Xtreme P91-1000 Guide

P91 / P91g Lead Acid Online UPS
1000VA, 2000VA, 3000VA Models
User & Installaon Manual
www.xpcc.com | © 2020 Xtreme Power Conversion Corporaon. All rights reserved. (Rev 8/13/20)

P91 Lead Acid 2U User’s Manual Uninterruptible Power Supply
Xtreme Power Conversion Corporation
Table of Contents
1. Important Safety Warning .......................................................................................................... 1
1-1. Transportation........................................................................................................................... 1
1-2. Preparation ............................................................................................................................... 1
1-3. Installation ................................................................................................................................ 1
1-4. Operation .................................................................................................................................. 2
1-5. Maintenance, service and faults............................................................................................... 2
2. Installation and setup................................................................................................................. 4
2-1. Rear panel view......................................................................................................................... 4
2-2. Operating principle ................................................................................................................... 6
2-3. Install the UPS........................................................................................................................... 6
2-4. Setup the UPS ........................................................................................................................... 7
2-5. Battery Replacement .............................................................................................................. 11
2-6. Battery Kit Assembly............................................................................................................... 12
3. Operations ............................................................................................................................... 15
3-1. Button operation..................................................................................................................... 15
3-2. LCD Panel ................................................................................................................................ 15
3-3. Audible Alarm ......................................................................................................................... 16
3-4. LCD display wordings index..................................................................................................... 17
3-5. UPS Setting.............................................................................................................................. 18
3-6. Operating Mode Description .................................................................................................. 22
3-7. Faults Reference Code ............................................................................................................ 23
3-8. Warning indicator ................................................................................................................... 23
4. Troubleshooting ....................................................................................................................... 24
5. Storage and Maintenance......................................................................................................... 25
6. Specifications ........................................................................................................................... 26
7. Obtaining Service ..................................................................................................................... 28
8. Xtreme Power Conversion Limited Warranty............................................................................. 29
9. Xtreme Power Conversion Load Protection Policy ..................................................................... 31

P91 Lead Acid 2U User’s Manual Uninterruptible Power Supply
Xtreme Power Conversion Corporation Page 1
1. Important Safety Warning
SAVE THESE INSTRUCTIONS - This manual contains important instructions that should be followed
during installation and maintenance of the UPS and batteries.
Please comply with all warnings and operating instructions in this manual strictly. Do not operate this
unit before reading through all safety information and operating instructions carefully.
1-1. Transportation
Please transport the UPS system only in the original package to protect against shock and
impact.
1-2. Preparation
Condensation may occur if the UPS system is moved directly from cold to warm
environment. The UPS system must be absolutely dry before being installed. Please allow
at least two hours for the UPS system to acclimate to the environment.
Do not install the UPS system near water or in moist environments.
Do not install the UPS system where it would be exposed to direct sunlight or near heater.
Do not block ventilation holes in the UPS housing.
1-3. Installation
Do not connect appliances or devices which would overload the UPS system (e.g. laser
printers) to the UPS output sockets.
Place cables in such a way that no one can step on or trip over them.
Do not connect domestic appliances such as hair dryers to UPS output sockets.
The UPS can be operated by any individuals with no previous experience.
Connect the UPS system only to an earthed shockproof outlet which must be easily
accessible and close to the UPS system.
Please use only VDE-tested, CE-marked (for P91g models or UL-marked for P91 models)
mains cable (e.g. the mains cable of your computer) to connect the UPS system to the
building wiring outlet (shockproof outlet).
Please use only VDE-tested, CE-marked (for P91g models or UL-marked for P91 models)
power cables to connect the loads to the UPS system.
When installing the equipment, it should ensure that the sum of the leakage current of the
UPS and the connected devices does not exceed 3.5mA.
Temperature Rating - Units are considered acceptable for use in a maximum ambient of
40°C (104°F).
For Pluggable Equipment - The socket-outlet shall be installed near the equipment and shall
be easily accessible.
CAUTION: The unit is heavy. Lifting the unit requires a minimum of two people.
Batteries with minimum case flame rating V-2 are intended for use in a computer room as
defined in the Standard for the Protection of Information Technology Equipment,
ANSI/NFAP 75. Batteries with case flame rating HB are not intended for use in a computer
room. (US installations only.)

