CDVI SOLARPW User manual

The installer’s choice
cdvigroup.com
SOLARPW
SOLARPB
STARPW
STARPB
SOLARPW
STARPW
SOLARPB
STARPB
Lector de proximidad Wiegand 125 kHz
Wiegand 125 kHz Proximity Readers
ESPAÑOL
ES
ENGLISH
EN

2cdvigroup.com
Wiegand 26, 30 o 44 bits.
Conexión directa a control de accesos o a
través de controlador de puerta (INTBUSW).
Electrónica sellada con resina epoxi.
Señalización visual y sonora.
Cable de 3 metros (STARPW-STARPB).
Disponible en blanco y negro.
SOLARP (A x A x P): 130 x 90 x 28 mm.
STARP (A x A x P): 130 x 41 x 28 mm.
Tecnología: 125 kHz.
Protococolo: Marin y HID.
Alimentación: 12 Vcc.
Consumo: 100 mA.
1] PRESENTACIÓN DE PRODUCTO
3] ELEMENTOS INCLUIDOS
2] NOTAS Y RECOMENDACIONES
Junta de
espuma Junta de
espuma Tornillo
TF 3x30 Taco de
jación S5
Cabezal para
destornillador
TORX®
Tornillo TORX®
3x8 Varistor
SOLARPW(PB) 1 - 2 2 1 1 1
STARPW(PB) -122111
Recomendaciones de
instalación
Para asegurar el sistema,
no se olvide de instalar un
varistor en paralelo a cada
uno de los dispositivos de
cierre.
Cable recomendado
Cable 4 pares 6/10
º
(AWG 24).
Fuentes de alimentación
ADC335 y BS60, siempre
que el lector no esté ali-
mentado por el control de
accesos o el controlador de
puerta INTBUSW.
Entorno
Si los lectores están en un
entorno cercano al mar o
salino, se recomienda barni-
zar los bornes para prevenir
la oxidación.
Este producto se
suministra con un
varistor.
Un varistor regula las sobre-
tensiones causadas por la
bobina de una cerradura en
su activación o desactivación;
debe conectarse directamente
a los bornes de la cerra-
dura o ventosa gestionada
por el equipo. Si el control
de accesos gestiona varias
cerraduras, cada una debe
tener su propio varistor. En
caso de usar una ventosa de
cizalla u otro tipo de cierre, se
recomienda usar una fuente
de alimentación exclusiva para
el cerradero.
Ref: SOLARPW-SOLARPB Ref: STARPW-STARPB
Para una
iluminación
óptima, no
deje cable
enrollado
en el
interior del
producto
Certicado CE Certicado FCC CFR 47
conforme parte 15
WEEE IP53 -25°C a +70°C
ES
SOLARPW-SOLARPB-STARPW-STARPB
Lector de proximidad Wiegand 125 kHz
MANUAL DE INSTALACIÓN

3cdvigroup.com
1 Mida y marque las posiciones del agujero del cableado
y de los tornillos de jación (diámetros de 15 y 5 mm
respectivamente). Utilice la tapa trasera del lector para
ayudarse.
2 Coloque la junta de espuma en la tapa trasera del
lector comenzando por la parte inferior (Fig. A). La junta
debe sobresalir aproximadamente 2 mm por encima de
la tapa trasera del lector (Fig. B).
4] MONTAJE
Ref: SOLARPW- SOLARPB
Asegúrese de que todas las piezas necesarias están incluidas en la caja del producto. Utilice las herramientas
adecuadas para cada tipo de instalación (taladro, destornilladores, cinta métrica...) y siga las instrucciones de
montaje del lector.
1
3
2
Fig. A
Fig. B
Fig. C
3 Coloque los tacos, pase el cableado y haga las conexiones según el esquema indicado en este manual. Después,
je la tapa trasera a la pared con los tornillos y coloque el lector, aanzándolo con el tornillo TORX® suministrado
(Fig. C). No olvide colocar el varistor en paralelo al dispositivo de cierre utilizado.
Juna de espuma
ES
SOLARPW-SOLARPB-STARPW-STARPB
Lector de proximidad Wiegand 125 kHz
MANUAL DE INSTALACIÓN

