Cosel KHEA30F User manual

1 Functions KH-22
1.1 Input Voltage Range
1.2 Inrush Current Limiting
1.3 Overcurrent Protection
1.4 Peakcurrent Protection
1.5 Overvoltage Protection
1.6 Thermal Protection
1.7 Output Ripple and Ripple Noise
1.8 Remote ON/OFF
1.9 Output Voltage Adjustment Range
1.10 Isolation
1.11 Signal Output
1.12 Derating for low temperature start-up
2 Peak Current KH-24
3 Series/Parallel Operation KH-24
4Temperature Measurement Point KH-25
5Life Expectancy and Warranty KH-26
6 Applicable Electric Cable KH-29
KH-22
KH-22
KH-22
KH-22
KH-22
KH-23
KH-23
KH-23
KH-23
KH-23
KH-23
KH-24
3.1 Series Operation
3.2 Parallel Operation
KH-24
KH-24
AC-DC Power Supplies DIN Rail Type
Instruction Manual
7 Option KH-29
7.1 Outline of option
7.2 Others
KH-29
KH-29
KH-21
June 29, 2020

1.1 Input Voltage Range
¡Input voltage range of the power supplies is from AC85V to
AC264V or DC (please see SPECIFICATIONS for details).
¡If input value doesn’t fall within above range, a unit may not oper-
ate in accordance with specications and/or start hunting or oper-
ate protection circuit or fail.
If you need to apply a square waveform input voltage, which is
commonly used in UPS and inverters, please contact us.
¡When the input voltage changes suddenly, the output voltage
accuracy might exceed the specication. Please contact us.
¡To comply with safety standards,input voltage range is shown in
Table 1.1.
Table 1.1 Input voltage range of safety standards
No. Series Input Voltage range
AC input DC input
1 KHEA30F, KHNA30F
100V-240V
(50/60Hz)
88V-250V2 KHEA60F, KHNA60F
3 KHEA90F, KHNA90F
4 KHEA120F, KHNA120F
88V-350V5 KHEA240F, KHNA240F
6 KHEA480F, KHNA480F
¿ KHEA30F/60F/90F, KHNA30F/60F/90F
¡Operation stop voltage is set at a lower value than of a standard
version (derating is needed).
-Use Conditions
Output
KHEA30F,KHNA30F 10W
KHEA60F,KHNA60F 20W
KHEA90F,KHNA90F 30W
Input AC50V or DC70V
Duty 1s/30s
*Please avoid using continuously for more than 1 second under
above conditions. Doing so may cause a failure.
1.2 Inrush Current Limiting
¡An inrush current limiting circuit is built-in.
¡If you need to use a switch on the input side, please select one
that can withstand an input inrush current.
¿ KHEA30F/60F/90F/120F,
KHNA30F/60F/90F/120F
¡Thermistor is used in the inrush current limiting circuit. When you
turn the power ON/OFF repeatedly within a short period of time,
please have enough intervals so that a power supply cools down
before being turned on.
¿
KHEA240F/480F, KHNA240F/480F
¡Thyristor technique (KHEA/KHNA240F) and power relay tech-
nique (KHEA/KHNA480F) is used in the inrush current limiting
circuit.
1 Functions ¡When you turn the power ON/OFF repeatedly within a short period
of time, please have enough intervals so that the inrush current
limiting circuit becomes operative.
¡When the switch of the input is turned on, the primary inrush cur-
rent and secondary inrush current will be generated.
1.3 Overcurrent Protection
¿ KHEA30F/60F/90F, KHNA30F/60F/90F
¡A overcurrent protection circuit is built-in and activated over 105%
of the rated current. A unit automatically recovers when a fault
condition is removed. Please do not use a unit in short circuit and/
or under an overcurrent condition.
¡Hiccup Operation Mode (except KHEA/KHNA90F)
When the overcurrent protection circuit is activated and the output
voltage drops to a certain extent, the output becomes hiccup so
that the average current will also decrease.
