Tyco TY7258 User manual

Model TY7258 — 16.8 K-factor
Standard Response Sprinklers
Pendent and Recessed Pendent — Specific Use
Page 1 of 4 MARCH 2018 TFP337
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Worldwide
Contacts
www.tyco-fire.com
General
Description
The TYCO 16.8 K-factor Model TY7258
Pendent and Recessed Pendent Sprin-
kler is an automatic, standard response
sprinkler intended for a specific end
use application.
The Tyco Model TY7258 Pendent and
Recessed Pendent Sprinkler has been
subjected to full-scale fire testing at
UL LLC using test parameters speci-
fied by TYCO that are considered rep-
resentative of the specific end use.
The fire test performance results of
the large scale testing have been veri-
fied by UL. Details of the tests per-
formed and results obtained may be
found in UL Test Report ‘Report of a
Special Services Investigation Involving
K16.8 gpm/(psi)½Upright and Pendent
Sprinkler Protection of a Shelf Display
and Rack Storage Arrangement of Car-
toned Group A Plastic’ (Report Number
NC27954).
For further details, contact the Techni-
cal Services Department.
NOTICE
The Model TY7258 Pendent Sprinkler
described herein must be installed and
maintained in compliance with this
document, as well as with the appli-
cable standards of the National Fire
Protection Association, in addition to
the standards of any other authorities
having jurisdiction. Failure to do so
may impair the performance of these
devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
Sprinkler
Identification
Number (SIN)
TY7258
Technical
Data
Approvals
Maximum Working Pressure
175 psi (12,1 bar)
Pipe Thread Connection
3/4 inch NPT
Minimum Spacing
7 ft (2,13 m)
Recessed Installation
Maximum 1/2 in. (12,7 mm) Recess
Discharge Coefficient
K=16.8 gpm/psi½(241,9 lpm/bar½)
Temperature Ratings
155°F (68°C), 200°F (93°C)
Finish
Sprinkler: Natural Brass, Signal White,
Bright Chrome
Separately Ordered Escutcheon: Brass
Plated, Signal White, Chrome Plated
Physical Characteristics
Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass
Deflector . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Compression Screw . . . . . . . . . . . . . . . . . .Brass
Bulb (5 mm) . . . . . . . . . . . . . . . . . . . . . . . . . Glass
Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass
Sealing Assembly ..Beryllium Nickel w/TEFLON