4cdvigroup.com
ES
SOLARPW-SOLARPB-STARPW-STARPB
Lector de proximidad Wiegand 125 kHz
MANUAL DE INSTALACIÓN
1 Mida y marque las posiciones del agujero del cableado
y de los tornillos de jación (diámetros de 15 y 5 mm
respectivamente). Utilice la tapa trasera del lector para
ayudarse.
2 Coloque la junta de espuma en la tapa trasera del
lector comenzando por la parte inferior (Fig. A). La junta
debe sobresalir aproximadamente 2 mm por encima de
la tapa trasera del lector (Fig. B).
Ref STARPW-STARPB
1
3
2
Fig. A Fig. B
Fig. C
3 Coloque los tacos, pase el cableado y haga las conexiones según el esquema indicado en este manual. Después,
je la tapa trasera a la pared con los tornillos y coloque el lector, aanzándolo con el tornillo TORX® suministrado
(Fig. C). No olvide colocar el varistor en paralelo al dispositivo de cierre utilizado.
Junta de espuma

5cdvigroup.com
Al conectar el lector
- El LED verde se enciende 1 seg.
- El LED rojo se enciende 1 seg.
- Se emite un pitido durante 1 seg.
Funcionamiento
- Activación de buzzer con 0 V.
- Activación de LED con 0 V.
1
R V B D1 D0 H - +
Bornero (8 puntos)
+Alimentación 12 Vcc
-0 V
HClock
D0 Data 0
D1 Data 1
BBuzzer
VLED verde
RLED rojo
SOLARPW-SOLARPB
Cableado
Rouge Alimentación 12 Vcc
Noir 0 V
Bleu Clock
Vert Data 0
Blanc Data 1
Marron Buzzer
Jaune LED verde
Orange LED rojo
STARPW-STARPB
Funcionamiento de los LED
LED verde LED rojo Estado
OFF OFF Inactivo
OFF ON Rojo
ON OFF Verde
ON ON Azul
1 2
OFF OFF
26 bits
1 2
ON OFF
30 bits
1 2
OFF ON
44 bits
1 2
ON ON
No utilizado
3
ON
Standard
Pulls up 12 V o 5 V
Para salidas de colector abierto,
existen dos posibilidades:
OFF
ON
OFF
ON
OFF
ON
OFF
ON
ON
OFF
ON
4
3
2
1
ONON
ONON
4
3
2
1
ONON
ONON
4
3
2
1
ONON
ONON
4
3
2
1
ONON
ONON
4
3
2
1
ONON
ONON
4
3
2
1
ONON
ONON
OFF = 5 V
ON = 12 V
Presentación de tarjeta
(DIP3 = ON)
- Tag leído: El LED naranja se
enciende durante 0,15 segundos y
se emite un pitido antes de conti-
nuar con la validación.
- Tag no leído: Sin efecto.
4
3
2
1
ONON
ONON
4
3
2
1
ONON
ONON
4
3
2
1
ONON
ONON
4
3
2
1
ONON
ONON
4
3
2
1
ONON
ONON
4
3
2
1
ONON
ONON
4
3
2
1
ONON
ONON
4
3
2
1
ONON
ONON
4
3
2
1
ONON
ONON
4
3
2
1
ONON
ONON
4
3
2
1
ONON
ONON
4
3
2
1
ONON
ONON
5] ESQUEMA DE CABLEADO
C56
C58
C61
1
MM10
4
3
2
1
ON
ON
ON
ON
L7
Q6
Q7
Q8
R77
R78
R79
P1
1P3
BZ3
C6
C24
C59
-
+
MM1
MM14
CR3
+
-
CR10
CR25
CR26
CR24
MM3
MM15
CR12
CR13
CR15
I1
+
-
+
-
MM16
CR22
P2
-
+
CR19
CR21
CR20
CR28
CR27
CR29
CR11
R70
R67
R68
R64
R69
R65
C68
CR30
4 1
ON
4
1
ON
Posicionamientos
dipswitch 1 y 2
Pocisionamiento dipswitch 3
Posicionamiento dipswitch 4
ES
SOLARPW-SOLARPB-STARPW-STARPB
Lector de proximidad Wiegand 125 kHz
MANUAL DE INSTALACIÓN

