CKD PARECT MEVT Series User manual

SM−295321−A
INSTRUCTION MANUAL
PARECT
Electro
-
pneumatic Regulator
MEVT Series
COMMON TERMINAL STAND
TYPE
MEVT
-
T11R
D-SUB CONNECTOR TYPE
MEVT
-
T30R
●
Please read this instruction manual
carefully before using this product, par-
ticularly the section describing safety
.
●
Retain this instruction manual with the
product for further consultation whenev-
er necessary
.
Ver.4

[SM-295321-A]
―
1
―
For Safety Use
To use this product safety, basic knowledge of pneumatic
equipment, including materials, piping, electrical system
and mechanism, is required (ISO 4414 *1 JIS B 8370 *2).
We do not bear any responsibility for accidents caused by
any person without such knowledge or arising from im-
proper operation.
Our customers use this product for a very wide range of
applications, and we cannot keep track of all of them. De-
pending on operating conditions, the product may fail to
operate to maximum performance, or cause an accident.
Thus, before placing an order, examine whether the product
meets your application, requirements, and how to use it.
This product incorporates many functions and mecha-
nisms to ensure safety. However, improper operation could
result in an accident. To prevent such accidents
read this
operationmanualcarefullyforproperoperation.
Observe the cautions on handling described in this manu-
al, as well as the following instructions:
Additionally, the caution is classified into the following
three groups, “CAUTION”, “WARNING”, and “DANGER”,
to identify the degree of the danger it presents and possible
hazard.
Failure to pay attention to DANGER no-
ticesmaycauseasituationthatresultsin
afatalityorseriousinjuryandthatrequires
urgentaddressing.
Failure to pay attention to WARNING no-
ticesmayresultinafatalityorseriousin-
jury.
Failure to pay attention to WARNING no-
tices may result in injury or damage to
equipmentorfacilities.
*1) ISO 4414 : Pneumatic fluid power
・・・
Recommendations for
the application of equipment to transmission and
control systems.
*2) JIS B 8370 : General rule for pneumatic systems
DANGER :
!
WARNING:
!
CAUTION:
!

[SM-295321-A]
−
2
−
CAUTION
Points to caution when handling the product
(1) Inferior quality air will deteriorate the product characteristics and affect its
durability badly. Use an air dryer, filter and Oil mist filter to eliminate solid
material, moisture and tar and thus provide clean air from the pressure
source.
When the control pressure decreases, for example, the air runs from the sec-
ondary side through the regulator to the exhaust port (R). Dust inside the
secondary side piping or the load circuit, therefore, will similarly deteriorate
the product’s characteristics and greatly affect its durability. Ensure the in-
terior of the piping is always clean.
(2) The products response capability will be affected by the working pressure
and load volume. When a stable response is required, regulate the
working pressure.
(3) Flush air into the pneumatic pipes employed in the PARECT
electro-pneumatic regulator before connection. Be careful not to allow
sealant tape to stray into the pipes.
(4) To avoid malfunction caused by electrical noise:
(a) Insert a line filter into the AC power line.
(b) Use a surge suppresser like a CR or diode in the inductive load (solenoid valve, relay and
so on) to remove any noise at the source.
(c) Keep the MEVT series cables as far away as possible from power line for motor.
(d) For wiring to the PARECT electro-pneumatic regulator, always use the shield wire. (T30R)
(e) In the case of the influence of noise, each slave station can possibly be supplied the power
and wire individually.
(
f
) Wire the power line as short as possible.
(
g
) Don’t share the power with devices that generate the noise, such as inverter motor.
(h) Don’t wire the power line or communication line in parallel with other lines.
(5)
Connect the shield wire to the grounding terminal on the power supply
side.
(6)
If the monitor output is not used, take appropriate measures so that the
monitor output terminals and lines are not in contact with other terminals
and lines. Failure to do so may cause the product to malfunction. If this
product is operated with any monitor output terminal or line short-circuited
with the grounding line, this may cause the circuit to break, resulting in
malfunction.
(
7
) Avoid unplanned dismantling of the product. We shall not warrant the
product operation in cases where it has been dismantled without
authorization.
Air filter
5
μ
m
Air dryer Oil mist filter
(Oil removing)
Pressure switch
Regulator

