Young ResponseONE 91000 User manual

ResponseONE
MODEL 91000
ULTRASONIC ANEMOMETER
METEOROLOGICAL INSTRUMENTS
INSTRUCTIONS
R.M. YOUNG COMPANY 2801 AERO PARK DRIVE, TRAVERSE CITY, MICHIGAN 49686, USA
TEL: (231) 946-3980 FAX: (231) 946-4772 WEB: www.youngusa.com PN: 91000-90
REV: B021918

91000-90(B)
Contents
SECTION DESCRIPTION PAGE
1.0 INTRODUCTION ................................................................................................................. 1
2.0 SPECIFICATIONS ............................................................................................................... 1
3.0 BEFORE INSTALLATION ................................................................................................... 2
4.0 INSTALLATION ................................................................................................................... 2
4.1 Placement ............................................................................................................................ 2
4.2 Mounting and Alignment ...................................................................................................... 2
4.3 Wiring Connections ............................................................................................................. 3
5.0 OPERATION ....................................................................................................................... 3
5.1 Serial Output Formats ......................................................................................................... 3
5.2 SDI-12 Measurement Commands ....................................................................................... 4
5.2.3 Extended Commands .......................................................................................................... 5
5.3 Low Power Operation .......................................................................................................... 5
6.0 SETTING SERIAL OUTPUTS AND OPERATING PARAMETERS .................................. 6
6.1 Sensor Conguration with ResponseONE CONFIG program ............................................ 6
6.2 Sensor Conguration using a General Purpose Communications Program ....................... 6
6.3 Command Overview ............................................................................................................ 7
6.4 Command Details ................................................................................................................ 7
7.0 EXAMPLE SETTINGS ........................................................................................................ 9
8.0 EMC COMPLIANCE ........................................................................................................... 9
9.0 WARRANTY ........................................................................................................................ 9
10.0 CE COMPLIANCE ............................................................................................................. 9
APPENDIX
A WIRING CONNECTIONS
A1: RS-232 Serial Connection........................................................................................ 10
A2: RS-485 / RS-422 Serial Connection - Full Duplex .................................................. 10
A3: RS-485 / RS-422 Serial Connection - Half Duplex...................................................11
A4: RS-485 / RS-422 Serial Connection - Output Only ..................................................11
A5: SDI-12 Serial Connection........................................................................................ 12
A6: RS-485 Serial Connection - Full Duplex (Model 26800 Translator) ........................ 12
A7: 06201 Wind Tracker Wiring Connections ............................................................... 13
A8: 06206 Marine Wind Tracker Wiring Connections................................................... 13
B SENSOR ORIENTATION AND DIMENSIONS ................................................................. 14
C TROUBLESHOOTING ...................................................................................................... 15
OPERATING INSTRUCTIONS
Model 91000 ResponseONE Ultrasonic Anemometer


Page 1
91000-90(B)
MODEL 91000
ResponseONE
ULTRASONIC ANEMOMETER
2.0 SPECIFICATIONS
WIND SPEED
Range: 0 - 70 m/s (156 mph)
Resolution: 0.01 m/s
Accuracy: 0 - 30 m/s ±2% or 0.3 m/s
30 - 70 m/s ±3%
Response Time: <0.25 seconds
WIND DIRECTION
Azimuth Range: 0 - 360 degrees
Resolution: 0.1 degree
Accuracy: ± 2 degrees
Response Time: <0.25 seconds
COMPASS
Range: 0 - 360 degrees
Resolution: 0.1 degrees
Accuracy: ± 2 degrees
SERIAL OUTPUT (Selectable)
Interface Type: RS-232 or RS-485/422, SDI-12
Formats: ASCII Text - polled or continuous
NMEA - continuous
SDI-12 - polled
RMYT - continuous
Baud Rates: 1200, 4800, 9600, 19200 and 38400
GENERAL
Output rate: 0.1 to 10 Hz
Power Supply: 10 - 30 VDC,
7 mA typical, 80 mA max
Protection Class: IP66
EMC Compliance: FCC Class A digital device
IEC standard 61326-1
Dimensions: 23 cm high x 13.5 cm wide
Weight: 0.5 kg (1.1 lb)
Shipping Weight: 1.4 kg (3.1 lb)
Operating Temperature: -40 - +60°C
1.0 INTRODUCTION
The Model 91000 ResponseONEtm Ultrasonic Anemometer is
a 2-axis, no-moving parts wind sensor. It is ideal for general
meteorological applications requiring accurate and reliable
measurement. The sensor features wide operating range, compact
size, easy installation and low power operation.
The sensor features durable corrosion-resistant construction
throughout. An internal compass provides wind direction orientation
when needed.
The ResponseONE installs on readily-available 1 inch (IPS)
pipe. Wiring connections are made in a convenient, weather-
proof junction box; special connectors and custom cables are not
needed.
Measured data is output in a serial format. NMEA, SDI-12, RMYT,
and ASCII protocols are available to suit many applications.
Continuous serial output or polled operation may be used.
RS-232 or RS-485 serial format options allows direct connection
to YOUNG displays, marine NMEA systems, data loggers, or other
compatible serial devices.
Operating parameters are easily reviewed and changed using the
ResponseONE CONFIG program available for download at www.
youngusa.com. All settings are stored internally in non-volatile
memory.