TFP337
Page 2 of 4
Operation
When the glass bulb reaches its rated
temperature of 155°F (68°C) or 200°F
(93°C), the glass bulb bursts allowing
the sprinkler to activate and flow water.
Installation
Install the TYCO Model TY7258
Pendent Sprinkler in accordance with
this section.
General Instructions
Do not install any bulb type sprinkler
if the bulb is cracked or there is a loss
of liquid from the bulb. With the sprin-
kler held horizontal, a small air bubble
should be present. For the Model
TY7258 Sprinkler, the diameter of the
air bubble is approximately 1/16 inch
( 7, 0 m m) .
A leak tight 3/4 inch NPT sprinkler joint
should be obtained with a torque of 10
to 20 ft.-lbs. (13,4 to 26,8 Nm). Higher
levels of torque can distort the sprin-
kler inlet with consequent leakage or
impairment of the sprinkler.
Model TY7258 Pendent Sprinkler
The Model TY7258 Pendent Sprinklers
must be installed in accordance with
the following instructions:
Step 1. Apply pipe-thread sealant to
sprinkler threads.
Step 2. Hand-tighten the sprinkler into
the sprinkler fitting. Do not apply force
to the glass bulb, grasp only by wrench
flats while hand-tightening.
Step 3. Wrench tighten the Model
TY7258 Sprinkler using only the W-Type
8 Sprinkler Wrench (Ref. Figure 2) and
by fully engaging (seating) the wrench
on the sprinkler wrench flats.
Model TY7258 Recessed Pendent
Sprinkler with Style 30 Escutcheon
The Model TY7258 Recessed Pendent
Sprinklers must be installed in accor-
dance with the following instructions.
Step 1. After installing the Style 30
Escutcheon Mounting Plate over the
sprinkler threads, and with pipe thread
sealant applied to the pipe threads,
hand tighten the sprinkler into the
sprinkler fitting.
Step 2. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
38 Sprinkler Wrench (Ref. Figure 3).
With reference to Figure 4, apply the
W-Type 38 Recessed Sprinkler Wrench
to the sprinkler wrench flats.
Step 3. After the ceiling is installed,
slide the Style 30 Escutcheon Closure
over the Model TY7258 Sprinkler and
push the closure over the mounting
plate until its flange comes in contact
with the ceiling.
Model TY7258 Pendent Sprinkler
with Style 65 Escutcheon
The pipe connected to the sprin-
kler fitting must be cut to locate the
escutcheon plate seating surface at the
proper nominal distance in front of the
wall or below the ceiling. Manufacturing
variations in the take-out of the fittings
as well as the make-in of the sprinklers
(as permitted by ANSI B1.20.1) may
require that trial cuts of the connecting
pipe be made.
Step 1. After installation of the Style
65 Escutcheon Plate over the sprinkler
threads, and with pipe thread sealant
applied to the pipe threads, hand
tighten the sprinkler into the sprinkler
fitting.
Step 2. Wrench tighten the sprinkler
into the sprinkler fitting using only the
W-Type 8 Sprinkler Wrench (Ref. Figure
2). With reference to Figure 5, apply
the W-Type 8 Sprinkler Wrench to the
sprinkler wrench flats.
Model TY7258 Pendent Sprinkler
with Style 401 Escutcheon
Step 1. After installation of the Style
401 Escutcheon Cup over the sprinkler
threads, and with pipe thread sealant
applied to the pipe threads, hand
tighten the sprinkler into the sprinkler
fitting.
Step 2. Wrench tighten the sprinkler
into the sprinkler fitting using only the
W-Type 8 Sprinkler Wrench (Ref. Figure
2). With reference to Figure 6, apply
the W-Type 8 Sprinkler Wrench to the
sprinkler wrench flats.
Step 3. After the ceiling is installed,
align the detents in the escutcheon skirt
over those in the cup and then slide
the skirt over the cup until it comes
in contact with the mounting surface.
Do not push the skirt such that it lifts
a ceiling tile out of its normal posi-
tion. Holding the skirt in contact with
the mounting surface, rotate approxi-
mately 1/8-turn relative to the cup, cre-
ating a friction fit between skirt detents
and cup surface to hold the Style 401
Escutcheon firmly together.
Compression Screw
Button
Frame Bulb
Deector
Sealing Assembly
-
-
-
-
-
-
2
1
3
5
4
6
2-3/8"
(60,3 mm)
WRENCH
FLAT
1/2"
(12,7 mm)
NOMINAL
MAKE-IN
1
2
3
5
4
6
3/4" NPT
1-5/8"
(41,3 mm)
ESCUTCHEON
SEATING SURFACE
WRENCH
RECESS
WRENCH
HEX
WRENCH
RECESS
FIGURE 1
MODEL TY7258 STANDARD RESPONSE PENDENT AND
RECESSED PENDENT SPRINKLERS
FIGURE 3
W-TYPE 38 RECESSED
SPRINKLER WRENCH
FIGURE 2
W-T Y PE 8
SPRINKLER WRENCH

TFP337
Page 3 of 4
Care and
Maintenance
The TYCO Model TY7258 Pendent
Sprinkler must be maintained and ser-
viced in accordance with this section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
system from the proper authorities
and notify all personnel who may be
affected by this decision.
Inspection, testing, and maintenance
must be performed as indicated below
and in accordance with the local
requirements and/or national codes.
Any impairment must be immediately
corrected.
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of any authorities having jurisdiction.
Contact the installing contractor or
product manufacturer regarding any
questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.
2-7/8" DIA.
(73,0 mm)
2-1/4" DIA.
(57,2 mm)
CLOSURE
MOUNTING
PLATE
1/8"
(3,2 mm)
1/4" (6,4 mm)
1/2" (12,7 mm)
1-1/4" (31,8 mm)
1-1/2" (38,1 mm)
MOUNTING
SURFACE
FACE OF
SPRINKLER
FITTING
1/2±1/8"
(12,7±3,2 mm)
CLEARANCE
HOLE
MOUNTING
SURFACE
FACE OF
SPRINKLER
FITTING
CLEARANCE
HOLE
1-5/8"
(41,3 mm)
1/2"
(12,7 mm)
1/4"
(6,4 mm)
2-13/16" DIA.
(71,4 mm)
2" DIA.
(50,8 mm)
2-1/4" DIA.
(57,2 mm)
MOUNTING
SURFACE
FACE OF
SPRINKLER
FITTING
CLEARANCE
HOLE
CUP
SKIRT
1-5/8" MIN.
(41,3 mm)
2-5/8" MAX.
(66,8 mm)
2-1/2" DIA.
(63,5 mm)
3-1/2" DIA.
(89,0 mm)
1-5/8"
(41,3 mm)
2-7/8" MAX.
(73,0 mm)
1-7/8" MIN.
(47,6 mm)
FIGURE 4
MODEL TY7258 RECESSED PENDENT SPRINKLER
WITH STYLE 30 RECESSED ESCUTCHEON
FIGURE 5
MODEL TY7258 PENDENT SPRINKLER
WITH STYLE 65 FLUSH ESCUTCHEON
FIGURE 6
MODEL TY7258 PENDENT SPRINKLER
WITH STYLE 401 DEEP ESCUTCHEON