[SM-295321-A]
−
3
−
(
8
) Avoid operating the product in places where it may be affected by direct
sunlight, water or oil.
(
9
) If the product remains connected to its supply pressure for a long time
while leaving the power turned off, the output pressure may increase to the
level of the supply pressure. For safety, when there is a problem, use the
valve on either the inlet or outlet side. It is recommended to set up the
system for safe operation.
(
10
) If the power is turned off when the unit is up to control pressure, the pres-
sure will be maintained. In this case, if you need to be in an exhaust state,
lower the control pressure first and then turn off the power or use the ex-
haust valve. However, the maintained pressure is not guaranteed to last for
very long.
(
11
) Since the working pressure is supposed to provide the exact control pres-
sure, it is important for the working pressure not to drop below “Control
pressure + Maximum control pressure
×
0.1”.
In particular, if the primary pressure is supplied for a long period of time
with the secondary pressure specified in a range that exceeds 0MPa up to
12% F.S., this will shorten the life span of the product and thus the product
should not be used in this way.
(1
2
) The MEVT Series regulators may oscillate if a leak occurs to the secondary
side piping. When connecting pipes to the regulator, connect them firmly
to prevent leaks. Do not use the regulator for blowing or in any other ap-
plication where the secondary side can be affected by back pressure. If
used in such applications, the regulator will not be able to achieve the spec-
ified pressure. Moreover, a large oscillation noise will be heard and the
product’s durability will be greatly reduced.
(1
3
) In the wiring of the MEVT common terminal stand type and D-Sub con-
nector type, the power grounding line and the signal common line are used
commonly. Therefore, when the MEVT-series product is driven by one
PLC and D/A unit, the correct signals may not be output due to wiring de-
pending on the circuit method of the D/A unit. Before starting the opera-
tion, always contact the PLC manufacturer.
(1
4
) Don’t supply the input signal over maximum control pressure, because an
excessive input signal exerts a bad influence on the deterioration of the
characteristic and also the durability.
(1
5
) Keep the exhaust port (R) open to the air to allow the release of the exhaust
into the air.
(1
6
) When it is maintained the condition where the power is on and the working
pressure isn’t supplied or the condition where the power is on and the input
signal is missing from the control range, the deterioration of the character-
istic and also life occur. Therefore, the product should not be used in this
way.

Jun.19.2003
Aug.22.2017
−
4
−
INDEX
MEVT Series
PARECT Electro-pneumatic Regulator
COMMONTERMINAL STAND TYPE (MEVT-T11R)
D-SUB CONNECTOR TYPE (MEVT-T30R)
Manual No. SM-
295321
-A
1. DESIGN AND SELECTION 5
2. INSTALLATION 8
3. OPERATION12
4. MAINTENANCE 14
5. PRODUCTS
5.
1
Specifications 15
5.
2
Dimensions 16
5.3 Inside structure 17
5.4 Component18
5.5 Block constitution 19
6. WIRING 20
6.1 Common Terminal Stand Type (T11R)22
6.2 D-sub Connector Type (T30R) 23
7. HOW TO EXTEND EVT 27
8. PRODUCT CODE
8.1 How to order30
8.2 Component code31