Page 2
91000-90(B)
3.0 BEFORE INSTALLATION
3.0 UNPACKING THE ResponseONE
The ResponseONE comes in a custom shipping carton. Carefully
inspect the instrument when rst unpacking and report any visible
damage to your YOUNG supplier. Be sure to retain the bird spikes
and orientation ring for use.
1
2
3
4
5
6
1. Ultrasonic wind sensor array
2. Junction box / wiring terminals
3. Sensor cable (ordered separately)
4. Mounting post clamp
5. Orientation ring
6. Bird spikes
Figure 3.0 ResponseONE Features
The ResponseONE arrives fully calibrated and ready to use. As
supplied, the sensor is congured as follows:
FACTORY DEFAULT CONFIGURATION
Protocol: RS-232 ASCII Continuous
Baud Rate: 9600
Wind Format: Polar
Wind Units: m/s, Degrees azimuth
Default connections are shown in APPENDIX A, FIGURE A1.
Other options are also described in APPENDIX A. These are
accomplished using the ResponseONE CONFIG program which
is available at www.youngusa.com. Note: Always connect and
bench test a complex system before installation in the eld.
4.0 INSTALLATION
4.1 PLACEMENT
Proper instrument placement is important. Eddies from buildings,
trees, or other structures can inuence measurements. Locate
the sensor well away from obstructions. As a general rule, air ow
around a structure is disturbed to 10 times the height of the structure
downwind and 1-1/2 times the height of the structure above the roof.
10H
1.5 H
H
OPEN, LEVEL GROUND
Fig 4.1 Wind Siting Considerations
4.2 MOUNTING AND ALIGNMENT
The ResponseONE mounts on standard 1-inch (IPS) pipe. This is
commonly available steel pipe with an outside diameter of 1.34 inches
(34 mm). The pipe should be secured vertically. Place the orientation
ring over pipe end with guide pin facing up. Do not tighten clamps yet.
Most applications require aligning the wind sensor array to
geographic north (0 degrees). In this orientation the junction box
faces SOUTH (180 degrees). See the diagram in APPENDIX B for
details. Two methods are suggested below :
4.2.1 ORIENTATION USING KNOWN GEOGRAPHIC DATA
(PREFERRED) Obtain accurate geographic data for the
installation site, this can be a topographic map, graphical
GPS map or detailed road map. Using the transducers
as a sighting aid, align the sensor with a remote feature
that represents the proper orientation. After alignment,
tighten the mounting post band clamp to secure the
position. DO NOT OVER-TIGHTEN. Engage orientation
ring pin with slot (Fig 4.2.3) in sensor base (under J-box).
Now tighten the band clamp on the orientation ring. If the
ResponseONE is later removed, the orientation ring will
preserve the sensor alignment. Compass is NOT enabled
for this method.
NORTH
Fig 4.2.1 Sighting of Wind Sensor using Geographic Feature

Page 3
91000-90(B)
4.2.2 ORIENTATION USING BUILT-IN ELECTRONIC
COMPASS.
Note: Acclimate the ResponseONE to ambient
temperature at the installation site before calibrating.
Place ResponseONE sensor on mounting pipe, fully
seating it on the pipe and allowing for free rotation of
the sensor. Connect cable as indicated in APPENDIX
A and apply power to the system. (Refer to Fig 4.2.2)
With junction box cover removed, press and hold the
“CALIBRATE” button for 3 seconds; the indicator light
will blink rapidly to indicate that calibration mode is
active. Slowly rotate the sensor for 1-1/4 rotations. After
completing the rotations, press and hold the “CALIBRATE”
button again for 3 seconds; the indicator will double blink.
Within the next 60 seconds, tighten the mounting post band
clamp to secure the sensor. DO NOT OVER-TIGHTEN. At
this point, the compass will lock the direction of the sensor
and the ResponseONE will output correct wind direction
data; the indicator will continue to blink once per second.
Reattach J-Box cover and engage orientation ring as
shown in Fig 4.2.3 Tighten the orientation ring band clamp.
Important: Be sure to allow for magnetic declination in
your measurement. A declination value can be entered
using the ResponseONE CONFIG program or it can be
compensated in the data-logger program. Please note that
declination may change if the sensor is moved to a new
location. Accurate declination data can be obtained from
the following website:
http://www.ngdc.noaa.gov/geomag-web/#declination
CALIBRATE
BUTTON
ROTATE
1-1/4 TURNS
Fig 4.2.2 Orientation of Wind Sensor Using Electronic Compass
SENSOR CLAMP
INDEX PIN IN NOTCH
ORIENTATION RING
Fig 4.2.3 Proper Engagement of Orientation Ring with Sensor
4.3 WIRING CONNECTIONS
The ResponseONE is supplied with RS-232, RS-485 and SDI-12
signal capability. Please select the signal type desired and refer to
the appropriate WIRING CONNECTIONS diagram in APPENDIX A
for connecting the ResponseONE to your serial device. Please note,
the ResponseONE is not equipped with analog outputs.
5.0 OPERATION
5.1 SERIAL OUTPUT FORMATS
The ResponseONE comes standard with the following serial output
formats:
Format/Protocol Wiring Format
ASCII Polled and Continuous RS-232, RS-485
NMEA 0183 v3.0 Automatic RS-232, RS-485
SDI-12 Polled SDI-12
RMYT RS-485
Detailed information about each protocol is in the following section.
If you wish to change settings from the factory default values shown
in Section 3, this is easily done using the ResponseONE CONFIG
program described in Section 6.0.