6cdvigroup.com
6] FORMATO DE SALIDA WIEGAND 26, 30 Y 44 BITS
Cronogramas
Salidas en colector abierto con pull ups internos de 1 K a +5 o +12 V según posición de dipswitch ST4.
Formato Wiegand 26 bits
Formato de 26 bits hexadecimal. La comunicación se efectúa por una conexión Wiegand de 26 bits (señales:
DATA1, DATA0 y CLOCK) en la que la trama se descompone de la siguiente manera:
1 - Primera paridad: 1 bit – paridad par de los primeros 12 bits.
Código del tag: 6 mitades de un byte que representan los últimos 6 dígitos del código (4 bit = 1 dígito).
Cada byte se transmite desde el bit 7 al bit 0.
2 - Segunda paridad: 1 bit – paridad impar de los últimos 12 bits.
Bit 1 Bit 2 a bit 25 Bit 26
Paridad par de bit 2 a bit 13 Datos (24 bits)
Paridad impar de bit 14 a bit 25
Ejemplo: para una tarjeta donde el código hexadecimal es 0100166A37.
1 0001 0110 0110 1010 0011 0111 0
Paridad 1 1 6 6 A 3 7 Paridad 2
El código que se transmite en hexadecimal es 166A37.
Paridad 1: «0» si el número de 1 desde el bit 2 al bit 13 es par.
«1» si el número de 1 desde el bit 2 al bit 13 es impar.
Paridad 2: « 0» si el número de 1 desde el bit 14 al bit 25 es impar.
«1» si el número de 1 desde el bit 14 al bit 25 es par.
Lógica 0
\DATA1
\CLOCK
\DATA0
50 μs 50 μs
2ms 2ms
Lógica 1
ES
SOLARPW-SOLARPB-STARPW-STARPB
Lector de proximidad Wiegand 125 kHz
MANUAL DE INSTALACIÓN

7cdvigroup.com
Formato Wiegand 30 bits
Formato de 30 bits hexadecimal. La comunicación se efectúa por una conexión Wiegand de 30 bits (señales:
DATA1, DATA0 y CLOCK) en la que la trama se descompone de la siguiente manera:
1 - Primera paridad: 1 bit – paridad par de los primeros 14 bits.
Código del tag: Se forma con 7 mitades de un byte.
Cada byte se transere desde el bit 7 al bit 0.
2 - Segunda paridad: 1 bit – paridad impar de los últimos 12 bits.
Bit 1 Bit 2 a bit 29 Bit 30
Paridad par de bit 2 a bit 15 Datos (28 bits) Paridad impar de bit 16 a bit 29
Ejemplo A: para una tarjeta cuyo código decimal es 689905 (en hexadecimal: A86F1).
1 0000 0000 1010 0110 0110 1111 0001 0
Paridad 1 0 0 A 8 6 F 1 Paridad 2
El código que se transmite en hexadecimal es 00A86F1.
Ejemplo B: para una tarjeta cuyo código hexadecimal es 0100166A37.
1 0000 0000 0001 0001 0110 1011 0110 1
Paridad 1 0 0 6 6 A 3 7 Paridad 2
El código que se transmite en hexadecimal es 0166A37.
Paridad 1: «0» si el número de 1 desde el bit 2 al bit 15 es par.
«1» si el número de 1 desde el bit 2 al bit 15 es impar.
Paridad 2: «0» si el número de 1 desde el bit 16 al bit 29 es impar.
«1» si el número de 1 desde el bit 16 al bit 29 es par.
Formato Wiegand 44 bits
Formato de 44 bits hexadecimal. La comunicación se efectúa por una conexión Wiegand de 44 bits (señales:
DATA1, DATA0 y CLOCK) en la que la trama se descompone de la siguiente manera:
Datos: SN de 10 dígitos en hexadecimal (MSByte en primer lugar).
Cada dígito en hexadecimal = 4 bit (MSBit en primer lugar).
LRC : 4 bit = O restringido entre los dígitos de los datos (MSBit en primer lugar).
Bit 1 a bit 40 Bit 41 a bit 44
SN de la tarjeta, MSBit primero LRC
Ejemplo: para una tarjeta EM cuyo SN en hexadecimal es 01001950C3.
0000 0000 0000 0000 0001 1001 0101 0000 1100 0011 0011
01001950C33
El código que se transmite en hexadecimal es 01001950C3.
ES
SOLARPW-SOLARPB-STARPW-STARPB
Lector de proximidad Wiegand 125 kHz
MANUAL DE INSTALACIÓN

