
1
INSTALLATION
NOTE: Prior to installation of the ZW215FP, ensure that all debris
is ushed out the piping system before installed.
1. During the installation of a ZW215FP in a sprinkler system, verify
installation meets requirements of local law or the Authority Having
Jurisdiction.
2. Allow for adequate space around the valve for making adjust-
ments and servicing.
3. PositiontheZW215FPinlinematchingthedirectionofowas
indicatedonthevalvemodeltagwiththeproperdirectionofowin
the system. The valve must be installed on the discharge side of the
repump.
4. Connect pilot control sensing connection to the suction side of
the pump by minimum 3/8 in diameter tubing.
5. Once control valve and sensing line are installed, double check
all fasteners/bolts in the pilot system and on main valve are tight and
there is no damage prior to pressurizing system.
NOTE: Pressure in some applications can be very high so be
thorough in checking and inspecting for proper installation and
makeup.
6. Zurn Wilkins valves are designed to operate in both the vertical
and horizontal positions. However, it is recommended that ZW215FP’s
6” and larger, be installation in the horizontal position. The horizontal
positioning of the larger valves avoids premature wear due to mass of
plunger assemblies as well as allows for greater accessibility during
annual inspections, and maintenance.
START-UP
CAUTION: To prevent personnel injury and damage to equip-
ment check that downstream venting is adequate prior to
start-up and test procedures. All adjustments under pressure
should be made slowly. If the main valve opens or closes too fast
it may cause surging in upstream piping.
Installation Start-up Maintenance Instructions
Model ZW215FP
Fire Pump Suction Control Valve
Globe and Angle Pattern Bodies
2", 2-1/2", 3", 4", 6", 8", & 10"
ZW215FP
Class 150 Flanged
Max 250 psi Inlet
ZW215FPG
Grooved
Max 300 psi Inlet
ZW215FPY
Class 300 Flanged
Max 300 psi Inlet
1. Pressurize the upstream side of the ZW215FP.
2. Asthevalveisllingwithwater,itisnecessarytobleedthemain
valve and pilot system of air. To vent air, partially open or loosen the
highestplugsorttingsinthesystem.TheZPIvalvepositionindicator
is a great location, as it has a test cock at the top to vent air pressure.
It may be necessary to bleed system more than once. After removal of
airinthesystemtightenallloosettings.NOTE: If valve is installed
vertically, it will be necessary to loosen some upper cover bolts
until you have vented all the air from the cover chamber.
3. Install a pressure gauge on the suction side of the pump or install
a gauge in the test cock on the sensing line to read the suction pres-
sure.
4. Loosen the pilot adjustment screw until the adjustment screw
can be turned by hand. Note: A small amount of spring force must
be maintained so the spring and spring discs do not fall out of
alignment. Do not loosen the pilot adjustment screw completely.
Note: The control valve should open and allow a lot of water to
ow. If there is no ow, continue turning the pilot adjustment screw
counterclockwise.Oncewaterisowingthroughthecontrolvalveit
is necessary to lower the suction pressure below the desire set pres-
sure. One can cause the suction pressure to decrease by increasing
owthroughthepumporusingavalveupstreamofthepumpsuction
to throttle water to the pump.
5. Once suction pressure is below desired minimum suction pres-
sure, slowly turn the pilot valve adjustment screw clockwise. As the
screw is tightened the control valve will slowly start to close causing
upstream pressure to increase. Continue turning adjustment screw
clockwise until suction pressure is stable at the desired set pressure.
6. Tighten adjustment screw jam nut once step 4 is completed. To
verify proper operation of the ZW215FP, view the valve during normal
operation and check the valve for minimum suction pressure setting.
Adjustments can be made at anytime.
Installation / Start-up
DESCRIPTION
The Zurn Wilkins Model ZW215FP Fire Pump Suction Control Valve
isdesignedspecicallyforFireSuppressionSystemstopreventre
pumps from over-drawing from the water supply resulting in damage
to the pump or the supply network because of very low or negative
pressuresonthesuctionsideoftherepump.Thepilotassembly
reacts quickly to increases and decreases of suction pressure.
The control valve will close if suction pressure drops below the set
pressure. The control valve will open again once suction pressure
rises to the control valve set pressure and will modulate to keep
the suction pressure at the set pressure until supply increases. In
addition the Model ZW215FP comes standard with red epoxy coat-
ing internally and externally for corrosion protection, as well as a
test cock on the sensing port for quick bleeding of sensing line. The
ZW215FP is available in both globe and angle pattern bodies.
ZW215FPTH
Threaded
Max 300 psi Inlet
ZURN WILKINS
1747 Commerce Way, Paso Robles, CA 93446 Phone:855-663-9876 Fax:805-238-5766
www.zurn.com
FM
APPROVED
!WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov
!ADVERTENCIA: Cáncer y daño reproductivo - www.P65Warnings.ca.gov
!AVERTISSEMENT: Cancer et néfastes sur la reproduction - www.P65Warnings.ca.gov