Page 4
91000-90(B)
5.1.1 ASCII
ASCII output format provides continuous measurement data in text
format at any of the available baud rates.
The wind measurement in ASCII output appears either in POLAR
(default) or CARTESIAN UV format. With POLAR format, the wind
speed threshold and wind speed units are user-selectable. With
CARTESIAN the wind threshold is ignored and wind speed units
are always meters per second (m/s).
ASCII POLAR FORMAT
a www.ww ddd.d ss*cc<CR>
where:
a = Sensor address
www.ww = Wind speed
ddd.d = Wind direction
ss = Status code
* = Asterisk (ASCII 42)
cc = Checksum
<CR> = Carriage return (ASCII 13)
ASCII CARTESIAN (UV) FORMAT
a uu.uu vv.vv ss*cc<CR>
where:
a = Sensor address
±uu.uu = U-axis wind speed (m/s)
±vv.vv = V-axis wind speed (m/s)
ss = Status code
* = Asterisk (ASCII 42)
cc = Checksum
<CR> = Carriage return (ASCII 13)
CHECKSUM is a two-character hexadecimal value (in printable
ASCII format) generated by taking the exclusive-or of all characters
up to the asterisk. STATUS CODE shows a non-zero value when the
sensor cannot acquire sufcient samples or a measurement error has
occurred. See APPENDIX C for more information on status codes.
5.1.2 ASCII POLLED
ASCII POLLED is like ASCII format described above except just
one serial output string is sent for each polling command received.
The polling command is Ma! where 'a' is the sensor address (valid
characters: 0-9, A-Z, a-z). The default address is '0' (ASCII 48).
5.1.3 RMYT
RMYT is a 6-byte binary data format sent at 9600 baud using RS-485
OUTPUT ONLY mode. It is for use with the YOUNG Model 06201
Wind Tracker.
5.1.4 NMEA
NMEA format provides continuous measurements in standard
NMEA marine sentences at 4800 baud. The ResponseONE must be
connected to a NMEA-capable device. Specic details of the NMEA
data string are below:
NMEA FORMAT
$WIMWV,ddd,R,www.w,u,A*cc<CR><LF>
where:
WI = Device type (weather instrument)
MWV = Wind direction and speed
ddd = Wind direction (degrees)
www.w = Wind speed
u = Wind speed units
S = mph
N = knots
K = kmph
M = m/s
A = Data status code: A=valid, V=invalid
* = Asterisk (ASCII 42)
cc = Checksum
<CR><LF> = Carriage return,Line feed (ASCII 13,10)
CHECKSUM is the two-character printable hexadecimal value
generated by taking the exclusive-or of all characters between '$'
and '*'.
5.2 SDI-12
SDI-12 stands for serial data interface at 1200 baud. It is often used
to interface battery powered data recorders with microprocessor
based devices designed for environmental data acquisition. SDI-
12 is typically used when low power usage is required. The SDI-12
device normally remains in a low power, standby state until it is polled
at which time a measurement is sent. SDI-12 can effectively address
multiple sensors on the same cable.
5.2.1 SDI-12 MEASUREMENT COMMANDS
Model 91000 uses the SDI-12 (v1.3) serial communication protocol
to initiate measurements and set sensor operation parameters.
The default sensor address is 0 (zero), and can be changed to
any valid single-character value if needed. Additional details about
the SDI-12 protocol may be found at www.sdi-12.org.
After initial power-up with 12 VDC, the sensor is in a low-
power standby state with a quiescent current of 4.2 mA. A valid and
properly addressed SDI-12 command wakes the sensor to initiate a
measurement, set or check operating parameters. After command
processing has nished, the sensor returns to the low-power standby
state.
SDI-12 'M' or 'C' commands initiate a measurement. The sensor
response message indicates the maximum time needed before
the measurement is ready, and data values will be available. The
maximum time ranges from 1 to 5 seconds depending on the Sample
Count.
If an 'M' command initiates a measurement, the sensor sends a
Service Request when the measurement is ready to be retrieved.
When the polling device receives the Service Request it then sends
a 'D' command to request measurement results from the sensor.
With 'C' commands, no Service Request is sent, and the polling
device must wait the full delay time before sending the 'D' command
to request the measurement.