P91 Lead Acid 2U User’s Manual Uninterruptible Power Supply
Xtreme Power Conversion Corporation Page 2
1-4. Operation
Do not disconnect the mains cable on the UPS system or the building wiring outlet
(shockproof socket outlet) during operations since this would cancel the protective
earthing of the UPS system and of all connected loads.
The UPS system features its own, internal current source (batteries). The UPS output
sockets or output terminals block may be electrically live even if the UPS system is not
connected to the building wiring outlet.
In order to fully disconnect the UPS system, first press the OFF/Enter button to turn off the
unit.
Prevent fluids or other foreign objects from inside of the UPS system.
The EPO and USB circuits are an IEC 60950-1 safety extra low voltage (SELV) circuit. This
circuit must be separated from any hazardous voltage circuits by reinforced insulation.
1-5. Maintenance, service and faults
The UPS system operates with hazardous voltages. Repairs may be carried out only by
qualified maintenance personnel.
Caution - risk of electric shock. Even after the unit is disconnected from the mains (building
wiring outlet), components inside the UPS system are still connected to the battery and
electrically live and dangerous.
Before carrying out any kind of service and/or maintenance, disconnect the batteries and
verify that no current is present and no hazardous voltage exists in the terminals of high
capability capacitor such as BUS-capacitors.
To avoid electrical shock, turn off the unit and unplug it form the AC power source before
servicing the battery
Only persons adequately familiar with batteries and with the required precautionary
measures may replace batteries and supervise operations. Unauthorized persons must be
kept well away from the batteries.
Caution -risk of electric shock. The battery circuit is not isolated from the input voltage.
Hazardous voltages may occur between the battery terminals and the ground. Before
touching, please verify that no voltage is present!
Caution - Do not dispose of batteries in a fire. The batteries may explode.
Caution - Do not open or mutilate batteries. Released electrolyte is harmful to the skin and
eyes. It may be toxic.
A battery can may cause a risk of electrical shock and high short-circuit current. The
following precautions should be observed when working on batteries:
a) Remove watches, rings, or other metal objects.
b) Use tools with insulated handles.
c) Wear rubber gloves and boots.
d) Do not lay tools or metal parts on top of batteries.
e) Disconnect charging source prior to connecting or disconnecting battery terminals.
f) Determine if battery is inadvertently grounded. If inadvertently grounded,remove source
from ground. Contact with any part of a grounded battery can resultin electrical shock.
The likelihood of such shock can be reduced if such grounds are removed during
installation and maintenance.

P91 Lead Acid 2U User’s Manual Uninterruptible Power Supply
Xtreme Power Conversion Corporation Page 3
When changing batteries, install the same number and same type of batteries or battery
packs.
Please replace the fuse only with the same type and amperage in order to avoid fire
hazards.
Do not dismantle the UPS system.
WARNING: This is a category C2 UPS product. In a residential environment, this product
may cause radio interference, in which case the user many be required to take additional
measures. (only for CE models)
NOTE: This equipment has been tested and found to comply with the limits for a Class A
digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference when the equipment is operated in a
commercial environment. This equipment generates, uses, and can radiate radio frequency
energy and, if not installed and used in accordance with the instruction manual, may cause
harmful interference to radio communications. Operation of this equipment in a residential
area is likely to cause harmful interference in which case the user will be required to correct
the interference at his own expense.
WARNING: Changes or modifications not expressly approved by the party responsible for
compliance could void the user's authority to operate the equipment.

