperature reading including indication
of current mode ( , ) (no setting, display
only)
•100 = input open (no sensor
connected, heating mode ( )
•41°F to 104°F (5°C to 40C) = current
temperature value
•0 = input bridged, cooling mode ( )
Test mode for checking the actuator
direction
NOTE: P15 can be turned off only if the
setting is back at “---” and by
pressing buttons + and –
simultaneously (RDU20U only).
“---“= Output Y1 and Y2 OFF.
“OPE” = Output Y1 forced open
“CLO” = Output Y2 forced open
* Not applicable for RDU50.2U; LCD shows N/A.