Page 5
91000-90(B)
SDI-12 Measurement commands and responses are listed below.
COMMAND RESPONSE DESCRIPTION
aM! attts<CR><LF> Take a measurement
aMC! attts<CR><LF> Take a measurement with CRC
checksum
aC! atttss<CR><LF> Take a concurrent measurement
aCC! atttss<CR><LF> Take a concurrent measurement
with CRC checksum
aD0! a+www.ww+ddd.d<CRC><CR><LF> (Polar)
a±uu.uu±vv.vv<CRC><CR><LF> (Cartesian)
where:
a = Sensor address
ttt = Delay time (seconds)
s/ss = Number of samples to collect
www.ww = Wind speed (selected units)
ddd.d = Wind direction (degrees)
±uu.uu = U-axis wind speed (m/s)
±vv.vv = V-axis wind speed (m/s)
<CRC> = CRC checksum (only where requested)
<CR><LF> = Carriage return, line feed (ASCII 13, 10)
Wind data format depends on the sensor Output Format parameter
setting (Polar or Cartesian).
5.2.2 SDI-12 NON-MEASUREMENT COMMANDS
The SDI-12 protocol includes standard commands for identifying the
sensor and changing its address.
COMMAND RESPONSE DESCRIPTION
?! a<CR><LF> Address Query
a! a<CR><LF> Acknowledge Active
aI! a13 YOUNG C091000 vvvnnnnnn<CR><LF>
Send Identication
vvv = Firmware Version
nnnnnn = Serial Number
aAb! b<CR><LF> Change Address
a = Sensor address
b = New sensor address
aV! a0000<CR><LF> Start Verication
5.2.3 EXTENDED COMMANDS
The SDI-12 command set may be customized with Extended
Commands to accommodate manufacturer settings and other
functions. Extended Commands are listed below. Where two
responses are shown, one is for a valid command, the other is for
an invalid (ERR) command.
COMMAND RESPONSE DESCRIPTION
aXB! aXB, OK<CR><LF> Save parameter settings to ash.
aXFn! aXF, F=n<CR><LF> n = Output Format code.
0 or 1 (Polar or Cartesian)
aXF,ERR F=0/1<CR><LF>
aXPn! Parameter report, 4 reports needed for all parameters
aXP1,F=f,UW=uw,T=t,S=s,W=w,CE=ce<CR><LF>
a = Sensor address
f = Wind Format
uw = Polar wind speed units
1=mph
2=knots
3=km/h
4=m/s
t = Threshold, polar only (0-150 cm/s)
s = Sample count, internal (1-800)
w = Wait (seconds)
ce=Compass Enable
aXP2,OD=od,M=m,CD=cd,PWR=v VDC<CR><LF>
od=WD Offset
m=WS Multiplier
cd=Compass Declination
v=Supply Voltage
aXPn,ERR n=1/2/3/4 ONLY<CR><LF>
aXSnnn! nnn = Sample Count (001-800 samples)
aXS,S=nnn<CR><LF>
aXS,ERR S=001-800 ONLY<CR><LF>
aXMnnnnn! nnnnn=WS multiplier x 10000 (00000 - 30000)
aXM,M=nnnnn<CR><LF>
aXM,ERR M=00000-30000 ONLY<CR><LF>
aXTnnn! nnn = Wind Speed Threshold (000 - 150 cm/s)
aXT,T=nnn<CR><LF>
aXT,ERR T=000-150 ONLY<CR><LF>
aXUWn! n = Wind Speed Units
(1=mph, 2=knots, 3=kmph, 4=m/s)
aXUW,UW=n<CR><LF>
aXUW,ERR UW=1/2/3/4 ONLY<CR><LF>
aXOD±nnnn! ±nnnn = Wind Direction Offset x 10 (-3600 to
3600) aXOD,OP=±nnnn<CR><LF>
aXOD,ERR OD=-3600 - +3600
ONLY<CR><LF>
aXCEn! n = Compass Enable (0=Disable, 1=Enable)
aXCE,CE=n<CR><LF>
aXCE,ERR CE=0/1 ONLY<CR><LF>
aXCDnddmm! nddmm = Declination (n=E/W/0,dd=DEG,
mm=MIN) aXCD,CD=nddmm<CR><LF>
aXCD,ERR CD=nddmm n=E/W/0, dd=00-
90, mm=00-60 ONLY<CR><LF>
IMPORTANT! PARAMETER CHANGES MUST BE STORED IN
FLASH MEMORY USING THE aXB! COMMAND OR THEY WILL
REVERT TO PREVIOUSLY STORED VALUES AT POWER UP.
The aXB! command may be sent after all changes have been
made, or not sent at all if the changes are temporary.
SAMPLE COUNT (aXSnnn!)
Each wind measurement is calculated from the median of multiple
wind samples. Each sample requires a power pulse so more samples
consume more power. The default sample count of 16 is a good
balance of low power consumption and robust performance. If winds
above 30 m/s are expected, 100 samples may be more suitable.
Winds reaching the performance limit of the sensor (70 m/s) may
require a setting of up to 800 samples.
THRESHOLD (aXTnnn!)
Threshold sets the minimum wind speed needed before a new polar
wind direction is calculated. The default value is 25 cm/s (0.25 m/s). A
greater-than-zero threshold can help provide more meaningful scalar
wind direction averages. The threshold for Cartesian (UV) output
format is automatically zero regardless of this setting.
5.3 LOW POWER OPERATION
Average current consumption with default settings is about 7.5 mA.
This conguration uses minimal power and enables all features even
though they may not be used. This is suitable for many low power
applications.
To reduce current consumption further, additional strategies include
disabling unused outputs, using polled serial operation, increasing
the output interval, and limiting the sample count to the minimum
optimal number. Faster baud rates also reduce power by limiting
transmit duration.

