Xtreme M90-80 Series Guide

M90-80 & 140 Modular Online
Three-Phase UPS
15-140kVA Models
User & Installaon Manual
www.xpcc.com | © 2019 Xtreme Power Conversion Corporaon. All rights reserved. (Rev 9/23/19)

Xtreme Power Conversion Corporaon
M90 User’s Manual
Page 2
Uninterrupble Power Supply
Table of Contents
1.Safety...........................................................................................................4
1.1 Important Safety Instrucons....................................................................................................4
1.2 EMC...........................................................................................................................................4
1.3 Installaon Informaon.............................................................................................................4
1.4 Maintenance.............................................................................................................................4
1.5 Recycling the Used Baery........................................................................................................5
2. Installaon...............................................................................................5
2.1 Inial Inspecon.........................................................................................................................5
2.2 Installaon Environment............................................................................................................5
2.3 Unpacking..................................................................................................................................6
2.4 Moving the Cabinet....................................................................................................................8
2.5 Types of UPS Cabinet.................................................................................................................9
2.6 Exterior......................................................................................................................................9
2.7 Internal Mechanisms...............................................................................................................12
2.8 Control Panel...........................................................................................................................15
2.9 Introducon of Modules...........................................................................................................16
2.10 Power Cable...........................................................................................................................20
2.11 Wiring....................................................................................................................................22
2.12 Power Module Installaon....................................................................................................23
2.12 Baery Module Installaon....................................................................................................23
3. Operaon Mode and UPS Operaon.......................................................26
3.1 Block Diagram of UPS..............................................................................................................26
3.2 Operaon Mode......................................................................................................................27
3.3 UPS Operaon..........................................................................................................................30
4. Control Panel and Display Descripon.....................................................40
4.1 Introducon.............................................................................................................................40
4.2 Screen Descripon...................................................................................................................41
4.3 Alarm List................................................................................................................................ 62

Xtreme Power Conversion Corporaon
M90 User’s Manual
Page 3
Uninterrupble Power Supply
4.4 History Record.........................................................................................................................64
5. Interface and Communicaon.................................................................65
5.1 Dry Contact Port......................................................................................................................65
5.2 Extra Comm. Slot.....................................................................................................................67
5.3 Local Communicaon Ports – RS232 & USB............................................................................67
5.4 SNMP Slot................................................................................................................................67
6. Troubleshoong.....................................................................................68
7.Service....................................................................................................70
7.1 Replacement Procedures Of Power Module.............................................................................71
7.2 Replacement Procedures Of STS Module................................................................................71
7.3 Replacement Procedures Of Baery Module...........................................................................71
7.4 Replacement Procedures Of Air Filter.....................................................................................71
8. Specicaons.........................................................................................72
9. Obtaining Service....................................................................................74
10. Xtreme Power Conversion Limited Warranty.........................................75

Xtreme Power Conversion Corporaon
M90 User’s Manual
Page 4
Uninterrupble Power Supply
1 Safety
1.1 Important Safety Instrucons
This UPS contains LETHAL VOLTAGES. All repairs and service must be performed by AUTHORIZED SERVICE PERSON-
NEL ONLY. There are NO USER SERVICEABLE PARTS inside the UPS.
WARNING:
• The UPS designed for commercial and industrial purpose, it is forbidden to apply for any life sustainment
and support.
• The UPS system contains its own energy source. The output terminals may carry live voltage even when
UPS is disconnected to an AC source.
• To reduce the risk of re or electrical shock, UPS installaon has to be in a controlled room where tem-
perature and humidity are monitored. Ambient temperature must not exceed 40°C. The system is only for
indoor use.
• Ensure all power is disconnected before installaon or service.
• Service and maintenance should be performed by qualied personnel only.
Before working on this circuit
• Isolate Uninterrupble Power System (UPS).
• Then check for Hazardous Voltage between all terminals including the protecve earth.
Risk of Voltage Backfeed
The isolaon device must be able to carry the UPS input current.
1.2 EMC
WARNING:
This is a product for commercial and industrial applicaon in the second environment - installaon restricons or
addional measures may be needed to prevent disturbances.
1.3 Installaon Informaon
WARNING:
• Installaon must be performed by qualied personnel only.
• The cabinets must be installed on a level oor suitable for computer or electronic equipment.
• The UPS cabinet is heavy. If unloading instrucons are not closely followed, cabinet may cause serious
injury.
• Do not lt the cabinets more than 10 degree.
• Before applying electrical power to the UPS, make sure the Ground conductor is properly installed.
• Installaon and Wiring must be performed in accordance with the local electrical laws and regulaons.
• The disconnecon device should be chosen based on the input current and should break line and neutral
conductors - four poles for three phases.
1.4 Maintenance
• Only qualied service personnel should perform the baery installaon.
• The following PRECAUTIONS should be observed:
1. Remove watches, rings, or other metal objects.