¡Output Voltage Shutdown
If the output voltage drops according to the overcurrent protection
circuit operating continuously for about 0.5 second, the output
voltage may shut down. To recover the output voltage, remove a
condition that is causing an overcurrent, shut down the input volt-
age, wait more than 3 minutes and turn on the AC input again.
¿
KHEA120F/240F/480F, KHNA120F/240F/480F
¡An overcurrent protection circuit is built-in and activated over
101% of the peak current. A unit automatically recovers when a
fault condition is removed. Please do not use a unit in short cir-
cuit and/or under an overcurrent condition.
¡Hiccup Operation Mode
When the overcurrent protection circuit is activated and the out-
putvoltage drops to a certain extent, the output becomes hiccup
so that the average current will also decrease.
1.4 Peakcurrent Protection
¿
KHEA120F/240F/480F, KHNA120F/240F/480F
¡Peakcurrent protection is built-in (refer to Instruction Manual 3 for
Peak loading).
If this function comes into effect, the output is shut down.
A few seconds later, A unit automatically recovers.
But if the overcurrent condition has not been released, the output
will stop again (hiccup Operation Mode).
*The recovery time varies depending on input voltage and load
condition.
1.5 Overvoltage Protection
¿ KHEA30F/60F/90F, KHNA30F/60F/90F
¡An overvoltage protection circuit is built-in. If the overvoltage pro-
tection circuit is activated, shut down the input voltage, wait more
than 3 minutes and turn on the AC input again to recover the out-
put voltage. Recovery time varies depending on such factors as
input voltage value at the time of the operation.
¿
KHEA120F/240F/480F, KHNA120F/240F/480F
¡An overvoltage protection circuit is built-in.
AC-DC Power Supplies DIN Rail Type Instruction Manual
KH-22 June 29, 2020

A unit automatically recovers when the fault condition is removed.
Note :
Please avoid applying a voltage exceeding the rated voltage to an
output terminal. Doing so may cause a power supply to malfunc-
tion or fail. If you cannot avoid doing so, for example, if you need
to operate a motor, etc., please install an external diode on the
output terminal to protect the unit.
1.6 Thermal Protection
¿
KHEA120F/240F/480F, KHNA120F/240F/480F
¡A thermal protection circuit is built-in.
The thermal protection circuit may be activated under the follow-
ing conditions and shut down the output.
1
When a temperature continue to exceed the values determined
by the derating curve.
2
When a current exceeding the rated current is applied.
3When convection stops.
4When peak load is applied in conditions other than those shown
in Section 3.
A unit automatically recovers when the fault condition is removed.
1.7 Output Ripple and Ripple Noise
¡Output ripple noise may be inuenced by measurement environ-
ment, measuring method g 1.1 is recommended.
+Vout
-Vout
150mm
C
2
C
1
+Load
Osiloscope/
Ripple noise meter
Bw:20MHz Differential probe
C
1
:Film capacitor 0.1mF
C
2
:Aluminum electrolytic capacitor 22 mF
Fig.1.1 Measuring method of Ripple and Ripple Noise
1.8 Remote ON/OFF
¿
KHEA120F/240F/480F, KHNA120F/240F/480F
¡You can reduce the standby power by Remote ON/OFF.
To do so, connect an external DC power supply and apply a volt-
age to a remote ON/OFF connector.
Table 1.2 Remote ON/OFF Specications
ON/OFF logic Between +RC and -RC Output voltage
Negative L level (0 to 0.5V) or open ON
H level (4.5 to 29.5V) OFF
Ri=2040W
Input current
(20mA max)
-
RC
+RC
*1
RSW
External Power
Souce
Inside of a Power
Supply
Fig.1.2 Example of use with remote ON/OFF
*1 If the output of an external power supply is within the range of
4.5 - 29.5V, you do not need a current limiting resistor R. If the
output exceeds 29.5V, however, please connect the current limit-
ing resistor R.
To calculate a current limiting resistance value, please use the fol-
lowing equation.