Page 6
91000-90(B)
6.0 SETTING OUTPUTS AND OPERATING
PARAMETERS
6.1 SENSOR CONFIGURATION WITH ResponseONE CONFIG
PROGRAM (RECOMMENDED)
The YOUNG ResponseONE CONFIG program is available from the
factory web site: www.youngusa.com. It provides an easy method
for checking and conguring sensor operation. Install the program
on a Windows 7 or higher PC and follow instructions that appear
on the program screen to retrieve current sensor settings or send
new settings.
6.1.1 Opening the Program
After installing the program on your PC, click the desktop icon to open
the program. The following screen should appear:
Fig 6.1 ResponseONE CONFIG program opening screen
If you are using the ResponseONE for the rst time, the default
settings will appear. For reference these are:
FACTORY DEFAULT CONFIGURATION
Protocol: RS-232 ASCII Continuous
Baud Rate: 9600
Wind Format: Polar
Wind Units: m/s, Degrees azimuth
If these settings are correct for your application, then you may
proceed with operation of the device. If you wish to change any
settings, available options can be selected from menu items visible.
After changes are made, the ResponseONE CONFIG program
automatically saves the new settings in ash memory
6.2 SENSOR CONFIGURATION USING A GENERAL PURPOSE
COMMUNICATIONS PROGRAM
A general purpose text-based serial communications program like
HyperTerminal may be used to manually congure the sensor by
sending simple text commands. The following guidelines apply:
The YOUNG sensor and communication program must operate at
the same baud rate and be properly connected. Sensor RS-232
mode must be enabled. See the RS-232 wiring diagram, FIGURE
A1, in APPENDIX A.
Factory default sensor baud rate is 9600, Congure the serial
communications program for NO handshaking and 1 start, 8 data, 1
stop bit, no parity, no ow control.
The sensor must be in COMMAND MODE in order to set parameters.
Enter COMMAND MODE by sending three ESC characters (ASCII
27) in quick succession while the sensor is running. When the sensor
is in COMMAND MODE, it sends a '>' prompt character indicating
that it is ready to accept commands.
If the prompt does not appear after sending three indicating
characters, re-check wiring and communication program setup. If
the sensor baud rate is unknown, try sending the ESC characters
at each of the ve available baud rates (1200, 4800, 9600, 19200
and 38400). It is also possible that sensor parameters have been
purposely congured to disable RS-232 mode. If this is the case, the
following method must be used.
In order to provide access under all conditions, the sensor always
begins operation at power up with serial communications set to 38400
baud and RS-232 connections enabled. Immediately after power up,
there is a short time window in which to send the ESC characters
and enter COMMAND MODE.
To use this feature, set your serial communication program baud rate
to 38400. Remove power then wait 5 seconds. Re-apply power to
the sensor. The sensor will transmit four asterisks immediately after
power up. After the asterisks appear, send three ESC characters.
The COMMAND MODE '>' prompt should appear. To do this
using ResponseONE CONFIG, connect the ResponseONE to your
computer, open the program (make sure the correct serial port is
selected), then go to the 'COMMANDS' menu and select 'ACQUIRE
ResponseONE'.
A window will come up telling you that the serial port will be set to
38400 baud. Click 'OK' to continue. Then simply apply power to the
ResponseONE and the program will connect automatically.

Page 7
91000-90(B)
6.3 COMMAND OVERVIEW
After the '>' prompt appears, send '??' to display a list of available
commands. Send 'RPTV' to report current settings. (Note that some
values in the report are for factory settings and cannot be changed
by the user.)
Commands are case sensitive and the exact format must be used.
For example, the SET01nn command requires two digits for the serial
format code. If you send SET014 instead of SET0104 the sensor will
reject the command and indicate an error. End all commands with
a carriage return (ASCII 13). In HyperTerminal, do this by pressing
the ENTER key.
After receiving the carriage return, the sensor will evaluate the
command. Valid commands will be executed. Current settings can be
evaluated at any time by sending RPTV to get a new report.
IMPORTANT NOTE:
The YOUNG ResponseONE CONFIG program automatically
saves all settings to ash memory when they are sent to the
sensor. Settings that are changed manually must be saved to
ash with the SET77 command.
COMMAND DESCRIPTION
SET01nn Set output mode
SET02n Set output format
SET03nn Set baud rate
SET04n Set wind speed units
SET05a Set sensor address
SET06nnn Set wind speed threshold
SET07nnnnn Set wind speed multiplier
SET08±nnnn Set direction offset
SET09dd Set damping factor
SET10nnnn Set output interval
SET12nnn Set sample count
SET13n Set wind output format
SET25n Turn compass on/off
SET26nddmm Set compass declination
SET77 Save settings
XX Operate mode
RPTV Report current settings
?? Display command list
HELP Display command list
6.4 COMMAND DETAILS
COMMAND DESCRIPTION
SET01nn Enable RS-232 and RS-485 output modes.
Default value is 04.
Where nn=04 Enable RS-232
08 Enable RS-485 output only
16 Enable RS-485 half duplex
24 Enable RS-485 full duplex
Usage example:
>SET0104 Enables RS-232 only.
SET02n Set the serial output format. Default value is 2.
Where n= 1 RMYT
2 ASCII
3 ASCII POLLED
4 NMEA
5 SDI-12
Usage example:
>SET022 Sets output to ASCII continuous. Note: If SDI-12
is selected, save settings (SET77) then power
must be cycled off, then on again to operate
properly. SDI-12 automatically sets baud rate
to 1200 and disables RS-232 and RS-485.
SET03nn Set the baud rate for RS-232/RS-485 serial
communication. Default value is 96. Note: Baud
rate must be the same as connected device.
Where nn=12 1200 baud
48 4800 baud
96 9600 baud
19 19200 baud
38 38400 baud
Usage example:
>SET0338 Sets baud rate to 38400.
SET04n Set wind speed units (ASCII, ASCII POLLED, NMEA
and SDI-12). Default value is 4.
Where n= 1 mph
2 knots
3 mph
4 m/s
Usage example:
>SET044 Sets wind speed to m/s.
SET05a Set sensor address for ASCII POLLED and
SDI-12. Note: This is the address when
polling with the “aM!” command (SDI-12) and
‘Ma!’ command (ASCII Polled) where 'a' is the
address. Default value is 0.
Where a= 0-9, A-Z, or a-z
Usage example:
>SET052 Sets polling address to number 2.
SET06nnn Set the wind speed threshold. Minimizes erratic
wind direction indications at very low wind
speeds. In polar mode, this allows the sensor
output to mimic a mechanical wind vane that
retains its orientation when there is no wind.
Default value is 25.
Where nnn= 000-150 cm/s
Usage example:
>SET06025 Sets wind speed threshold to 25 cm/s.
SET07nnnnn Set wind speed multiplier. Value is x10000. All
wind speed measurements are multiplied by this
parameter. Default value is 10000 for a multiplier
of 1.0000.
Where nnnnn= 00000-30000
Usage example:
>SET0709909 Sets multiplier to 0.9909
>SET0710023 Sets multiplier to 1.0023
SET08±nnnn Set wind direction offset. Value is degrees x10
and may be positive or negative. Wind direction
is always re-scaled to a 0-360 range after offset
is applied. Default value is 00000.
Where ±nnnn= -3600 to +3600
Usage example:
>SET08-0012 Offsets wind direction reading by -1.2 degrees
>SET08+0005 Offsets wind direction reading by +0.5 degrees
SET09dd Set damping factor. Default value is 00. This
means no damping is applied. High damping
values at long output intervals can slow the rate
at which indicated wind values change. Wind
measurement outputs are damped using the
following formula:
Sdamped = [(dd-1) * Sdamped + Ssample] / dd
Where dd= Damping factor (00-99)
Sdamped = New or last damped wind speed
Ssample = New wind speed
Usage example:
>SET0905 Sets damping factor to 5 (Note: Damping
factor only applies to wind reading.)