Xtreme Power Conversion Corporaon
M90 User’s Manual
Page 5
Uninterrupble Power Supply
2. Use tools with insulated handles.
3. Wear rubber gloves and boots.
4. Do not lay tools or metal parts on top of baeries or baery cabinets.
5. Disconnect the charging source prior to connecng or disconnecng terminal.
6. Check if the baery is inadvertently grounded. If it is, remove the source of grounding. Contacng
with any part of the ground might result in electrical shock. The likelihood of such shock can be
prevented if such grounds are removed during installaon and maintenance.
• UPS is designed to supply power even when disconnected from the ulity power. Aer disconnect the ul-
ity and DC power, authorized service personnel should aempt internal access to the UPS.
• Do not disconnect the baeries while the UPS is in Baery mode.
• Disconnect the charging source prior to connecng or disconnecng terminals.
• Baeries can result in a risk of electrical shock or burn from high short circuit current.
• When replacing baeries, use the same number of sealed, lead-acid baeries.
• Do not open or mulate the baery. Release electrolyte is harmful to the skin and eyes, and may be toxic.
1.5 Recycling the Used Baery
• Do not dispose of the baery in a re. Baery may explode. Proper disposal of baery is required. Refer
to your local codes for disposal requirements.
• Do not open or mulate the baery. Released electrolyte is harmful to the skin and eyes. It may be toxic.
• Do not discard the UPS or the UPS baeries in the trash. This product contains sealed, lead-acid baeries
and must be disposed properly. For more informaon, contact your local recycling/reuse or hazardous
waste center.
• Do not discard waste electrical or electronic equipment (WEEE) in the trash. For proper disposal, contact
your local recycling/reuse or hazardous waste center.
2 Installaon
2.1 Inial Inspecon
1. Visually examine if there is any damage inside and outside of packages in the process of the transportaon. If
any damage, report it to the carrier immediately.
2. Verify the product label and conrm the consistency of the equipment.
3. If the equipment needs to be returned, carefully repack the equipment by using the original packing material
that came with.
2.2 Installaon Environment
1. The UPS is designed for indoor use only and should be located in a clean environment with adequate venla-
on to keep the environmental parameters within the required specicaon.
2. Make sure that transportaon routes (e.g. corridor, door gate, elevator, etc.) and installaon area can accom-
modate and bear the weight of the UPS, the external baery cabinet and handling equipment.
3. The UPS uses forced convecon cooling by internal fans. Cooling air enters the module through venlaon
grills located at the front of the cabinet and exhausted through grills located in the rear part of the cabinet.
Please do not block the venlaon holes.
4. Ensure that the installaon area is spacious for maintenance and venlaon.
5. Operang temperature range is 0–40°C (32–104°F) and humidity up to 90%. Reference M90 altude and tem-
perature derang chart for specic applicaons. Lead Acid baery life is reduced above 25°C (77F).
6. If necessary, install a system of room extractor fans to avoid formaon of room temperature. Air lters are
necessary if the UPS is operated in a dusty environment.