Vcc-(1.1+RiX0.005)
0.005
R [W]=
¡Please wire carefully. If you wire wrongly, the internal components
of a unit may be damaged.
¡Remote ON/OFF circuits (+RC and -RC) are isolated from input,
output and PE.
¡Restart time is 750 ms max .
1.9 Output Voltage Adjustment Range
¡To increase an output voltage, turn a built-in potentiometer clock-
wise. To decrease the output voltage, turn it counterclockwise.
1.10 Isolation
¡When you run a Hi-Pot test as receiving inspection, gradually
increase the voltage to start. When you shut down, decrease the
voltage gradually by using a dial. Please avoid a Hi-Pot tester with
a timer because, when the timer is turned ON or OFF, it may gen-
erate a voltage a few times higher than the applied voltage.
¡When you test a unit for isolation between the output and the
DC_OK, short all terminals of DC_OK.
1.11 Signal Output
Functions of LED indicators and signal output (KHEA series)
¿
KHEA120F/240F/480F, KHNA120F/240F/480F
¡Functions of LED indicators and signal output in the form of relay
contact are shown below. Checking the presence/absence of volt-
age at the output terminal of a power supply is possible.
Table 1.3 Description of the signal output
Signal Output Normal Output is decreasing
DC_OK (LED: Green) ON OFF
ALARM (LED: Red) OFF ON
DC_OK (Relay Contact) *Short Open
*DC_OK signal (relay contact) is built in KHEA series. This circuit
is insulated from other circuits (input and output circuits).
Caution on signal outputs :
¡The timing of signals might be very depending on models, input
and load conditions. Please make sure enough evaluation.
AC-DC Power Supplies DIN Rail Type Instruction Manual
KH-23
June 29, 2020

1.12 Derating for low temperature start-up
¡Derating shown in Table 5.5 is required for low temperature start-
up.
Table 1.4 Derating for low temperature start-up
No. Model temperature range Load factor
1 KHEA30F, KHNA30F
-40Cto -20C50%2 KHEA60F, KHNA60F
3 KHEA90F, KHNA90F
4 KHEA120F, KHNA120F
-40Cto -25C75%5 KHEA240F, KHNA240F
6 KHEA480F, KHNA480F
2 Peak Current
¿
KHEA120F/240F/480F, KHNA120F/240F/480F
¡The units can generate the peak current under the following con-
ditions.
-t1[5sec
-Ip[Rated peak current
-Iave[Rated current
*Please use a maximum of Duty following shown in Table 2.1.
-Duty= t1 X100 [%]
t1+t2
[A]
Output current
Ip : Peak current
Iave : Average current
I : Load current
t1 t2
Fig.2.1 Peak current
Table 2.1 Maximum Duty by the mounting orientation
Mounting
orientation
Input
Voltage
Maximum Duty
KHEA120F
KHNA120F
KHEA240F
KHNA240F
KHEA480F-24
KHNA480F-24
KHEA480F-48
KHNA480F-48
A
AC85 - 170V
35% 35%
20% 20%
AC170 - 264V
15%
B
AC85 -
264
V
20%
C
AC85 -
264
V
5%
D
AC85 -
264
V
20%
E
AC85 -
264
V
3 Series/Parallel
Operation
3.1 Series Operation
¡You can use a power supply in series operation. The output cur-
rent in series operation should be lower than the rated current of a
power supply with the lowest rated current among the power sup-
plies that are serially connected. Please make sure that no current
exceeding the rated current ows into a power supply.
Load
(a)(b)
Load Load
Power
Supply
+
-
Power
Supply
+
-
Power
Supply
+
-
+
-
Power
Supply
Fig.3.1 Examples of connecting in series operation
3.2 Parallel Operation
¡There is no current balance function.
When operating in parallel, such as diode-OR, please use on the
output voltage was adjusted enough to balance the current.
Exceeds the rated output current, the output is shut down.
¡Redundancy operation is available by wiring as shown below.