Page 8
91000-90(B)
SET10nnnn Set output interval. Sets the time interval
between measurements in one millisecond
increments. Lower values increase power
consumption when continuous measurements
are taken. Default is 1000.
Where nnnn= 0000-9999
Usage example:
>SET101000 Sets output interval to 1000 milliseconds
(1 second) (Note: If output interval is set
too low, the ResponseONE will automatically
calculate the minimum output interval.)
SET12nnn Set sample count. The rate at which the sensor
internally takes complete sonic wind samples
is greater than 200 times per second. This
command sets the number of internal samples
used to calculate the median measurement
result. Default is 16.
Where nnn= 000-800
Usage example:
>SET12016 Sets sample count to 16.
More internal samples consume more power
while providing greater immunity to conditions
like turbulent high-speed wind. Fewer samples
consume less power while providing less
immunity to disruptive conditions. This command
interacts with the OUTPUT INTERVAL setting.
More samples may require a longer output
interval.
SET13n Set ASCII output format. Determines whether
ASCII and ASCII POLLED serial outputs provide
wind data in either Polar (speed and direction)
or Cartesian (UV) form. Default is Polar.
Where n= 0 Polar
1 Cartesian (UV)
Usage example:
>SET130 Sets output format to polar.
SET25n Turn compass on or off. Default is 0.
Where n= 0 Off
1 On
Usage example:
>SET251 Turns compass on. Note: This command should
only be used if the sensor has been calibrated at
current location. Calibration automatically turns
on compass.
SET26nddmm Set compass (magnetic) declination.
M a g n e t i c d e c l i n a t i o n i s t h e a n g l e
between magnetic north and true north.
Where n= E, W, or 0 (East, West, or none)
dd= 00 to 90 degrees
mm= 00 to 60 minutes
Usage example:
>SET26W0606 Set declination to West 6° 6’ (zip code 49686)
SET77 Save all settings to non-volatile memory. Any
settings which have not been saved will be
lost when power is removed. Saved settings
are loaded at power up. This command may
be used any time the sensor is in COMMAND
MODE. Note: ResponseONE CONFIG
program automatically sends this command
when <Send Parameters> button is pressed.
XX Returns the sensor to OPERATE MODE
RPTV Report current settings
?? Display command list
HELP Display command list

Page 9
91000-90(B)
7.0 EXAMPLE SETTINGS
Suggested settings. Not all possible setting combinations are shown.
The ResponseONE CONFIG program is recommended for changing
setup parameters. See wiring diagrams for jumper settings.
7.1 FACTORY DEFAULT
RS-232 Enabled
RS-485 Disabled
Serial Output Format: ASCII
Output Interval 1000
Sample Count: 16
7.2 MINIMUM POWER
RS-232 Enabled
RS-485 Disabled
Serial Output Format: ASCII
Output Interval 1000
Sample Count: 16
7.3 HIGH WIND
Output Delay: 1000
Sample Count: 200
AVERAGE CURRENT DRAW AT 12V
Output Format
Output
Interval
Sample
Count
Baud Rate
(bps)
Average
Current Draw
(mA)
5 minutes 16 1200 4.5
5 minutes 100 1200 4.5
1 second 16 9600 8.4
1 second 100 38400 20.7
ASCII Polled 5 minutes 16 9600 5.8
1 second 16 4800 7.4
1 second 50 4800 12.4
0.25 second 16 9600 15.6
1 second 200 9600 34.2
Table Typical current draw per output format.
NMEA
ASCII
SDI-12 (polled)
RMYT
8.0 EMC COMPLIANCE
This device complies with Part 15 of the FCC Rules. Operation
is subject to the following two conditions: (1) this device may not
cause harmful interference, and (2) this device must accept any
interference received, including interference that may cause
undesired operation.
This equipment has been tested and found to comply with the
limits for a Class A digital device, pursuant to part 15 of the FCC
Rules. These limits are designed to provide reasonable protection
against harmful interference when the equipment is operated in a
commercial environment. This equipment generates, uses, and
can radiate radio frequency energy and, if not installed and used
in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment
in a residential area is likely to cause harmful interference in which
case the user will be required to correct the interference at his own
expense.
This ISM device complies with Canadian ICES-001.
Cet appareil ISM est conforme à Ia norme NMB-001 du Canada.
EN55011/CISPR 11, Group 1, Class B device.
Class B equipment is suitable for use in domestic establishments
and in establishments directly connected to a low voltage power
supply network which supplies buildings used for domestic
purposes.
9.0 WARRANTY
This product is warranted to be free of defects in materials and
construction for a period of 12 months from date of initial purchase.
Liability is limited to repair or replacement of the defective item. A copy
of the warranty policy may be obtained from R. M. Young Company.
10.0 CE COMPLIANCE
This product has been tested and complies with European
CE requirements for the EMC Directive. Please note that shielded
cable must be used.

