1. Safety
1.1 Equipment Markings
1.2 Operational Safety
The VIP 100 and VIP 150 are designed to be used by skilled persons in
accordance with safe methods of work. If the VIP 100 or VIP 150 are used in a
manner not specified by Socket and See, the protection provided by them may
be impaired.
Inspect the product before using. If any damage is visible; such as cracks in the
casing, damage leads or probes, the unit should not be used.
Keep fingers behind the finger guards. Avoid touching a free prod while the
other prod is in contact with an electrical circuit. Avoid obscuring the indicator
LED’s during use.
This tester has been designed to be used with suitable PPE, including insulated
gloves if required.
Caution - refer to the instruction manual
Construction is double insulated
Product should be recycled as electronic waste
Conforms to EU standards
Measurement Category IV is applicable to test and measuring
circuits connected at the source of the building’s low-voltage MAINS
installation. This part of the installation is expected to have a
minimum of one level of over-current protective devices between
the transformer and connecting points of the measuring circuit.
Due to these high short-circuit currents (above 50kA) which can be
followed by a high energy level, measurements made within these
locations are extremely dangerous. Great precautions shall be made
to avoid any chance of short circuit.
Examples of CAT IV are measurements on devices installed before
the main fuse or circuit breaker in the building installation.