I2
I1I3
-
+
+
-
Load
Power
Supply
Power
Supply
Fig.3.2 Example of connecting in redundancy operation
Even a slight difference in output voltage can affect the balance
between the values of I1and I2.
Please make sure that the value of l3 does not exceed the rated
current of a power supply.
l3[rated current value
AC-DC Power Supplies DIN Rail Type Instruction Manual
KH-24 June 29, 2020

4 Temperature
Measurement Point
¡Ambient temperature indicates the temperature of the inlet of the
air.
Ambient temperature
measurement point
Airflow
Fig.4.1 Ambient temperature measurement point
¡Temperature of Forced air
Use the temperature measurement point as shown in Fig.4.2 to
4.3. Please use at the temperature dose not exceed the values in
Table 4.1. Please also make sure that the ambient temperature
does not exceed 70C.
¿ KHEA30F, KHNA30F
POINT C
(T201)
POINT A
(C106)
POINT B
TB2
TB1
(C515)
Fig.4.2 Temperature measurement point (Forced air)
¿ KHEA60F, KHNA60F
POINT C
(T201)
POINT A
(C107)
POINT B
TB2
TB1
(C516)
Fig.4.3 Temperature measurement point (Forced air)
¿ KHEA90F, KHNA90F
POINT A
(C106)
POINT B
TB2
TB1
(C515)
*
*
*
Please be careful of electric shock or earth leakage in case of temperature measurement,
because POINT A and POINT B is live potential.
Fig.4.4 Temperature measurement point (Forced air)
Table 4.1 Specied temperature of the measurement point
No. Model Temperature measurement point
Point A Point B Point C
1 KHEA30F, KHNA30F 80C80C105C
2 KHEA60F, KHNA60F 80C80C105C
3 KHEA90F, KHNA90F 80C80C
OUTPUT CASE
CHASSIS
4- JOINT PART
INPUT
Fig.4.5 Installation removing chassis and case
Thermocouple for temperature checking must be added into tem-
perature measuring point after removing chassis and case.
Then assembling chassis and case again, the temperature can be
measured.
Chassis and case are xed in 4 parts which are shown in the gure.
Please contact us about detail.
¡Temperature of Forced air
Use the temperature measurement point as shown in Fig 4.6.
Please use at the temperature does not exceed the values in
Table 4.2.
Please also make sure that the ambient temperature does not ex-
ceed 70C.
AC-DC Power Supplies DIN Rail Type Instruction Manual
KH-25
June 29, 2020

Temperature
measureing point
Airflow
Airflow
Fig.4.6 Temperature measurement point (Forced air)
Table 4.2 Specied temperature of the measurement point
No. Model temperature measurement point
1 KHEA120F, KHNA120F 75C
2 KHEA240F, KHNA240F 80C
3 KHEA480F, KHNA480F 85C
5 Life Expectancy and
warranty
Please note derating curve depend on input voltage is required.