Page 10
91000-90(B)
SETTINGS
Output Mode: RS-232
Output Format: ASCII, ASCII POLLED, or NMEA
Baud Rate: 1200, 4800, 9600, 19200 or 38400
Set connected device baud rate to match
ResponseONE
.
1 start bit, 8 data bits, no parity, 1 stop bit, no flow control.
Use shielded cable. Connect cable shield to earth ground as shown.
(Color code is for Young 18446 cable)
Figure A1: RS-232 SERIAL CONNECTION
Serial Device
SDI
Z
B
A
TX
RX
P2
JUMPER
P2
JUMPER
Z.SDI
Y
TX.B
RX.A
REF
+PWR
-PWR
EARTH GND
WHT
GRN
BRN
RED
BLK
Earth Ground
(+)
(-)
Supply Voltage 10-30 VDC
80mA max
92000
RESPONSE ONE
5 3 2
Typical DB-9
RS-232 Connection
Z.SDI
Y
TX.B
RX.A
REF
+PWR
-PWR
EARTH GND
WHT
BLU
GRN
ORG
BRN
RED
BLK
Earth Ground
(+)
(-)
Supply Voltage 10-30 VDC
80mA max
Sensor TX (Z Inverted signal)
Sensor TX (Y Non-inverted signal)
Sensor RX (B Inverted signal)
Sensor RX (A Non-inverted signal)
Signal Reference
SDI
Z
B
A
TX
RX
P2
JUMPER
P2
JUMPER
SETTINGS
Output Mode: RS-485 Full Duplex
Output Format: ASCII, ASCII POLLED, or NMEA
Baud Rate: 1200, 4800, 9600, 19200 or 38400
Set serial device baud rate to match
ResponseONE
.
1 start bit, 8 data bits, no parity, 1 stop bit, no flow control.
Use shielded cable. Connect cable shield to earth ground as shown.
(Color code is for Young 18660 Cable)
Figure A2: RS-485 / RS-422 SERIAL CONNECTION - FULL DUPLEX
Serial Device
92000
RESPONSE ONE
APPENDIX A: WIRING CONNECTIONS

Page 11
91000-90(B)
Z.SDI
Y
TX.B
RX.A
REF
+PWR
-PWR
EARTH GND
WHT
GRN
BRN
RED
BLK
Earth Ground
(+)
(-)
Supply Voltage 10-30 VDC
80mA max
Sensor TX/RX (Inverted signal)
Sensor TX/RX (Non-inverted signal)
Signal Reference
SDI
Z
B
A
TX
RX
P2
JUMPER
SETTINGS
Output Mode: RS-485 Half Duplex
Output Format: ASCII, ASCII POLLED, or NMEA
Baud Rate: 1200, 4800, 9600, 19200 or 38400
Set serial device baud rate to match
ResponseONE
.
1 start bit, 8 data bits, no parity, 1 stop bit, no flow control.
Use shielded cable. Connect cable shield to earth ground as shown.
(Color code is for Young 18446 Cable)
Figure A3: RS-485 / RS-422 SERIAL CONNECTION - HALF DUPLEX
Serial Device
SETTINGS
Output Mode: RS-485 Output Only
Output Format: ASCII, or NMEA
Baud Rate: 1200, 4800, 9600, 19200 or 38400
Set serial device baud rate to match
ResponseONE
.
1 start bit, 8 data bits, no parity, 1 stop bit, no flow control.
Use shielded cable. Connect cable shield to earth ground as shown.
(Color code is for Young 18446 Cable)
Figure A4: RS-485 / RS-422 SERIAL CONNECTION - OUTPUT ONLY
Serial Device
SDI
Z
B
A
TX
RX
P2
JUMPER
Z.SDI
Y
TX.B
RX.A
REF
+PWR
-PWR
EARTH GND
WHT
GRN
BRN
RED
BLK
Earth Ground
(+)
(-)
Supply Voltage 10-30 VDC
80mA max
Sensor TX (Z Inverted signal)
Sensor TX (Y Non-inverted signal)
Signal Reference
92000
RESPONSE ONE
APPENDIX A: WIRING CONNECTIONS

Page 12
91000-90(B)
Z.SDI
Y
TX.B
RX.A
REF
+PWR
-PWR
EARTH
GND
WHT
BLU
GRN
ORG
BRN
RED
BLK
P2
JUMPER
SDI
Z
B
A
TX
RX
P2
JUMPER
Earth
Ground
Connection
SHIELD
BRN
WHT
BLU
GRN
ORG
BLK
RED
Signal Ref
Sensor TX Z
Sensor TX Y
Sensor RX B
Sensor RX A
PWR Ref
+Sensor PWR
Figure A6: RS-485 SERIAL CONNECTION - FULL DUPLEX
Model 26800
Translator
SETTINGS
Output Mode: RS-485 Full Duplex
Output Format: ASCII, ASCII POLLED, or NMEA
Baud Rate: 1200, 4800, 9600, 19200 or 38400
Set 26800 Translator baud rate to match
ResponseONE
.
Use shielded cable. Connect cable shield to earth ground as shown.
(Color code is for Young 18660 cable)
Z.SDI
Y
TX.B
RX.A
REF
+PWR
-PWR
EARTH GND
GRN
RED
BLK
Earth Ground
(+)
(-)
Supply Voltage 10-30 VDC
80mA max
To SDI-12 Data Recorder
Use shielded cable.
Connect cable shield to earth ground as shown.
Figure A5: SDI-12 SERIAL CONNECTION
SDI-12
Serial Device
SDI
Z
B
A
TX
RX
P2
JUMPER
APPENDIX A: WIRING CONNECTIONS