P91 Lead Acid 2U User’s Manual Uninterruptible Power Supply
Xtreme Power Conversion Corporation Page 4
2. Installation and setup
NOTE: Before installation, please inspect the unit. Be sure that nothing inside the package is damaged.
Please keep the original package in a safe place for future use.
2-1. Rear panel view
P91g models:
1500 Model 2000 Model
3000 Model
P91 models:
1000/1500 Model 2000 Model
3000 Model
1. Programmable outlets: connect to non-critical loads.
2. Output receptacles: connect to mission-critical loads.
3. AC input
4. Network/Fax/Modem surge protection

P91 Lead Acid 2U User’s Manual Uninterruptible Power Supply
Xtreme Power Conversion Corporation Page 5
5. USB communication port
6. RS-232 communication port
7. SNMP intelligent slot
8. Emergency power off function connector (EPO)
9. External battery connection
10. Output circuit breaker

P91 Lead Acid 2U User’s Manual Uninterruptible Power Supply
Xtreme Power Conversion Corporation Page 6
2-2. Operating principle
The operating principle of the UPS is shown as below
EMI/RFI
Filters
Battery
Charger Battery
DC-to-DC
Converter
Inverter
Rectifier
/PFC
Input Output
Dynamic
Bypass
The UPS is composed of mains input, EMI/RFI filters, rectifier/PFC, inverter, battery charger, DC-to-DC
converter, battery, dynamic bypass and UPS output.
2-3. Install the UPS
This UPS can be either displayed on the desk or mounted in the 19” rack chassis. Please choose
proper installation to position this UPS.
Rack-mount Installation
Step 1 Step 2
UPS Tower Installation
Step 1
Step 2
Step 3

P91 Lead Acid 2U User’s Manual Uninterruptible Power Supply
Xtreme Power Conversion Corporation Page 7
Tower Installation with battery pack
Step 1
Step 2
2-4. Setup the UPS
Before installing the UPS, please read below to select proper location to install UPS.
1. UPS should be placed on the flat and clean surface. Place it in an area away from vibration, dust,
humidity, high temperature, flammable liquids, gas, corrosive and conductive contaminants.
Install the UPS indoors in a clean environment, where it is away from window and door. Maintain
minimum clearance of 100mm in the bottom of the UPS to avoid dust and high temperature.
2. Place UPS:
It’s equipped with fan for cooling. Therefore, place the UPS in a well-ventilated area. It’s required to
maintain minimum clearance of 100mm in the front of the UPS and 300mm in the back and two sides
of the UPS for heat dissipation and easy-maintenance.
Step 1: External battery connection
For safety consideration, the UPS is shipped out from factory without connecting battery wires.
Before connecting to external batteries, it’s required to have the internal battery wire disconnected.
Follow the below steps to make external battery connection.
1. Turn off UPS and remove power plug from the mains.
2. Remove front panel and disconnect internal battery wire.

P91 Lead Acid 2U User’s Manual Uninterruptible Power Supply
Xtreme Power Conversion Corporation Page 8
3. Remove the cover of the external battery connector by using a screwdriver.
4. Plug the battery cable into the external battery connector of the UPS and
the battery pack(s).
Note: If you have multiple battery packs available, connect them serially. An example is shown
in the diagram below (connecting the second battery connector of the first battery pack to the
first battery connector of the second battery pack).
5. Stabilize the connector to the UPS and the battery pack(s) by fixing screws as shown below
diagram.
6. Connect internal battery connector and put the front panel back to the unit.
UPS
Battery
pack #1
Battery
pack #2

P91 Lead Acid 2U User’s Manual Uninterruptible Power Supply
Xtreme Power Conversion Corporation Page 9
Step 2: UPS input connection
Plug the UPS into a two-pole, three-wire, grounded receptacle only. Avoid using extension cords.
For P91g models:The power cord is supplied in the UPS package.
For P91 models: The power cord is attached to the UPS. The input plug is a NEMA 5-15P for 1000
and 1500 models, NEMA 5-20P for 2000 model and NEMA L5-30P for 3000 model.
To reduce the risk of fire, connect only to a circuit provided with (@) a maximum branch circuit
overcurrent protection in accordance with the National Electrical Code, ANSI/NFPA 70 and the
Canadian Electrical Code, Part I, C22.1.
Model (@)
P91-1000 20A
P91-1500 20A
P91-2000 20A
P91-3000 40A
Step 3: UPS output connection
There are two kinds of outputs: programmable outlets and general outlets. Please connect
non-critical devices to the programmable outlets and critical devices to the general outlets. During
power failure, you may extend the backup time to critical devices by setting shorter backup time for
non-critical devices.
Step 4: Communication connection
Communication port:
USB port RS-232 port Intelligent slot
To allow for unattended UPS shutdown/start-up and status monitoring, connect the communication
cable one end to the USB/RS-232 port and the other to the communication port of your PC. With the
monitoring software installed, you can schedule UPS shutdown/start-up and monitor UPS status
through PC.
The UPS is equipped with intelligent slot perfect for either SNMP or AS400 card. When installing
either SNMP or AS400 card in the UPS, it will provide advanced communication and monitoring
options.
Step 5: Network connection
Network/Fax/Phone surge port