¡Life Expectancy
Table 5.1 Life Expectancy (KHEA30F, KHNA30F)
Mounting
method
Cooling
method
Input
voltage
Average ambient
temperature (year)
Life Expectancy
Load factor
Io[75%
Load factor
75%<Io[100%
A
Convection
AC85 - 170V
Ta = 50Cor less
10years or more 7years
Ta = 60C
6years 3years
AC170 - 264V
Ta = 50Cor less
10years or more 9years
Ta = 60C
6years 4years
B
Convection
AC85 - 170V
Ta = 40Cor less
10years or more 10years or more
Ta = 50C
10years or more 6years
AC170 - 264V
Ta = 50Cor less
10years or more 9years
Ta = 60C
6years 4years
C
Convection
AC85 - 170V
Ta = 35Cor less
10years or more 10years or more
Ta = 45C
10years or more 7years
AC170 - 264V
Ta = 50Cor less
10years or more 6years
Ta = 60C
5years 3years
D
Convection
AC85 - 170V
Ta = 35Cor less
10years or more 10years or more
Ta = 45C
10years or more 6years
AC170 - 264V
Ta = 50Cor less
10years or more 7years
Ta = 60C
5years 3years
E
Convection
AC85 - 170V
Ta = 35Cor less
10years or more 10years or more
Ta = 45C
10years or more 6years
AC170 - 264V
Ta = 50Cor less
10years or more 7years
Ta = 60C
5years 3years
A,B,C,D
and E Forced air
AC85 - 264V
Ta = 70C
5years 3years
Table 5.2 Life Expectancy (KHEA60F, KHNA60F)
Mounting
method
Cooling
method
Input
voltage
Average ambient
temperature (year)
Life Expectancy
Load factor
Io[75%
Load factor
75%<Io[100%
A
Convection
AC85 - 170V
Ta = 45Cor less
10years or more 7years
Ta = 55C
6years 3years
AC170 - 264V
Ta = 45Cor less
10years or more 10years or more
Ta = 55C
9years 6years
B
Convection
AC85 - 170V
Ta = 30Cor less
10years or more 8years
Ta = 40C
10years or more 3years
AC170 - 264V
Ta = 45Cor less
10years or more 7years
Ta = 55C
5years 3years
C
Convection
AC85 - 170V
Ta = 40Cor less
10years or more 6years
Ta = 50C
7years 3years
AC170 - 264V
Ta = 40Cor less
10years or more 10years or more
Ta = 50C
8years 5years
D
Convection
AC85 - 170V
Ta = 30Cor less
10years or more 5years
Ta = 40C
8years 2years
AC170 - 264V
Ta = 40Cor less
10years or more 10years or more
Ta = 50C
7years 4years
E
Convection
AC85 - 170V
Ta = 30Cor less
10years or more 7years
Ta = 40C
9years 3years
AC170 - 264V
Ta = 35Cor less
10years or more 10years or more
Ta = 45C
10years or more 9years
A,B,C,D
and E Forced air
AC85 - 264V
Ta = 70C
5years 3years
Table 5.3 Life Expectancy (KHEA90F, KHNA90F)
Mounting
method
Cooling
method
Input
voltage
Average ambient
temperature (year)
Life Expectancy
Load factor
Io[75%
Load factor
75%<Io[100%
A
Convection
AC85 - 170V
Ta = 45Cor less
10years or more 8years
Ta = 55C
7years 4years
AC170 - 264V
Ta = 45Cor less
10years or more 10years or more
Ta = 55C
10years or more 7years
B
Convection
AC85 - 170V
Ta = 35Cor less
10years or more 10years or more
Ta = 45C
10years or more 7years
AC170 - 264V
Ta = 30Cor less
10years or more 10years or more
Ta = 40C
10years or more 10years or more
C
Convection
AC85 - 170V
Ta = 30Cor less
10years or more 10years or more
Ta = 40C
10years or more 8years
AC170 - 264V
Ta = 30Cor less
10years or more 10years or more
Ta = 40C
10years or more 10years or more
D
Convection
AC85 - 170V
Ta = 35Cor less
10years or more 10years or more
Ta = 45C
10years or more 5years
AC170 - 264V
Ta = 30Cor less
10years or more 10years or more