8cdvigroup.com
7] GESTIÓN DE LED EN EL SISTEMA DE CONTROL DE ACCESOS CENTAUR
AJUSTES DEL
LED VERDE
AJUSTE DEL
LED ROJO
VERDE ACCESO CONCEDIDO
ROJO ACCESO DENEGADO
AZUL EN STAND-BY
SIGNIFICADO
DE LED
8] NOTAS
ES
SOLARPW-SOLARPB-STARPW-STARPB
Lector de proximidad Wiegand 125 kHz
MANUAL DE INSTALACIÓN

9cdvigroup.com
Wiegand 26, 30 or 44 bit.
Direct connection.
PCB sealed in epoxy.
Audible and visual feedback.
45cm pigtail wire connection (STARPW-STARPB).
Versions available: white, black or grey.
SOLARPW-SOLARPB (L x W x D): 130 x 90 x 28mm.
STARPW-STARPB (L x W x D): 130 x 41 x 28mm.
Technology: 125 Khz.
Multi card protocol reader - Marin/HD.
Input voltage: 12V dc.
Consumption: 100mA.
1] PRODUCT PRESENTATION
3] MOUNTING KIT
2] REMINDERS AND RECOMMENDATIONS
Foam seal Foam seal 3x30
TF screw S5
Plastic anchor TORX® bit 3x8
TORX®screw Varistor
SOLARPW(PB) 1 - 2 2 1 1 1
STARPW(PB) -122111
Important
To protect the device
from back-emf, do not
forget to install the varistor
across the lock terminals,
in parallel.
Suggested
power supplies
ARD12 & BS60 (in case
the reader is powered
neither by the controller
nor by the reader controller
[INTBUSW]).
Recommended cables
4 twisted pairs 0.6mm (AWG 24).
Environment
When in a humid area or
close to the sea, we recom-
mend applying varnish to the
terminals to avoid oxidation.
This product is supplied
with a varistor.
The varistor must be connec-
ted directly to the locking
system terminals (electric
strikes, electromagnet, or
lock) operated by the device.
If the device functions with
several locking systems,
each one must be tted with
a varistor. The varistor limits
overload produced by the
strike coil, known as self-
effect or back-emf. If you are
using a “Shear Lock”, elec-
tromagnet or other type of
electric lock, we recommend
the use of a dedicated power
supply for the lock.
For optimal
illumination,
do not fold
the cable
inside the
product.
CE Certication Certication FCC CFR 47
part 15 compliance
WEEE IP53 -25°C to +70°C
Ref : SOLARPW-SOLARPB Ref : STARPW-STARPB
EN
SOLARPW-SOLARPB-STARPW-STARPB
Wiegand 125 kHz Proximity Readers
INSTALLATION MANUAL