P91 Lead Acid 2U User’s Manual Uninterruptible Power Supply
Xtreme Power Conversion Corporation Page 10
Connect a single modem/phone/fax line into surge-protected “IN” outlet on the back panel of the
UPS unit. Connect from “OUT” outlet to the equipment with another modem/fax/phone line cable.
Step 6: Disable and enable EPO function
This UPS is equipped with EPO function. By default, the UPS is delivered from factory with Pin 1 and
pin 2 closed (a metal plate is connected to Pin 1 and Pin2) for UPS normal operation. To activate EPO
function, remove two screws on EPO port and metal plate will be removed.
Note: The EPO function logic can be set up via LCD setting. Please refer to program 16 in UPS setting
for the details.
It’s in closed status for UPS
normal operation as default.
To activate EPO
function, remove
these two screws.

P91 Lead Acid 2U User’s Manual Uninterruptible Power Supply
Xtreme Power Conversion Corporation Page 11
Step 7: Turn on the UPS
Press the ON/Mute button on the front panel for two seconds to power on the UPS.
Note: The battery charges fully during the first five hours of normal operation. Do not expect full
battery run capability during this initial charge period.
Step 8: Install software
For optimal computer system protection, install UPS monitoring software to fully configure UPS
shutdown. Use supplied RS-232 or USB communication cable to connect RS-232/USB port of UPS and
RS-232/USB port of PC. Then, follow below steps to install monitoring software.
1. Insert the included installation CD into CD-ROM drive and then follow the on-screen instructions
to proceed software installation. If there no screen shows 1 minute after inserting the CD, please
execute setup.exe file for initiating software installation.
2. Follow the on-screen instructions to install the software.
3. When your computer restarts, the monitoring software will appear as an orange plug icon located
in the system tray, near the clock.
2-5. Battery Replacement
When the icons of and are flashing in LCD display and alarm is sounding every 2 seconds,
it’s time to replace batteries. Contact your service representative to replace batteries.
Do not disconnect battery connectors under load. If you prefer to remove input power to change the
batteries, press the OFF button on the front panel for two seconds to power off the UPS and switch
off utility power where the UPS is connected.
NOTE 1: DO NOT DISCONNECT the batteries while the UPS is in Battery mode.
NOTE 2: A small amount of arcing may occur when connecting the internal batteries. This is normal
condition and no harm for personnel. Connect the cables quickly and firmly.
NOTE 3: This UPS is equipped with internal batteries and only service person can replace the
batteries.
NOTE 4: Upon battery disconnection, equipment is not protected from power outages.
CAUTION!! Consider all warnings, cautions, and notes before replacing batteries.
Step 1 Step 2 Step 3
Remove front panel. Disconnect battery wires. Pull out the battery box by
removing two screws on the front
panel.

P91 Lead Acid 2U User’s Manual Uninterruptible Power Supply
Xtreme Power Conversion Corporation Page 12
Step 4 Step 5 Step 6
Remove the top cover of
battery box and replace the
inside batteries.
After replacing the batteries,
put the battery box back to
original location and screw it
tightly.
Re-connect the battery wires.
Step 7
Put the front panel back to the unit.
2-6. Battery Kit Assembly
NOTICE: Please assemble battery kit first before installing it inside of UPS. Please select correct
battery kit procedure below to assemble it.
2-battery kit
Step 1: Remove adhesive tapes. Step 2: Connect all battery terminals by following
below chart.
Step 3: Put assembled battery packs on one
side of plastic shells.
Step 4: Cover the other side of plastic shell as
below chart. Then, battery kit is assembly well.
Tapes