TFP337
Page 4 of 4
NATIONAL FIRE PROTECTION ASSOCIATION is a registered trademark of National Fire Protection Association;
TEFLON is a registered trademark of DuPont
1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700
© 2018 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
When placing an order, indicate the full
product description and Part Number
(P/N).
Sprinkler Assembly
Specify: Model TY7258 Pendent Sprin-
kler, SIN TY7258, (specify temperature
rating), with (specify) finish, P/N (specify
from Table A)
Separately Ordered Style 30
Recessed Escutcheon
Specify: Style 30 Recessed Escutch-
eon, 3/4” NPT, 1/2” total adjustment,
(specify finish, P/N (specify):
Brass Plated..................5 6 -70 5 -2 - 011
Signal White (RAL9003). . . . . . . . . 56 -70 5 - 4 - 011
Chrome Plated ................5 6 -7 0 5- 9 - 011
Separately Ordered Style 65
One-Piece Flush Escutcheon
Specify: Style 65 One-Piece Flush
Escutcheon, 3/4” NPT, (specify finish),
P/N (specify):
Chrome Plated . . . . . . . . . . . . . . . . . . . . . . . 1152
Signal White (RAL9003). . . . . . . . . . . . . . . . 1175
Brass Plated. . . . . . . . . . . . . . . . . . . . . . . . . 1184
Separately Ordered Style 401
Two-Piece Deep Escutcheon
The Style 401 Two-Piece Deep
Escutcheon is comprised of separately
ordered Cup and Skirt components.
Specify: Style 401 Two-Piece Deep
Escutcheon Cup, 3/4” NPT (specify finish)
1/2” total adjustment, (specify finish), P/N
(specify):
Chrome Plated . . . . . . . . . . . . . . . . . . . . . . . 1193
Signal White (RAL9003). . . . . . . . . . . . . . . . 1197
Brass Plated. . . . . . . . . . . . . . . . . . . . . . . . . 1195
Specify: Style 401 Two-Piece Deep
Escutcheon Skirt (specify finish), P/N
(specify):
Chrome Plated . . . . . . . . . . . . . . . . . . . . . . . 1198
Signal White (RAL9003). . . . . . . . . . . . . . . . 1200
Brass ..............................1199
Sprinkler Wrenches
Specify: W Type 8 Sprinkler Wrench,
P/N 56-892-1-0 01
Specify: W Type 38 Sprinkler Wrench,
P/N 56-100 -1-607
SIN
900 16.8K PENDENT (3/4˝ NPT) TY7258
SPRINKLER
FINISH
1NATURAL BRASS
4SIGNAL WHITE (RAL9003)
POLYESTER
9BRIGHT CHROME
TEMPERATURE
RATINGS
155 155°F (68°C)
200 200°F (93°C)
P/N* 51 – XXX – X – XXX
TABLE A
MODEL TY7258 16.8K PENDENT SPRINKLERS
PART NUMBER SELECTION
Other Tyco Irrigation System manuals

Tyco
Tyco TY-B Series User manual

Tyco
Tyco TY3201 User manual

Tyco
Tyco TY-FRB Series User manual

Tyco
Tyco FSC 80 K-factor User manual

Tyco
Tyco Gem F916 User manual

Tyco
Tyco Rapidresponse LFII Series User manual

Tyco
Tyco DS-8 Series User manual

Tyco
Tyco TY-L Series User manual

Tyco
Tyco ELO-231 Series User manual

Tyco
Tyco K17-231 User manual

Tyco
Tyco EC-8 Series User manual

Tyco
Tyco ESFR-25 Operating and maintenance instructions

Tyco
Tyco TY-FRL Series User manual

Tyco
Tyco TY-B Series User manual

Tyco
Tyco K17-231 User manual

Tyco
Tyco LFII Series User manual

Tyco
Tyco ESFR-17 User manual

Tyco
Tyco TY-B Series User manual

Tyco
Tyco Royal Flush II User manual

Tyco
Tyco RFII Series User manual