Xtreme Power Conversion Corporaon
M90 User’s Manual
Page 6
Uninterrupble Power Supply
7. It is recommended that you parallel the external baery cabinets to the UPS. The following instrucons of
clearances are suggested:
• Keep a clearance of 40” from the top of the UPS for maintenance, wiring and venlaon.
• Keep a clearance of 40” from the back of the UPS and the external baery cabinets for venlaon.
• Keep a clearance of 60” from the front of the UPS and the external baery cabinets for maintenance and
venlaon.
8. For safety concerns, we suggest that you shall:
• Equip with CO2 or dry powder re exnguishers near the installaon area.
• Install the UPS in an area where the walls, oors and ceilings were constructed by reproof materials.
9. Do not allow unauthorized personnel to enter the installaon area. Assign specic personnel to keep the UPS
key.
2.3 Unpacking
1. Use a forkli to move the product to installed area. Please make sure the bearing capacity of forkli is suf-
cient.
2. Please follow the order in the gures below to remove carton and foams.
Figure 2-1
Figure 2-2

Xtreme Power Conversion Corporaon
M90 User’s Manual
Page 7
Uninterrupble Power Supply
3. Put a ramp in the front of the cabinet and insert small wood into groove. Then, remove two side panels. Refer
to Figure 2-3.
Figure 2-3
4. Remove 4 xing cabinet plates and loosen leveling feet by rotang them counterclockwise. Then, move the
cabinet from the pallet. Refer to Figure 2-4.
5. To x the cabinet in posion, simply rotate leveling feet clockwise. Refer to Figure 2-5.
Figure 2-4 Figure 2-5

Xtreme Power Conversion Corporaon
M90 User’s Manual
Page 8
Uninterrupble Power Supply
2.4 Moving the Cabinet
The UPS is xed on the pallet with 4 xing cabinet plates. When removing it, pay aenon to the movement of the
casters to avoid accidents.
The cabinet can be pushed forward or backward only. Pushing it sideward is not allowed. When pushing the cabi-
net, pay aenon not to overturn it as the gravity center is high.
1. If you need to move the UPS over a long distance, please use appropriate equipment like a forkli. Do not use
the UPS casters to move over a long distance.
2. Aer the UPS has been removed from the pallet to ground, we suggest that at least three people move the
UPS to the installaon area. One person holds a lateral side of the UPS with hands, another holds the other
lateral side of the UPS with hands, and the other person pushes the UPS either from the front side or from the
back side to the installaon area and avoid pping the UPS.
3. The casters are designed to move on level ground. Do not move the UPS on an uneven surface. This might
cause damage to the casters. Toppling the UPS could also damage the unit.
4. Ensure that the weight of UPS is within the designated bearing capacity of any handling equipment.
5. At the boom of the UPS, the four casters help you to move the UPS to a designated area. Before you move the
UPS, please turn the four leveling feet counterclockwise to raise them o the ground. This protects the leveling
feet from damage when moving the UPS. Refer to Figure 2-6.
Figure 2-6

Xtreme Power Conversion Corporaon
M90 User’s Manual
Page 9
Uninterrupble Power Supply
2.5 Types of UPS Cabinet
There are two types of UPS cabinets. One is the power cabinet only and the other is the power cabinet stacked on
the baery cabinet.
M90-80 M90-140
Photo
Cabinet Height 42U 42U
Switch Unit 1 1
STS 1 1
Max. Power Module 48
Baery Module 16 N/A
2.6 Exterior
In the front of the UPS, there are control interface (LCD Panel) and door lock.
The side panels are lockable. The casters at the boom of the UPS cabinet can be used to move over short dis-
tances. There are four leveling feet to x and stabilize the UPS cabinet on the ground. Refer to Figure 2-7.
Inside the cabinet, there are Breakers, STS Module, Power Module slots and Baery module slots (Baery Module
Slots is only for M90-80). All wiring terminal blocks are located in the back of cabinet.
Internal Baery Module Slots are only for M90-80

Xtreme Power Conversion Corporaon
M90 User’s Manual
Page 10
Uninterrupble Power Supply
Figure 2-7 Exterior
Mechanical Data
Dimensions
UPS cabinet Width Depth Height
42U 23.6” 43.3” 79.1”
Figure 2-8 Dimensions

Xtreme Power Conversion Corporaon
M90 User’s Manual
Page 11
Uninterrupble Power Supply
2.6.2 Front View
Unlock and open the front door and you will see the Main Breaker (Q1), Maintenance Breaker (Q2), Output Break-
er (Q3), STS Module, Power Module slots and Baery Module slots (Baery Module Slots is only for M90-80).
M90-80 M90-140
1. Baery Breaker
2. STS Module
3. Power Module
4. Baery Module
Figure 2-9 Front View