P91 Lead Acid 2U User’s Manual Uninterruptible Power Supply
Xtreme Power Conversion Corporation Page 13
3-battery kit
Step 1: Remove adhesive tapes. Step 2: Connect all battery terminals by following
below chart.
Step 3: Put assembled battery packs on one
side of plastic shells as below chart.
Step 4: Cover the other side of plastic shell as
below chart. Then, battery kit is assembly well.
4-battery kit
Step 1: Remove adhesive tapes. Step 2: Connect all battery terminals by following
below chart.
Step 3: Put assembled battery packs on one
side of plastic shells.
Step 4: Cover the other side of plastic shell as
below chart. Then, battery kit is assembly well.
Tapes
Tapes
Tapes
Tapes

P91 Lead Acid 2U User’s Manual Uninterruptible Power Supply
Xtreme Power Conversion Corporation Page 14
6-battery kit
Step 1: Remove adhesive tapes. Step 2: Connect all battery terminals by following
below chart.
Step 3: Put assembled battery packs on one
side of plastic shells.
Step 4: Cover the other side of plastic shell as
below chart. Then, battery kit is assembly well.
Tapes
Tapes

P91 Lead Acid 2U User’s Manual Uninterruptible Power Supply
Xtreme Power Conversion Corporation Page 15
3. Operations
3-1. Button operation
Button Function
ON/Mute
Button
Turn on the UPS: Press and hold ON/Mute button for at least 2 seconds to
turn on the UPS.
Mute the alarm: After the UPS is turned on in battery mode, press and hold
this button for at least 3 seconds to disable or enable the alarm system. But
it’s not applied to the situations when warnings or errors occur.
Up key: Press this button to display previous selection in UPS setting mode.
Switch to UPS self-test mode: Press ON/Mute buttons for 3 seconds to enter
UPS self-testing while in AC mode, ECO mode, or converter mode.
OFF/Enter
Button
Turn off the UPS: Press and hold this button at least 2 seconds to turn off the
UPS. UPS will be in standby mode under power normal or transfer to Bypass
mode if the Bypass enable setting is set by pressing this button.
Confirm selection key: Press this button to confirm selection in UPS setting
mode.
Select
Button
Switch LCD message: Press this button to change the LCD message for input
voltage, input frequency, input current, battery voltage, battery current,
battery capacity, ambient temperature, output voltage, output frequency,
load current and load percent.
Setting mode: Press and hold this button for 3 seconds to enter UPS setting
mode when Standby and Bypass mode.
Down key: Press this button to display next selection in UPS setting mode.
ON/Mute
+ Select
Button
Switch to bypass mode: When the main power is normal, press ON/Mute and
Select buttons simultaneously for 3 seconds. Then UPS will enter to bypass
mode. This action will be ineffective when the input voltage is out of
acceptable range.
Exit setting mode or return to the upper menu: When working in setting
mode, press ON/Mute and Select buttons simultaneously for 0.2 seconds to
return to the upper menu. If it’s already in top menu, press these two buttons
at the same time to exit the setting mode.
3-2. LCD Panel
Display
Function
Backup time information

P91 Lead Acid 2U User’s Manual Uninterruptible Power Supply
Xtreme Power Conversion Corporation Page 16
Indicates the estimated backup time.
H: hours, M: minute, S: second.
Configuration and fault information
Indicates the configuration items, and the configuration items are listed in
details in section 3-5.
Indicates the warning and fault codes, and the codes are listed in details in
section 3-7 and 3-8.
Mute operation
Indicates that the UPS alarm is disabled.
Input, Battery, Temperature, Output & Load information
IIndicate the input voltage, input frequency, input current, battery voltage,
battery current, battery capacity, ambient temperature, output voltage, output
frequency, load current and load percent.
k: kilo, W: watt, V: voltage, A: ampere, %: percent,
℃
: centigrade degree, Hz: frequency
Load information
Indicates the load level by 0-24%, 25-49%, 50-74% and 75-100%.
Indicates overload.
Programmable outlets information
Indicates that programmable management outlets are working.
Mode operation information
Indicates the UPS connects to the mains.
Indicates the battery is working.
Indicates charging status
Indicates the bypass circuit is working.
Indicates the ECO mode is enabled.
Indicates the AC to DC circuit is working.
Indicates the PFC circuit is working.
Indicates the inverter circuit is working.
Indicates the UPS is working in converter mode.
Indicates the output is working.
Battery information
Indicates the battery level by 0-24%, 25-49%, 50-74%, and 75-100%.
Indicates low battery.
3-3. Audible Alarm
Battery Mode Sounding every 5 seconds