[SM-295321-A]
―
5
―
1
DESIGNAND
SELECTION
1. DESIGNANDSELECTION
(1) With a thorough understanding of compressed air
characteristics,designapneumaticcircuit.
Where instantaneous stop holding at emergency stop is
required,thesamefunctionasinthemechanicalorhy-
draulicorelectricalunitscannotbeexpected.
There arise pop-up, jet-out and leaking phenomena
causedbycompressibilityandexpansibility,whichareair
characteristics.
(2) Prior to use, always ensure that the product with-
standstheoperatingenvironment.
The product cannot be used in corrosive gas, chemical
liquidsolvent,water,watervapor(steam)andozoneat-
mosphere. When a product is exposed to water drop-
lets, oil or metallic powder, such as spatters and chips,
besuretoprotectit.
Noproductcanbeusedintheexplosivegasatmosphere.
(3) Alwaysgivespecialcaretotheelectriccircuitduring
emergency stop, and cylinder operation, etc. during
powerfailure.
(4) Attach a
residual pressure discharge valve
to
thecompressedairinletoftheequipment.
Thepressureswitchcontrolsoperationsothatitcannot
becarriedoutwherethesetpressureisnotreached.
The residual pressure discharge valve discharges com-
pressed air remaining inside the pneumatic circuit, to
preventaccidentscausedbypneumaticequipmentoper-
ationduetoresidualpressure.
!
WARNING:

[SM-295321-A]
−
6
−
1
DESIGNAND
SELECTION
(1) Note the maintenance conditions clearly in the
equipmentinstructionmanual.
Theproductfunctionsmaysignificantlylower,depending
on the operating condition, operating environment and
maintenance situation, thereby safety might not be se-
cured. Ifthismaintenanceworkisconductedaccurately
andcorrectly,itispossibletoexhibittheproductfunc-
tionandperformancesufficiently.
(2) Usebeaconstantvoltagepowersupply.
(3) Check the leak current to avoid a malfunction
caused by such leakage from other control equip-
ment.
The EVT may malfunction under the influence of leak
current when a programmable controller or the like is
used.
(4) Toavoidmalfunctioncausedbyelectricalnoise:
InsertalinefilterintotheACpowerline.
UseasurgesuppresserlikeaCRordiodeintheinduc-
tiveload(solenoidvalve,relayandsoon)toremoveany
noiseatthesource.
Keep the MEVT series cables as far away as possible
frompowerlineformotor.
Inthecaseoftheinfluenceofnoise,eachslavestation
canpossiblybesuppliedthepowerandwireindividually.
Wirethepowerlineasshortaspossible.
Don
tsharethepowerwithdevices thatgeneratethe
noise,suchasinvertermotor.
Don
twirethepowerlineorcommunicationlineinpar-
allelwithotherlines.
(5)Cautionsforwiring
In the wiring of the common terminal stand type and
D-Subconnectortype,thepowergroundinglineandthe
signal common line are used commonly. Therefore,
when multiple EVT-series products are driven by one
PLCandD/Aunit,thecorrectsignalsmaynotbeoutput
duetowiringdependingonthecircuitmethodoftheD/A
unit. Before startingthe operation, always contact the
PLC manufacturer. Additionally, when using the shield
wire,connecttheshieldwiretothegroundingterminalon
thepowersupplyside.
(6) Do not use combined with a cylinder having a sub-
stantialleakageamountsuch as,acrawlingcylinder
oranairbearingcylinder.
Incaseof24VDC: 1.8mAorless
!
CAUTION:

[SM-295321-A]
―
7
―
1
DESIGNAND
SELECTION
Avoidusingaproduct inblowingorundertheoperating
conditionsthatthebackpressureisappliedtothesec-
ondaryside. Nosetpressurecanbemaintained,andits
service life may be shortened along with a large beat
sound.
(7) EVT100 arises residual pressure of 2kPa max and
EVT500, 10kPa max even when the input signal is
set to 0%. When 0MPa is required, take adequate
measures;forexample,attacha3-wayvalvetothe
secondarysideforchangeovertotheatmosphere.
(8)
Useavalveoninletandoutletasneeded
If the product is left as it is with the supply pressure
whennopoweristurnedON,thesecondarysidepressure
mayincreaseuptothesupplypressure.
Ifsometroubleisconcernedonsafety,takepropersafe-
ty measures in the system; for example, use a valve on
inletoroutlet.
(9) OperatingEnvironment
Avoid using a product in the place where it is ex-
poseddirecttosunlight,water,oilorthelike. Con-
tact us when using a product that falls outside the
designatedspecificationsandspecificationsforspe-
cialapplications.
AmbientTemperature
Contactuswhentheproductisusedatexceeding50℃
oralowtemperaturenotexceeding5℃.
Vibration&impact
Avoid using the product at the vibration of 50 m/s
2
min.
andimpactof300m/s
2
min.
!
CAUTION:

[SM-295321-A]
−
8
−
2
INSTALL
A
TION
2. INSTALLATION
(1) For MEVT installation, do not use the method of
supportingtheMEVTwithpiping.
AttachandfixtheMEVTmainbody.
(2) Do not wash and coat the MEVT, using water and
solvent
.
Someplasticspartsmaybedamaged.
The coating agent may block the exhaust port, causing
malfunctions.
(3) Check the piping port position by the product label
ornameplate,etc.forcorrectconnections.
Wrong piping connection causes abnormal operation of
theactuator.
!
WARNING:

[SM-295321-A]
―
9
―
2
INSTALL
A
TION
Wheninstalling:
(1) Keepasufficientspaceforremoval&re-installation,
wiringandpipingworkaroundtheEVT.
(2) Provide a pneumatic filter just in the pre-stage of
thecircuitinwhichthepneumaticequipmentisused.
(3) Theresponsetimeisaf-
fected by operating
pressure and load ca-
pacity.
When stable reproduci-
bility is required for this
responsibility, set up a
regulator in the
pre-stage.
(4) Attachingposition
SincetheMEVTisdesignedforDINrailmounting,fixthe
DIN rail to the attaching surface at intervals of 50 to
100mmwherethetotalmanifoldmassexceeds1kgorin
the environment under vibration and impact, and then
ensurethatnoabnormalityisidentifiedintheinstallation
conditionbeforeuse.
Thereisnorestrictionintheattachingdirectionandat-
tachingposture.Checkthemountingscrewdoesn
tget
loosebyresonanceduringoperation,toavoidthemani-
foldtofalloff.
Removal&re-installationofMEVT
ToRemoveMEVT:
LoosentheDINrailfixingscrews.(4pcs.in2right&left
places)
ToRe-installMEVT:
1. Set the jaw over the DIN rail from ① to ② as
shownbelow.
2. Presstheretainerinthedirectionto ③ below.
3. While pressing it so that no clearance is produced
between the blocks, tighten the DIN rail fixing
screws. (Recommendabletighteningtorque: 0.6to
0.8N・m.)
When the retainer
jaw is not hooked
firmly, air leakage
and product fall-
ing-off may result:
always check this
mounting condition
carefully.
Airfilter
(5μmorless)
EVT
①
②
③
Push
Retainer
DINrailfixingscrew
!
CAUTION:

[SM-295321-A]
−
10
−
2
INSTALL
A
TION
Whenpipingwork
(1) Do not detach the MEVT packing bag until piping
workisstarted.
Ifthepackingbagisremovedbeforepipingwork,foreign
substance may intrude into the interior EVT from the
pipingport,thuscausingtroubleandmalfunctions,etc.
(2) Inpipingwork,flushingisrequiredjust
before connecting to the pneumatic
equipment.
Foreign substance intruding inside during
pipingworkmustnotincorporateintothe
EVT.
(3) Makepipingarrangementssothatthecouplingsec-
tion in the piping connection part is not detached
due to equipment motion, vibration and tension or
thelike.
(4) Release the exhaust port (R) to air for satisfactory
exhaust.
(5) DonotreducetheEVTexhaustport(R)tolessthan
theborediameterofthepipingconnectingport.
TheEVTexhaustport(R)willbreatheduetovalving
elementmotion;therefore,foreignsubstancenearor
around the exhaust port (R) may be sucked, and
where the exhaust port (R) faces upward, foreign
substancemayintrudethereinto.
Attachasilencerormakepipingconnectionwiththe
exhaustport(R)lookingdown.
Ifnosmoothexhaustisinsured,theactuatorwillnotbe
actuated normally. When a manifold is used, exhaust
mayinterferewithnormaloperationofotherEVT
s.
(6) When piping connection has been completed and
compressedairissupplied,takecaresothatnohigh
pressureisappliedsuddenly.
The piping is disconnected and the piping tube springs
out,causingaccidents.
<CAUTION>: If compressed air is supplied too slowly,
there may arise air leak phenomena since no sealing
pressure is generated in some EVT internal sealing
mechanism.
(7) Whenthepipingconnectionhasbeencompletedand
compressedairissupplied,besuretocheckthatno
airisleakingfromallpipingconnectionsections.
Applyleakagedetectingsolutiontothepipingconnection
partwithabrushtocheckforairleaking.
(8) Whereanylontubeorpolyurethanetubeisusedfor
pipingmaterial,exercisethefollowingcare:
Always use a flame retardant tube in the atmosphere
suchthatspattersscatterabout.
(9) Donotthrottletheinputport.
Supply pressure lowers during equipment operation, re-
sultinginmalfunctions.
Eliminateforeign
substance
!
CAUTION:

[SM-295321-A]
―
11
―
2
INSTALL
A
TION
(10)PipingConnection
ApplicableTube:
UseourCKDdesignatedtube.
Softnylon(F-1500Series)
Polyurethane(U-9500Series)
Whenacommerciallyavailabletubeisused,givecareto
outsidediameteraccuracy,wallthicknessandhar
dness.
Thehardnessofthepolyurethanetubeusedshouldbe93
deg.min. (Rubberhardnesstester)
Ifatubethatdoesnotsatisfyoutsidediameteraccuracy
and hardness as specified is used, the chucking force
may lower, thereby causing the tube to come off and
makingithardtoinsertthetube.
TubeSize
OutsideDiameterTolerance
TubeBendingRadius
The tube bending radius should exceed the minimum
bending radius. (Otherwise, tube detachment and air
leakagemayresult.)
MinimumTubeLength
The standard length of output port (A) side tube used
shouldcorrespondtothetubeinternalvolumeof1m or
more. (Otherwise,oscillationmayresult.)
TubeCutting
Usingthetubecutter(AZ-1200),cutatubeverticallyin
the axial direction. Insertion of the tube cut aslant
causesairleakage.
TubeConnectionState
Providethelinearpartaslongastheoutsidediameterof
thetube used from the joint edge part to avoid sharply
bendingpipingatthejointinsertionport. Takecareso
that the tube tensile force in the lateral direction does
notexceed40N.
ApplicableBlankPlug
AlwaysusetheblankplugdesignatedbyCKD.
BlankplugGWP□-BSeries
Outside
diameter(mm)
Insidediameter(mm)
Nylon Urethane
φ4 φ2.5 φ2
φ6 φ4 φ4
Soft&hardnylon φ4, φ6 ±0.1mm
Urethaneφ4, φ6 +0.1mm
-0.15mm
Tubebore Minimumbendingradius(mm)
Nylon Urethane
φ4 10 10
φ6 20 20
Tubebore MinimumLength(mm)
Nylon Urethane
φ4 200 320
φ6 80 80
!
CAUTION:

[SM-295321-A]
−
12
−
OPERATION
3
3. OPERATION
Operating Conditions:
The pressure supplied to the electro-pneumatic regulator should be used in
the pressure range from the minimum operating pressure to maximum oper-
ating pressure that is specified in “5.1 Specifications”.
For supply power, use a stabilized power supply with the ripple rate 1% max.
at supply voltage 24 V DC+/-10%.
The input signal used and other working conditions should be based on “5.1
Specifications”.
Zero (Point) & Span Adjustment:
This product is factory adjusted for the specified control pressure output in
relation to each input signal before shipment.
As a rule, no zero & span adjustment change is allowed.
If zero & span adjustments are required at customer’s end, contact our near-
est sales office or agent.
However, it should be understood that the zero and span adjusted product is
out of warranty.
AirQuality:
(1) Supplyonly
compressedair
.
(2) For compressed air, always use clean air that does
notcontaincorrosivegas.
(3) Besuretouseoil-freefiltrateddryair
ISOGrade
1.3.2
.
AirQuality:
(1) Badqualityairmakesitscharacteristicsanddurabil-
ityworse.
Forthepneumaticsource,usecleanedairfromwhichthe
solids,waterandoilcontentswereeliminatedsufficiently,
usinganairdryer,filterandoilmistfilter
Also, where control pressure is reduced, for example,
secondaryairisdischargedfromtheexhaustport(R)via
the EVT interior. If the secondary piping and load side
interior arestained, the equipment will be adversely af-
fected;forexample,thecharacteristicsaredowngraded;
itis,therefore,necessarytomakeeffortsformakingthe
interiorpipingcleaner.
!
CAUTION:
!
WARNING:
Air filter
5
μ
m
Air dryer Oil mist filter
(Oil removing)
Pressure switch
Regulator