Xtreme Power Conversion Corporaon
M90 User’s Manual
Page 12
Uninterrupble Power Supply
2.6.3 Rear View
Unlock and open the rear door and you will see the rear panel of UPS. There is a baery breaker for internal bat-
tery modules in the M90-80, but there aren’t any in the M90-140.
M90-80 M90-140
Figure 2-10 Rear View
2.7 Internal Mechanisms
2.7.1 Breakers
Aer opening the front door, there are three breakers, Main Breaker (Q1), Maintenance Breaker (Q2) and Output
Breaker (Q3).
For the M90-80, there is a baery breaker for internal baery modules. You can see it when you open the rear
door.
Baery Breaker

Xtreme Power Conversion Corporaon
M90 User’s Manual
Page 13
Uninterrupble Power Supply
M90-80 M90-140
Figure 2-11 Front Breakers
M90-80
Figure 2-12 Rear Breaker
Baery Breaker

Xtreme Power Conversion Corporaon
M90 User’s Manual
Page 14
Uninterrupble Power Supply
2.7.2 Wiring Terminal Blocks
Open the UPS’s back doors and you will see the wiring terminal block. For UPS cabinet wiring, please refer to
Figure 2-13.
No. Item Funcon Descripon
1Output Block Connects the crical loads Includes R, S, T and Neutral terminals.
2Bypass Input Block Connects bypass AC source Includes R, S, T and Neutral terminals.
3 Main Input Block Connects main AC source Includes R, S, T and Neutral terminals.
4For UPS Grounding For UPS grounding Includes one grounding terminal.
5Baery Input Block Connects an external baery cabinet Includes: Posive (+), Negave (-) and
Neutral (N) terminals.
Figure 2-14 M90-80 Terminal Blocks

Xtreme Power Conversion Corporaon
M90 User’s Manual
Page 15
Uninterrupble Power Supply
Figure 2-15 M90-140 Terminal Blocks
2.8 Control Panel
2.8.1 LCD Display
Through the graphic LCD display, the user can easily understand the operaon mode of UPS. In addion, the mea-
surement, parameters, versions of rmware and warnings can be browsed in the friendly interface. For detailed
informaon, please refer to Charter 4.
Figure 2-16 Control Panel

Xtreme Power Conversion Corporaon
M90 User’s Manual
Page 16
Uninterrupble Power Supply
2.8.2 LED Indicators
LED Color Status Denion
LINE Green
On Input source is normal.
Flashing Input source is abnormal.
O No input source
BYPASS Yellow
On Load on Bypass.
Flashing Input source is abnormal.
O Bypass not operang.
LOAD Green On There is power output for the load.
O There is no power output for the load.
INV
BATTERY
Green
Red
On Load on inverters.
O Inverters not operang.
On Load on Baery.
FAULT/
ALARM Red
Flashing Low baery
O Baery converter is normal and baery is charging.
On UPS fault.
2.8.3 Control Key
Turn on or turn o the UPS.
2.9 Introducon of Modules
The design of STS Module, Power Module and Baery Module make maintenance and replacement quick and easy.
The modular and hot-swappable design of Power Module makes it a highly cost-eecve soluon to meet your
power requirement. The number of Power Modules installed in the UPS can be based on the inial needs. Once
the power requirement increases, you can easily install more Power Modules without interrupng the operaon
of the system.
Figure 2-17 Front View of Module
Baery Breaker

Xtreme Power Conversion Corporaon
M90 User’s Manual
Page 17
Uninterrupble Power Supply
2.9.1 STS Module
The STS Module is installed before leaving factory. It provides the bypass power when UPS is in Bypass Mode.
In addion to oering bypass power, it includes some communicaon interfaces. For detailed informaon, please
refer to Charter 5.
No. Item Descripon
1 Extra Comm.
Slot
This slot can insert an oponal card, Extra Comm. card which can enhance the
communicaon capability of UPS system. It can provide another SNMP slot and
some dry contact ports.
2LCD Port This port connects to Control Panel with a factory installed cable.
3 RS232 port Local communicaon interface.
4USB port Local communicaon interface.
5 SNMP Slot This slot can work with oponal cards, SNMP, AS400 or Modbus card.
6 Dry contact
ports
CN1 ~ CN8. For detailed informaon, please refer to Chapter 5.
Figure 2-18 STS Module