P91 Lead Acid 2U User’s Manual Uninterruptible Power Supply
Xtreme Power Conversion Corporation Page 17
Low Battery Sounding every 2 seconds
Overload Sounding every second
Fault Continuously sounding
Bypass Mode Sounding every 10 seconds
3-4. LCD display wordings index
Abbreviation Display content Meaning
ENA
Enable
DIS
Disable
ESC
Escape
HLS
High loss
LLS
Low loss
AO
Active open
AC
Active close
EAT
Estimated autonomy time
RAT
Running autonomy time
SD
Shutdown
OK
OK
ON
ON
BL
Battery Low
OL
Over Load
OI
Over input current
NC
Battery No Connect
OC
Over Charge
SF
Site wiring fault
EP
EPO
TP
Temperature
CH
Charger
BF
Battery Fault
BV
Bypass Out Range
FU
Bypass frequency unstable
BR
Battery Replace
EE
EEPROM error

P91 Lead Acid 2U User’s Manual Uninterruptible Power Supply
Xtreme Power Conversion Corporation Page 18
3-5. UPS Setting
Parameter 1 Parameter 2
There are three parameters to set up the UPS.
Parameter 1: It’s for program alternatives. Refer
to below table.
Parameter 2 is the setting options or values for
each program.
•01: Output voltage setting
Interface
Setting
Parameter 2: Output voltage
For P91g models, you may choose the following output voltage:
200: presents output voltage is 200Vac
208: presents output voltage is 208Vac
220: presents output voltage is 220Vac
230: presents output voltage is 230Vac (Default)
240: presents output voltage is 240Vac
For P91 models, you may choose the following output voltage:
100: presents output voltage is 100Vac
110: presents output voltage is 110Vac
115: presents output voltage is 115Vac
120: presents output voltage is 120Vac (Default)
125: presents output voltage is 125Vac
•02: Frequency Converter enable/disable
Interface
Setting
Parameter 2: Enable or disable converter mode. You may choose
the following two options:
CF ENA: converter mode enable
CF DIS: converter mode disable (Default)
•03: Output frequency setting
Interface
Setting
Parameter 2: Output frequency setting.
You may set the initial frequency on battery mode:
BAT 50: presents output frequency is 50Hz
BAT 60: presents output frequency is 60Hz
If converter mode is enabled, you may choose the following
output frequency:
CF 50: presents output frequency is 50Hz
CF 60: presents output frequency is 60Hz
This manual suits for next models
6
Table of contents
Other Xtreme UPS manuals

Xtreme
Xtreme 6kVA Guide

Xtreme
Xtreme V80 Series Guide

Xtreme
Xtreme XPRT-SNMP2 Guide

Xtreme
Xtreme E91 Guide

Xtreme
Xtreme 2000VA Operating manual

Xtreme
Xtreme P90-1000 Troubleshooting guide

Xtreme
Xtreme M90-80 Series Guide

Xtreme
Xtreme R91-20KVA Operating manual

Xtreme
Xtreme X90-5S Guide

Xtreme
Xtreme TX90 6kVA User manual
Popular UPS manuals by other brands

AEC
AEC IST710kVA user manual

Emerson
Emerson SolaHD SDU AC B-Series user manual

ICS
ICS Lifeline M95-600 Series operating instructions

AEG
AEG Protect alpha. 1200 user manual

MGE UPS Systems
MGE UPS Systems PULSAR 1000 Installation and user manual

CyberPower
CyberPower OfficePower 1500AVR-H0 Specification sheet