10 cdvigroup.com
3
1 Measure and mark the center lines to determine the
reader position. Drill the xing screw holes (Diameter:
5mm). Drill the wiring access area (Diameter: 15mm).
2 Place the foam seal at the back of the reader. Take
care to begin from the bottom. (Sch. a). The foam seal
must be visible (about 2mm) on the top-back of the rea-
der (Sch. b).
4] MOUNTING
Ref: SOLARPW-SOLARPB
Make sure that there are no pieces missing from the mounting kit. Use the correct tools according to the installa-
tion (drill, screwdrivers, tape measure,...) and follow the mounting instructions of the reader.
1 2
Sch. a
Sch. b
g. c
Sch. c
Foam seal
3 Insert the plastic plugs in the mounting holes, connect the cable (refer to wiring diagram on page 11), then fasten
the reader with the TORX® screw using the TORX® bit (Sch. c). Make sure that the varistor is connected across the
lock (refer to page 8 “Reminders and recommendations”).
EN
SOLARPW-SOLARPB-STARPW-STARPB
Wiegand 125 kHz Proximity Readers
INSTALLATION MANUAL

11cdvigroup.com
1 Measure and mark the center lines to determine the
reader position. Drill the xing screw holes (Diameter:
5mm). Drill the wiring access area (Diameter: 15mm).
2 Place the foam seal at the back of the reader. Take
care to begin from the bottom. (Sch. a). The foam seal
must be visible (about 2mm) on the top-back of the rea-
der (Sch. b).
Ref: STARPW-STARPB
1
3
2
g. a Sch. a Sch. b
Sch. c
Foam seal
3 Insert the plastic plugs in the mounting holes, connect the cable (refer to wiring diagram on page 11), then fasten
the reader with the TORX® screw using the TORX® bit (Sch. c). Make sure that the varistor is connected on the lock
(refer to page 8 “Reminders and recommendations”).
EN
SOLARPW-SOLARPB-STARPW-STARPB
Wiegand 125 kHz Proximity Readers
INSTALLATION MANUAL

12 cdvigroup.com
EN
SOLARPW-SOLARPB-STARPW-STARPB
Wiegand 125 kHz Proximity Readers
INSTALLATION MANUAL
When powered up
- Green LED illuminates for 1 sec.
- Red LED illuminates for 1 sec.
- Buzzer sounds for 1 second.
Operating mode
- Buzzer activated with 0V input.
- LEDs activate with 0V input.
1
R V B D1 D0 H - +
Terminal block (8 points)
+Input voltage 12 Vdc
-0 V
HClock
D0 Data 0
D1 Data 1
BBuzzer
VGreen LED
RRed LED
SOLARPW-SOLARPB
Cable
Red Input voltage 12 Vdc
Black 0 V
Blue Clock
Green Data 0
White Data 1
Brown Buzzer
Yellow Green LED
Orange Red LED
STARPW-STARPB
Input LED management
Green LED Red LED Status
OFF OFF Off
OFF ON red
ON OFF green
ON ON blue
1 2
OFF OFF
26 bits
1 2
ON OFF
30 bits
1 2
OFF ON
44 bits
1 2
ON ON
Not used
3
ON
Standard
Pulls up 12 V or 5 V
Open collector outputs:
OFF
ON
OFF
ON
OFF
ON
OFF
ON
ON
OFF
ON
4
3
2
1
ONON
ONON
4
3
2
1
ONON
ONON
4
3
2
1
ONON
ONON
4
3
2
1
ONON
ONON
4
3
2
1
ONON
ONON
4
3
2
1
ONON
ONON
OFF = 5 V
ON = 12 V
Card swiped (DIP3 = ON)
- Badge recognized: the orange
LED illuminates and the buzzer
activates for 150 milliseconds.
4
3
2
1
ONON
ONON
4
3
2
1
ONON
ONON
4
3
2
1
ONON
ONON
4
3
2
1
ONON
ONON
4
3
2
1
ONON
ONON
4
3
2
1
ONON
ONON
4
3
2
1
ONON
ONON
4
3
2
1
ONON
ONON
4
3
2
1
ONON
ONON
4
3
2
1
ONON
ONON
4
3
2
1
ONON
ONON
4
3
2
1
ONON
ONON
5] WIRING DIAGRAM
C56
C58
C61
1
MM10
4
3
2
1
ON
ON
ON
ON
L7
Q6
Q7
Q8
R77
R78
R79
P1
1P3
BZ3
C6
C24
C59
-
+
MM1
MM14
CR3
+
-
CR10
CR25
CR26
CR24
MM3
MM15
CR12
CR13
CR15
I1
+
-
+
-
MM16
CR22
P2
-
+
CR19
CR21
CR20
CR28
CR27
CR29
CR11
R70
R67
R68
R64
R69
R65
C68
CR30
4 1
ON
4
1
ON
Dipswitch 1 & 2
positioning
Dipswitch 3 positioning
Dipswitch 4 positioning

