page 5 / 12
Getting started | Adjusting transducer settings
Activate Voltage trans-
ducers, if the measure-
ment will not be carried
out in a direct way.
Activate Current trans-
ducers for connection:
▪with current transduc-
ers,
▪direct (multiloop)
measurement of small
current for accuracy
enhancement.
Direct current measurement - enhanced accuracy
C-7A probe ●nominal range 100 A ● no. of turns = 5
F-1A probe ●nominal range 3000 A ● no. of turns = 2
New range = 100 A = 20 A
5 turns
New range = 3000 A = 1500 A
2 turns
Theuseofacurrenttransmissionindirectconnectionenhancesprobesensitivityforsmallsignalmeasure-
ment.Itdecreasestheuppermeasuringrangeaccordingtotheformula:
New range = Nominal probe range
no. of turns
anddeepensthelowermeasuringrange.Itincreasestheaccuracyandoperatingrangeoftheprobe.
Measurement with transducers
For Delta type mains, tolerances, harmonics and ex-
ceedingsarecontrolledaccordingtophase-to-phase
value. Enter:
▪100-percent value of the nominal phase-to-phase
voltage,
▪ voltagetransducerratiokU.
Enter parameters of current transducers:
▪primary current,
▪secondary current.
Mains type: Delta
Enter parameters of current transducers:
▪primary current,
▪secondary current.
For WYE+N type mains, tolerances, harmonics and
exceedingsarecontrolledaccordingtophase-to-neu-
tral value. Enter:
▪100-percent value of the nominal phase-to-neutral
voltage,
▪ voltagetransducerratiokU.
Mains type: WYE with neutral conductor
Dependingonthetypeofmeasurednetwork(WYEwithneutral/Delta),entertransducers'parametersandthe
nominallevelofexceedingscontrol.