[SM-295321-A]
―
13
―
OPERATION
3
The pneumatic equipment should be disassembled and
re-assembledbytheworkerwhogottechnicalknowledge
thereon: this work requires the level of pneumaticskill
qualificationclass2orhigher.
When the pneumatic equipment is disassembled and re-
assembled, read the instruction manual for the corre-
sponding product carefully and have a thorough under-
standingofthecontents,thenstartthisoperationswork.
Miscellaneous:
(1) Avoiddisassembly;otherwise,accidentsmayresult.
Itshouldbeunderstoodthattheoperationafterdis-
assemblyfallsoutsidethewarrantyrange.
(2) Ifthepoweristurnedoffwhentheunitisuptocon-
trolpressure,thepressurewillbemaintained.Inthis
case,ifyouneedtobeinanexhauststate,lowerthe
controlpressurefirstandthenturnoffthepoweror
use the exhaust valve. However, the maintained
pressureisnotguaranteedtolastforverylong.
(3) Since the working pressure is supposed to provide
the exact control pressure, it is important for the
workingpressurenottodropbelow
Controlpres-
sure+Maximumcontrolpressure×0.1
.
Inparticular,iftheprimarypressureissuppliedfora
long period of time with the secondary pressure
specified in a range that exceeds 0MPa up to 12%
F.S.,thiswillshortenthelifespanoftheproductand
thustheproductshouldnotbeusedinthisway.
(4) The MEVT Series regulators may oscillate if a leak
occurs to the secondary side piping. When con-
necting pipes to the regulator, connect them firmly
to prevent leaks. Do not use the regulator for
blowing or in any other application where the sec-
ondary side can be affected by back pressure. If
used in such applications, the regulator will not be
abletoachievethespecifiedpressure. Moreover,a
large oscillation noise will be heard and the prod-
uct
sdurabilitywillbegreatlyreduced.
!
CAUTION:

[SM-295321-A]
−
14
−
4
MAINT
E
NANCE
4. MAINTENANCE
(1) Priortomaintenancework,besuretoturnthepow-
er OFF and stop supply compressed air to ensure
thatnoresidualpressureispresent.
Theseoperationsaretheconditionsrequiredforsecuring
operationalsafety.
(1) Carry out routine and periodic checking as planned
sothatmaintenancecontrolisimplementedcorrect-
ly.
Unless this maintenance control is satisfactory, the
productfunctionsremarkablylower,leadingtoequipment
malfunction and accidents, such as short service life,
damageandmalfunctioning.
1. Pressurecontroltosupplycompressedair
Checktoseeifthesetpressureissupplied.
Checktoseeifthepressuregaugeduringequipmentop-
erationispointingtothesetpressure.
2. Pneumaticfiltercontrol
Checktoseeifthebowlandelementfoulingconditionis
normal.
3. Control for compressed air leak in the piping con-
nectionpart
Checktosee iftheconditionoftheconnectionsection
especiallyinthemovablepartisnormal.
4. EVToperatingconditioncontrol
Check for operation delay and check to see if the ex-
hauststatusisnormal.
5. Controlforpneumaticactuatoroperatingcondition
Check to see if the pneumatic actuator is working
smoothly.
Checktoseeifthestoppedconditionatthestrokeend
isnormal.
Checktoseeifthesectioncoupledwiththeloadisnor-
mal.
(MAX)
(MIN)
!
CAUTION:
!
WARNING:

[SM-295321-A]
―
15
―
PRODUCT
5
5. PRODUCTS
5.1 PARECT Electro-pneumatic Regulator Specifications (Individual)
※
1
Model
Item EVT100 EVT500
Media Cleaned air (equivalent to ISO 1
.
3
.
2)
Max. working pressure 200kPa 0.7MPa
Min. working pressure Control pressure
+
Max. control pressure
×
0.1
Proof pressure Inlet side 300kPa 1.05 MPa
Outlet side 150kPa 0.75MPa
Pressure control range 0 to 100kPa 0 to 0.5MPa
Power supply voltage DC24V
±
10% (Stabilized power supply with a ripple rate of 1% or less)
Consumption current 0.1A or lower
Input signal (Input impedence) 0 to 10VDC (6.6k
Ω
), 0 to 5VDC (3.3k
Ω
), 4 to 20mA
Monitor output 1 to 5VDC (Load impedance 1 k
Ω
or more)
Insulation resistance 100M
Ω
(DC500V megger) or more
Withstand voltage AC 1500V 1 minute
Hysteresis
※
2
0.4% F.S. or less
Linearity
※
2
±
0.5% F.S. or less
Resolution
※
2
0.1% F.S. or less
Repeatability
※
2
0.3% F.S. or less
Temperature
characteristic
Zero point fluctuation 0.15% F.S. / or less
Span fluctuation 0.07% F.S. / or less
Max. flow rate (ANR)
※
3
2L / min 6L / min
Step response
※
4
No load 0.1s or less
15cm
3
load 0.5s or less
Ambient temperature 5 to 50
℃
Fluid temperature 5 to 50
℃
Lubrication Nil
Indicator
※
5
Green/Red LED
Installation position Free
Working environment No corrosive gas
Dimensions W14
×
D75
×
H75
Mass (body) 80g
※
1 : The above specifications are valid when the product is powered by 24
±
0.15VDC at normal temperature.
※
2 : These specifications are valid at a working pressure which is “1.1 times the maximum control pressure”
(EVT100 : 110kPa, EVT500 : 0.55MPa) and control pressure is from 10 to 100%. It is also assumed that the sec-
ondary side circuit constitutes a closed circuit. If the product is used for such purposes as blowing, for example, a
pressure fluctuation may occur.
※
3 : Working pressure : Maximum operating pressure, Control pressure : Maximum control pressure
※
4 : Working pressure : Maximum working pressure, Step rate : 50% F.S.
→
100% F.S.
50% F.S.
→
60% F.S.
50% F.S.
→
40% F.S.
※
5 : Indicator is for a rough standard. Accuracy is not guaranteed.
PARECT Electro-pneumatic Regulator (Manifold specifications)
Item Specifications
Manifold type Block manifold
Installation type DIN rail mount type
Air supply and exhaust Concentrated supply and exhaust
Max. manifold number 8
Port size Output port (A)
φ
4
、φ
6 Push-in joint
Input port (P) Exhaust port (R)
φ
4
、φ
6 Push-in joint

[SM-295321-A]
−
16
−
PRODUC
T
5
5.2 Dimensions
1) Common terminal stand type (T11R)
2) D-sub connector type (T30R)
End block L
L2
=
L1 + (40 to )
L3
=
L2 – 12.5
L1
=
(14
×
n) + 42 + 10 +23
n : EVT number
14 14
35
75
6
.5
EVT
Retainer
L
φ
4,
φ
6 Push-in joint (Select)
Input port (P)
Electric equipment, supply
(D-sub connector type)
Retainer R
φ
4,
φ
6 Push-in joint (Select)
Output port (A)
φ
4,
φ
6 Push-in joint (Select)
Exhaust port (R)
1
2
3
2.8
77.3
2
.3 131
10
11.5
5
.5
37
20
11.5
42
L2
=
L1 + (40 to )
L3
=
L2 – 12.5
L1
=
(14
×
n) + 42 + 10 + 23
n : EVT number
14 14
3
5
75
6
.5
End block L EVT
Retainer L
φ
4,
φ
6 Push-in joint (Select)
Input port (P)
Electric equipment, supply
(Common terminal stand type)
Retainer R
φ
4,
φ
6 Push-in joint (Select)
Output port (A)
φ
4,
φ
6 Push-in joint (Select)
Exhaust port (R)
1
2
3
2.8
77.3
2
.3 131
10
11.5
5
.5
37
20
11.5
42