13cdvigroup.com
EN
SOLARPW-SOLARPB-STARPW-STARPB
Wiegand 125 kHz Proximity Readers
INSTALLATION MANUAL
6] OUTPUT FORMATS 26, 30 AND 44 BIT WIEGAND
Chronograms
Open collector output with internal pulls up 1K at +5V or +12V according to the ST4 position.
26-bit Wiegand Output
Format 26-bits hexadecimal. The output format is 26-bit Wiegand (Signals: DATA1, DATA0 and CLOCK). The
frame is made of 26-bit and built as follows:
1 - First parity: 1 bit – even parity for the rst 12-bit.
Code of the badge: 6 half byte represent the last 6 digit of the code (4bit = 1 digit of the code).
Each byte is transferred from bit 7 to bit 0.
2 - Second parity: 1 bit – odd parity for the last 12-bit.
Bit 1 Bit 2 to bit 25 Bit 26
Even parity on bit 2 to bit 13 Data (24 bits)
Odd parity on bit 14 to bit 25
Example: code of the badge is 0100166A37.
1 0001 0110 0110 1010 0011 0111 0
Parity 1 1 6 6 A 3 7 Parity 2
The code transmitted is in hexadecimal format 166A37.
Parity 1 : 0 if the number of 1 in bit 2 to bit 13 is even.
1 if the number of 1 in bit 2 to bit 13 is odd.
Parity 2 : 0 if the number of 1 in bit 14 to bit 25 is odd.
1 if the number of 1 in bit 14 to bit 25 is even.
0 logic
\DATA1
\CLOCK
\DATA0
50 μs 50 μs
2ms 2ms
1 logic

14 cdvigroup.com
EN
SOLARPW-SOLARPB-STARPW-STARPB
Wiegand 125 kHz Proximity Readers
INSTALLATION MANUAL
30-bit Wiegand Output
Format 30-bits hexadecimal. The output format is 30-bit Wiegand (Signals: DATA1, DATA0 and CLOCK). The
frame is made of 30-bit and built as follows:
1 - First parity: 1 bit – even parity for the rst 14-bit.
Code of the badge: A code is formed from 7 half byte.
Each byte is transferred from bit 7 to bit 0.
2 - Second parity: 1 bit – odd parity for the last 14-bit.
Bit 1 Bit 2 to bit 29 Bit 30
Even parity from bit 2 to bit 15 Data (28-bit) Odd parity from bit 16 to bit 29
Example A: Temic card decimal code 689905 (in hexadecimal: A86F1).
1 0000 0000 1010 0110 0110 1111 0001 0
Parity 1 0 0 A 8 6 F 1 Parity 2
The code number of the card in hexadecimal is 00A86F1.
Example B: EM badge hexadecimal code: 0100166A37.
1 0000 0000 0001 0001 0110 1011 0110 1
Parity 1 0 0 6 6 A 3 7 Parity 2
The code transmitted in hexadecimal format is 0166A37.
Parity 1 : 0 if the number of 1 in bit 2 to bit 15 is even.
1 if the number of 1 in bit 2 to bit 15 is odd.
Parité 2 : 0 si le nombre de 1 dans bit 16 à bit 29 est impair,
1 si le nombre de 1 dans bit 16 à bit 29 est pair.
44-bit Wiegand format
44-bit hexadecimal format. The output format from the proximity card reader is 44-bit (Signals: DATA1, DATA0
and CLOCK) and is structured as follows:
Data: 10 digit code number hexadecimal MSByte rst.
Each hexadecimal digit = 4 bit, MSBit rst.
LRC: 4 bit = OR restricted in between the digit of the data, MSBit rst.
Bit to à bit 40 Bit 41 to bit 44
Data MSBit rst LRC
Example A: EM badge hexadecimal code: 01001950C3.
0000 0000 0000 0000 0001 1001 0101 0000 1100 0011 0011
01001950C33
The code number of the card in hexadecimal is 01001950C3.