Ta = 40C
10years or more 10years or more
E
Convection
AC85 - 170V
Ta = 35Cor less
10years or more 10years or more
Ta = 45C
10years or more 6years
AC170 - 264V
Ta = 30Cor less
10years or more 10years or more
Ta = 40C
10years or more 10years or more
A,B,C,D
and E Forced air
AC85 - 264V
Ta = 70C
5years 3years
AC-DC Power Supplies DIN Rail Type Instruction Manual
KH-26 June 29, 2020

Table 5.4 Life Expectancy (KHEA120F, KHNA120F)
Mounting
method
Cooling
method
Input
voltage
Average ambient
temperature (year)
Life Expectancy
Load factor
Io[75%
Load factor
75%<Io[100%
A
Convection
AC85 - 170V
Ta = 50Cor less
10years or more 8years
Ta = 60C
8years 3years
AC170 - 264V
Ta = 50Cor less
10years or more 10years or more
Ta = 60C
6years 4years
B
Convection
AC85 - 170V
Ta = 40Cor less
10years or more 10years or more
Ta = 50C
10years or more 6years
AC170 - 264V
Ta = 40Cor less
10years or more 10years or more
Ta = 50C
10years or more 9years
C
Convection
AC85 - 170V
Ta = 20Cor less
10years or more 10years or more
Ta = 30C
10years or more 10years or more
AC170 - 264V
Ta = 40Cor less
10years or more 10years or more
Ta = 50C
8years 6years
D
Convection
AC85 - 170V
Ta = 20Cor less
10years or more 10years or more
Ta = 30C
10years or more 10years or more
AC170 - 264V
Ta = 40Cor less
10years or more 10years or more
Ta = 50C
9years 7years
E
Convection
AC85 - 170V
Ta = 20Cor less
10years or more 10years or more
Ta = 30C
10years or more 10years or more
AC170 - 264V
Ta = 40Cor less
10years or more 10years or more
Ta = 50C
9years 7years
A,B,C,D
and E Forced air
AC85 - 264V
Ta = 70C
5years 3years
Table 5.5 Life Expectancy (KHEA240F, KHNA240F)
Mounting
method
Cooling
method
Input
voltage
Average ambient
temperature (year)
Life Expectancy
Load factor
Io[75%
Load factor
75%<Io[100%
A
Convection
AC85 - 170V
Ta = 40Cor less
10years or more 9years
Ta = 50C
8years 4years
AC170 - 264V
Ta = 50Cor less
10years or more 6years
Ta = 60C
6years 4years
B
Convection
AC85 - 170V
Ta = 30Cor less
10years or more 10years or more
Ta = 40C
10years or more 10years or more
AC170 - 264V
Ta = 40Cor less
10years or more 10years or more
Ta = 50C
10years or more 10years or more
C
Convection
AC85 - 170V
Ta = 20Cor less
10years or more 10years or more
Ta = 30C
10years or more 10years or more
AC170 - 264V
Ta = 40Cor less
10years or more 10years or more
Ta = 50C
9years 5years
D and E
Convection
AC85 - 170V
Ta = 20Cor less
10years or more 10years or more
Ta = 30C
10years or more 8years
AC170 - 264V
Ta = 40Cor less
10years or more 9years
Ta = 50C
8years 4years
A,B,C,D
and E Forced air
AC85 - 264V
Ta = 70C
5years 3years
Table 5.6 Life Expectancy (KHEA480F, KHNA480F)
Mounting
method
Cooling
method
Input
voltage
Average ambient
temperature (year)
Life Expectancy
Load factor
Io[75%
Load factor
75%<Io[100%
A
Convection
AC85 - 170V
Ta = 40Cor less
10years or more 4years
Ta = 45C
7years 3years
Ta = 50C
5years 2years
AC170 - 264V
Ta = 50Cor less
8years 4years
Ta = 55C
5years 3years
Ta = 60C
4years 2years
B
Convection
AC85 - 170V
Ta = 10Cor less
10years or more 10years or more
Ta = 20C
10years or more 10years or more
AC170 - 264V
Ta = 20Cor less
10years or more 10years or more
Ta = 30C