[SM-295321-A]
―
17
―
PRODUCT
5
5.3 Inside structure
EVT
Main component list
No. Name of parts Material No. Name of parts Material
1 Valve for supply
−
7 Connecting hook plate Polyamid
2 Wiring cover
Acryloni-
trile-butadiene-styr
ene
8 Valve for exhaust
−
3 Valve cover
Acryloni-
trile-butadiene-styr
ene
9 Controller
−
4 Indicator lens Polycarbonate 10 Pressure sensor
−
5 Body Polyamid 11 Case
Acryloni-
trile-butadiene-styr
ene
6 Push-in joint
−
⑪
⑩
⑨
④
⑤
⑥
⑦
⑧
①
②③
R
P
A

[SM-295321-A]
−
18
−
PRODUC
T
5
5.4 Component
Common Terminal Stand Type
D-sub Connector Type
Main component list
No. Name of parts Model no. Remarks
1 Retainer L EVT-HL
−
2 End block L EVT-EL
−
3 EVT EVT
※
00 For a single EVT, two pipe joints are included.
4 Electric equipment,
supply and exhaust block EVT-T
※
5 Retainer R EVT-HR
Mass
(g)
Name of parts Mass
EVT EVT
※
00 80
End block L EVT-EL 30
Retainer EVT-H
※
25
Electric equipment,
supply and exhaust block
EVT-T11R 115
EVT-T30R 125
①
②
③
④
⑤
①
②
③
④
⑤

[SM-295321-A]
―
19
―
PRODUCT
5
5.5 Block constitution
EVT:
①
The EVT can be installed on the DIN rails by the required number of stations. However,
the number of stations is determined, depending on the kind of the slave station.
(Refer to “PARECT Electropneumatic Regulator (Manifold) Specifications” given in Section
5.1 )
②
The EVT is called “1st, 2nd, 3rd
…
” from the right side with the joint in front.
③
REG. No. marked on the EVT wiring cover is assigned as 1, 2, 3
…
from the nearer side for
each connected electric equipment, supply and exhaust block.
Electric equipment, supply and exhaust block:
①
The EVT can be installed in the connecting part of each block freely as required.
End block:
①
Install the end block on the side opposite to the electric equipment and supply/exhaust block.
Piping
block
(A) EVT
●
4 Pin connector
(B) End block
●
Left side
Electric
equipment,
supply and
exhaust
block
(C) Common Terminal
Stand Type
(D) D-sub Connector
Type
Peripheral
equipment
●
DIN rail
●
Silencer
●
Blank plug
(D) Peripheral equip-
ment
Plumbing
section
MEVT
constitution
Peripheral
equipment
Wiring
section
This manual suits for next models
4
Table of contents
Other CKD Controllers manuals

CKD
CKD EVD-1000 Series User manual

CKD
CKD AX1R Series User manual

CKD
CKD KBX Series User manual

CKD
CKD KBX-T3 User manual

CKD
CKD LN Series User manual

CKD
CKD AX Series User manual

CKD
CKD ECG Series User manual

CKD
CKD ABSODEX MINI AX6000M Series User manual

CKD
CKD ECG Series User manual

CKD
CKD AXD Series User manual
Popular Controllers manuals by other brands

RESEARCH CONCEPTS
RESEARCH CONCEPTS RC4000 user manual

Emerson
Emerson Fisher easy-Drive 200R instruction manual

Musica
Musica MUSICAVC-70ZS installation instructions

Telecom Behnke
Telecom Behnke BEHNKE-STATION Technical manual

YASKAWA
YASKAWA Motoman DX200 instructions

Velleman
Velleman HQ-Power VDPDMXC146 manual