15cdvigroup.com
7] LED MANAGEMENT ON CENTAUR SYSTEM
GREEN LED
SETTINGS
RED LED
SETTINGS
GREEN ACCESS ALLOWED
RED ACCESS DENIED
BLUE STAND-BY
LED
ACTUATION
8] NOTES
EN
SOLARPW-SOLARPB-STARPW-STARPB
Wiegand 125 kHz Proximity Readers
INSTALLATION MANUAL

The installer’s choice
cdvigroup.com
Referencia:
Extranet:
All the information contained within this document (pictures, drawing, features, specications and dimensions)
could be perceptibly different and can be changed without prior notice.
Toda la información mostrada en este documento (dibujos, diagramas, especicaciones, características y dimensiones)
son a título informativo y pueden diferir del producto nal, del mismo modo que son susceptibles de sufrir modicaciones
sin noticación previa.
CDVI Group
FRANCE (Headquarter/Siège social)
Phone: +33 (0)1 48 91 01 02
Fax: +33 (0)1 48 91 21 21
CDVI
FRANCE + EXPORT
Phone: +33 (0)1 48 91 01 02
Fax: +33 (0)1 48 91 21 21
CDVI AMERICAS
[CANADA - USA]
Phone: +1 (450) 682 7945
Fax: +1 (450) 682 9590
CDVI
BENELUX
[BELGIUM - NETHERLAND - LUXEMBOURG]
Phone: +32 (0) 56 73 93 00
Fax: +32 (0) 56 73 93 05
CDVI
TAIWAN
Phone: +886 (0)42471 2188
Fax: +886 (0)42471 2131
CDVI
SUISSE
Phone: +41 (0)21 882 18 41
Fax: +41 (0)21 882 18 42
CDVI
CHINA
Phone: +86 (0)10 84606132/82
Fax: +86 (0)10 84606182
CDVI
IBÉRICA
[SPAIN - PORTUGAL]
Phone: +34 (0)935 390 966
Fax: +34 (0)935 390 970
CDVI
ITALIA
Phone: +39 0321 90 573
Fax: +39 0321 90 8018
CDVI
MAROC
Phone: +212 (0)5 22 48 09 40
Fax: +212 (0)5 22 48 34 69
CDVI
SWEDEN
[SWEDEN - DENMARK - NORWAY - FINLAND]
Phone: +46 (0)31 760 19 30
Fax: +46 (0)31 748 09 30
CDVI
UK
[UNITED KINGDOM - IRELAND]
Phone: +44 (0)1628 531300
Fax: +44 (0)1628 531003
Other manuals for SOLARPW
3
This manual suits for next models
3
Table of contents
Languages:
Other CDVI IP Access Controllers manuals

CDVI
CDVI KCPROXWLC User manual

CDVI
CDVI NANOPW User manual

CDVI
CDVI PROMI500 User manual

CDVI
CDVI GALEOR User manual

CDVI
CDVI PASS KCPASS User manual

CDVI
CDVI micro IEVO-M User manual

CDVI
CDVI Digicode Mifare PCV123D User manual

CDVI
CDVI SOLARPB Instruction Manual

CDVI
CDVI SOLARPW User manual

CDVI
CDVI TERENA User manual