Xtreme Power Conversion Corporaon
M90 User’s Manual
Page 18
Uninterrupble Power Supply
Power Module
Each Power Module is shipped with its own package. It has to be installed during the UPS system installaon.
The capacity of each Power Module is 20kVA/18kW or 15kVA/13.5kW. It includes a power factor correcon rec-
er, a baery charger, an inverter and control circuit.
No. Item Descripon
1Fan
The Power Module uses forced convecon cooling by these fans. Cooling air enters
the module through venlaon grills and exhalaon exhausts through grills located
at the rear of the module. Please do not block the venlaon area.
2Ready Switch Unlock it before removing the Power Module. Lock it when the Power Module is
well installed. Then the Power Module can start to work.
3 DIP Switches There are three DIP switches for Power Module address seng. In the same cabi-
net, each Power Module ID MUST be exclusive.
4Baery Start Buon When AC input is not exisng, use this buon to start baery power for UPS.
5FAULT LED
ON The Power Module is in fault condion or the Ready Switch is
unlocked.
ON/OFF 0.5 sec The Power Module IDs conict.
ON/OFF 0.15 sec The stac switch is not found.
6 RUN LED
ON The Power Module normally works as a slave module.
ON/OFF 0.5 sec The Power Module normally works as a master module.
ON/OFF 0.15 sec The CAN Bus communicaon doesn’t work.
Figure 2-19 M90-PWRM
DIP switch seng and Module Address
Module Address DIP SWITCH Module Address DIP SWITCH
0
1 2 3
1
1 2 3
2
1 2 3
3
1 2 3
4
1 2 3
5
1 2 3
6
1 2 3
7
1 2 3
Table 2-1 DIP switch seng and Module Address

Xtreme Power Conversion Corporaon
M90 User’s Manual
Page 19
Uninterrupble Power Supply
Power Module ID Assignment
According to the Module Address and the posion of SW1 and SW2, the Power Module’s ID is assigned. The Mod-
ule ID is shown in Table 2-2.
These two switches, SW1 & SW2 are mounted in the Parallel board which is located at the back of UPS cabinet.
Refer to Figure 2-20.
Figure 2-20 Parallel Board
The SW1 and SW2 posion have been well installed before leaving factory. It’s not necessary to change it for single
UPS system applicaon.
Module ID Assignment
SW1 & SW2 Module Address Module ID SW1 & SW2 Module Address Module ID
SW1SW2
0 0
SW1SW2
0 9
1 1 1 10
2 2 2 11
3 3 3 12
4 4 4 13
5 5 5 14
6 6 6 15
7 7 7 16
SW1SW2
018
SW1SW2
0 27
1 19 1 28
2 20 2 29
321 3 30
4 22 4 31
523 532
624 6 33
7 25 7 34
Table 2-2 Module ID Assignment

Xtreme Power Conversion Corporaon
M90 User’s Manual
Page 20
Uninterrupble Power Supply
2.9.3 M90-80 Baery Module (does not apply to M90-140
The Baery Module is shipped with its own package. The inside baeries can be installed at factory or installed by
the end user. M90-80 Baery Module contains 10 pcs of 12V/580W baeries
Figure 2-21 M90-80 Baery Module
Figure 2-22 M90-80 Baery Module
2.10 Power Cable
Please follow the local wiring regulaons. Follow environmental condions and refer to IEC60950-1.
2.10.1 AC input and output maximum current and power cable conguraon.
For M90-80 models
Model 15KVA 20KVA 30KVA 40KVA 45KVA 60KVA 75KVA 80KVA
Current (A) 45 60.1 90 120.2 135 180.3 225 240.4
Power cable (mm2) 16 16 50 50 95 95 150 150
Fixaon torque force (lb-in) 88.3 88.3 88.3 88.3 88.3 88.3 88.3 88.3
This manual suits for next models
12