The switch module a d its actuati g eleme t
may be used o ly withi the specified ambie t
a d operati g temperature ra ge.
Utiliz
atio i areas other tha those specified or
the alteratio of the produ
tha the ma ufacturer will exempt BARTEC
from liability for defects or a y further liability.
I correct i stallatio ca cause malfu ctio i g
a d the loss of explosio protectio .
The ge erally applicable statutory rules a d
other bi di
g directives relati g to workplace
safety, accide t preve tio a d e viro me tal
protectio must be observed.
Before commissio i g or restarti g operatio ,
check complia ce with the applicable laws a d
directives.
The switch module may be used o ly if it i
clea a d ot damaged i a y way.
permissible to modify the module i a y way.
Marking
Particularly importa t poi ts i these i struc-
tio s are marked with a symbol:
DANGER i dicates a hazardous situatio
which, if ot avoided, will result i death
serious i jury.
WARNING i dicates a hazardous
which, if ot avoided, could
serious i jury.
CAUTION i dicates a hazardous situatio
which, if ot avoided, could result i mi or
moderate i jury.
NOTICE is used to address practices ot
related to perso al i jury.
Note
Important instructions and information on
effective, economical and environmentally
compatible handling.
Standards con ormed to
IEC 60079-0:2007
EN 60079-0:2009
IEC/EN 60079-1:2007
IEC 60079-7:2006
EN 60079-7:2007
DIN EN 60068-2-27:2010, 30 g, 18 ms
Switch module damage through incorrect
transport or incorrect storage.
Tra sport a d storage is permissible i
origi al packagi g o ly.
Assembly, Installation, and
Commissioning
Risk o serious injury due to incorrect
proceedings.
O ly authoriz
ed a d qualified perso el
may do a y of the assembly, disassembly,
i stallatio a d commissio i g work.
Use suitable tools.
Assembly/disassembly
Mou ti g the switch module:
•Make sure the switch module to be at-
tached is i tact ( o cracks).
•
Positio the switch module’s bayo et lock
at the mou ted actuati g eleme t.
•
Tur the closi g latch to co ect the
switch module securely to the actuati g
eleme t.
Note
The assembly of the actuating element as well
as the assembly of the switch module and the
actuating element is described in the operating
instructions for actuating elements, type
05-0003-00../....
Installation
I hazardous areas groups I a d II, the swi
module must be used:
–
I appropriate e closures with “Ex e”
i creased safety type of protectio . The
cleara ce a d creepage dista ces u der
IEC/EN 60079-
a d Table 1 must be observed.
–
I a e closure that correspo ds to
a other approved type of protectio spe-
cified i IEC/EN 60079-0 Sectio 1.
Take care whe co ecti g co ductors:
•Strip 40 mm (1.6 i ) sheath off the co -
ductor.
•Remove approx. 6 mm (0.2
i sulatio from the cores.
•Prepare the e ds of fi e-stra ded
multi-
stra ded co ductors: Crimp wire e d
sleeves with suitable crimpi g tools.
Co ectio cross-sectio s: 0.75-2.5 mm
2
(14-18 AWG).
•Release termi als.
•I sert co ductors.
•
Tight the termi als with a maximum
torque of 0.4-0.7 Nm.
Co tact arra geme ts:
Type 073323-1100
2 N/C co tacts
Type 07-3323-1200
2 N/O co tacts
Type 07-3323-1400
1 N/O co tact a d 1 N/C co tact
Commissioning
Before commissio i g, check that:
•The device has bee i stalled i compli-
a ce with regulatio s.
•The device is ot damaged.
•
The co ectio has bee established
properly (make sure the cores are se-
cure).