Page 2 of 5
Safety First
BERMAD believes that the safety of personnel working with and around our equipment is the most important consideration. Please read
all safety information below and any other relevant source before attempting to perform any maintenance function.
Comply with all approved and established precautions for working with your type of equipment and/or environment. Authorized
personnel should perform all maintenance tasks.
Prior to performing a procedure, read it through to the end and understand it. If anything is unclear, ask the appropriate authority. When
performing a procedure, follow the steps in succession without omission.
1. Description
Bermad FP-3HC-0 Pressure-Relief Valve is an adjustable direct acting, diaphragm type, pressure relief valve, automatically relieving at the
chosen pre-set inlet pressure. It is suitable to for use as a pressure safety relief valve (PSV) downstream of a pressure control valve, a
thermal pressure relief valve for piping systems or as a Fire Pump Casing Relief Valve.
2. Specifications
2.1 Rated Pressure: 25 bar / 365 psi
2.2 Temperature rating: 80°C / 180°F (max water temperature)
2.3 Process Connections: 3/4" ISO-7 Rp
2.4 Pressure gauge connection: 1/4" NPT (F)
Table 1 Adjustment Range:
Model Adjustment Pressure Range In field adjustment
bar psi 1 turn of adjusting screw = approx.
FP-3HC-0-16 1 - 16 15 - 235 FP-3HC-0-16 1-16 15-235
FP-3HC-0-30* 7 - 25 100 - 365 1.8 bar/25.7 psi
* With high pressure setting kit
3. Installation
Be sure to use qualified personnel when installing, operating and maintaining this valve.
Prior to installation inspect the valve for any damage that may have been caused during shipment and ensure all ports are clean and
free from any obstructions.
The valve can be installed in any orientation, vertical or horizontal.
Be sure not to install the valve at any low point or at the bottom of the piping, where accumulated debris might enter the valve and
hamper correct functioning.
The valve will occasionally open to release over pressure, expelling water to the atmosphere. Where relevant, install piping to direct
the expelled water to a preferred drainage point.
NOTE: Model FP-3HC-0 is suitable for minimum flow fire pump applications, it is not suitable for discharging the full-rated pump
capacity of a fire pump. For full rated fire pump relief valves please select fire pump relief valve sized as per NFPA 20.
3.1 Before installing the valve, flush the pipeline to remove any scale, debris, etc.
Warning: not flushing the line may result in rendering the valve inoperable.
3.2 The BERMAD FP-3HC-0 relief valve maybe installed in any position, vertical horizontal or otherwise.
3.3 Select the valve position and orientation that will facilitate the future maintenance, adjustment and inspection.
3.4 Install the valve in the pipeline with the valve flow arrow on the body in the proper direction.
3.5 Ensure an unrestricted relief passage from the valve to the atmosphere.
3.6 Install a drainpipe with appropriate fitting facing downward at the FP-3HC-0 valve discharge port to prevent blockage.
3.7 Install the valve above or at the middle of the pipeline to avoid the accumulation of debris upstream of the FP-3HC-0 valve.