Page 13
91000-90(B)
SDI
Z
B
A
TX
RX
P2
JUMPER
P2
JUMPER
SDI
Z
B
A
TX
RX
P2
JUMPER
92000
RESPONSE ONE
SETTINGS
Output Mode: RS-485 Output Only
Output Format: RMYT
Baud Rate: 9600
These are the default sensor settings as shipped unless otherwise requested.
Use shielded cable. Connect cable shield to earth ground as shown.
(Color code is for Young 18446 Cable)
Figure A7: 06201 WIND TRACKER
SETTINGS
Output Mode: RS-485 Output Only
Output Format: NMEA
Baud Rate: 4800
Use shielded cable. Connect cable shield
to earth ground as shown.
(Color code is for Young 18446 Cable)
Figure A8: 06206 MARINE WIND TRACKER
GND
EXC
WS
WD
REF
B
A
WD
WD
WS
WS
WS
WD
REF
+PWR
-PWR
ALARM V OUT
Z.SDI
Y
TX.B
RX.A
REF
+PWR
-PWR
EARTH GND
WHT
GRN
BRN
RED
BLK
Earth
Ground
GND
EXC
WS
WD
REF
B
A
WD
WD
WS
WS
WS
WD
REF
+PWR
-PWR
ALARM V OUT
Z.SDI
Y
TX.B
RX.A
REF
+PWR
-PWR
EARTH GND
WHT
GRN
BRN
RED
BLK
Earth
Ground
APPENDIX A: WIRING CONNECTIONS

Page 14
91000-90(B)
135 mm
26 mm
220 mm
MOUNTING
PIPE
INSERTION
80 mm
ORIENTATION
RING
N
W
E
S
JUNCTION
BOX
270°
90°
180°
POLAR
(WIND SPEED, WIND DIRECTION)
0°
EXAMPLE:
"WIND AT 45° "
+V m/s
"WIND FROM NORTH"
CARTESIAN
(U, V)
+U m/s
"WIND FROM EAST"
APPENDIX B: SENSOR ORIENTATION AND DIMENSIONS
APPENDIX B: SENSOR ORIENTATION AND DIMENSIONS

Page 15
91000-90(B)
APPENDIX C: TROUBLESHOOTING
Problem Solution
No Output • Check input voltage at sensor (10 – 30 VDC).
• Check wiring connections.
• Verify serial settings (baud rate, 1 stop bit, 8 data bits, no parity, no ow control).
• ‘Acquire’ the sensor with the ResponseONE CONFIG program (see section 6.2)
and verify setup mode.
One-way
communication
• Check wiring connections.
• ‘Acquire’ the sensor with the ResponseONE CONFIG program (see section 6.2).
• Change output mode to RS-485 full or half duplex, or RS-232.
Status codes
other than 00
appear
• Status codes other than 00 (or ‘A’ in NMEA mode) mean there is an error. See
‘Status Codes’ section for details.
No response to
poll command
• Check power supply.
• Check wiring connections.
• Verify serial settings (baud rate, 1 stop bit, 8 data bits, no parity, no ow control).
• Verify sensor address (if the sensor’s address is ‘0’, then the poll command is ‘0M!’
in SDI-12 mode and 'M0! in ASCII Polled mode.).
• ‘Acquire’ the sensor with the ResponseONE CONFIG program (see section 6.2)
and verify setup mode.
Direction is
incorrect
• If compass is off, make sure junction box is facing south.
• ‘Acquire’ the sensor with the ResponseONE CONFIG program (see section
6.2) and verify settings. Enable and calibrate compass if needed, enter compass
declination, and set the wind direction offset (default is 0000).
• Turn compass on and calibrate if needed.
Status codes for ASCII output are hex values added together before output (a status code of 03 would be a
code of 01 and 02). NMEA only allows for ‘acceptable’ or ‘void’ data. SDI-12 does not show a status code.
Status Code Meaning
00 Valid data
01 Transducer path A blocked or dirty, clear blockage and clean transducers
02 Transducer path B blocked or dirty, clear blockage and clean transducers
04 Transducer path C blocked or dirty, clear blockage and clean transducers
A NMEA data acceptable (NMEA wind data only)
V NMEA data void (NMEA wind data only)
Table of contents
Other Young Measuring Instrument manuals

Young
Young Wind Sentry 03002V User manual

Young
Young 03102L User manual

Young
Young 86004 User manual

Young
Young 05631C User manual

Young
Young 27106T User manual

Young
Young Wind Sentry Series User manual

Young
Young 81000 Reference manual

Young
Young 03002L User manual

Young
Young 81000V User manual

Young
Young 09101 User manual
Popular Measuring Instrument manuals by other brands

Pintek
Pintek PA-622 instruction manual

Keysight Technologies
Keysight Technologies N5224/5A Service guide

Indu-Sol
Indu-Sol EmCheck ISMZ I user manual

bluelab
bluelab Commercial trunchelon nutrient meter Care and use guide

Agilent Technologies
Agilent Technologies U1401B User's guide and service guide

ModMAG
ModMAG M1000 user manual