10years or more 10years or more
C
Convection
AC85 - 170V
Ta = 15Cor less
10years or more 10years or more
Ta = 25C
10years or more 5years
AC170 - 264V
Ta = 30Cor less
10years or more 7years
Ta = 40C
8years 3years
D
Convection
AC85 - 170V
Ta = 10Cor less
10years or more 10years or more
Ta = 20C
10years or more 5years
AC170 - 264V
Ta = 20Cor less
10years or more 10years or more
Ta = 30C
10years or more 5years
E
Convection
AC85 - 170V
Ta = 10Cor less
10years or more 7years
Ta = 20C
8years 3years
AC170 - 264V
Ta = 20Cor less
10years or more 7years
Ta = 30C
10years or more 3years
A,B,C,D
and E Forced air
AC85 - 264V
Ta = 70C
5years 3years
¡Warranty
Table 5.7 Warranty (KHEA30F, KHNA30F)
Mounting
method
Cooling
method
Input
voltage
Average ambient
temperature (year)
Warranty term
Load factor
Io[75%
Load factor
75%<Io[100%
A
Convection
AC85 - 170V
Ta = 50Cor less
5years 5years
Ta = 60C
5years 3years
AC170 - 264V
Ta = 50Cor less
5years 5years
Ta = 60C
5years 3years
B
Convection
AC85 - 170V
Ta = 40Cor less
5years 5years
Ta = 50C
5years 3years
AC170 - 264V
Ta = 50Cor less
5years 5years
Ta = 60C
5years 3years
C
Convection
AC85 - 170V
Ta = 35Cor less
5years 5years
Ta = 45C
5years 5years
AC170 - 264V
Ta = 50Cor less
5years 5years
Ta = 60C
5years 3years
D and E
Convection
AC85 - 170V
Ta = 35Cor less
5years 5years
Ta = 45C
5years 3years
AC170 - 264V
Ta = 50Cor less
5years 5years
Ta = 60C
5years 3years
A,B,C,D
and E Forced air
AC85 - 264V
Ta = 70C
5years 3years
AC-DC Power Supplies DIN Rail Type Instruction Manual
KH-27
June 29, 2020

Table 5.8 Warranty (KHEA60F, KHNA60F)
Mounting
method
Cooling
method
Input
voltage
Average ambient
temperature (year)
Warranty term
Load factor
Io[75%
Load factor
75%<Io[100%
A
Convection
AC85 - 170V
Ta = 45Cor less
5years 3years
Ta = 55C
5years 3years
AC170 - 264V
Ta = 45Cor less
5years 5years
Ta = 55C
5years 3years
B
Convection
AC85 - 170V
Ta = 30Cor less
5years 5years
Ta = 40C
5years 3years
AC170 - 264V
Ta = 45Cor less
5years 3years
Ta = 55C
5years 3years
C
Convection
AC85 - 170V
Ta = 40Cor less
5years 3years
Ta = 50C
5years 3years
AC170 - 264V
Ta = 40Cor less
5years 5years
Ta = 50C
5years 3years
D
Convection
AC85 - 170V
Ta = 30Cor less
5years 3years
Ta = 40C
5years 2years
AC170 - 264V
Ta = 40Cor less
5years 5years
Ta = 50C
5years 3years
E
Convection
AC85 - 170V
Ta = 30Cor less
5years 3years
Ta = 40C
5years 3years
AC170 - 264V
Ta = 35Cor less
5years 5years
Ta = 45C
5years 3years
A,B,C,D
and E Forced air
AC85 - 264V
Ta = 70C
5years 3years
Table 5.9 Warranty (KHEA90F, KHNA90F)
Mounting
method
Cooling
method
Input
voltage
Average ambient
temperature (year)
Warranty term
Load factor
Io[75%
Load factor
75%<Io[100%
A
Convection
AC85 - 170V
Ta = 45Cor less
5years 5years
Ta = 55C
5years 3years
AC170 - 264V
Ta = 45Cor less
5years 5years
Ta = 55C
5years 5years
B
Convection
AC85 - 170V
Ta = 35Cor less
5years 5years
Ta = 45C
5years 5years
AC170 - 264V
Ta = 30Cor less
5years 5years
Ta = 40C
5years 5years
C
Convection
AC85 - 170V
Ta = 30Cor less
5years 5years
Ta = 40C
5years 5years
AC170 - 264V
Ta = 30Cor less
5years 5years
Ta = 40C
5years 5years
D and E
Convection
AC85 - 170V
Ta = 35Cor less
5years 5years
Ta = 45C
5years 3years
AC170 - 264V
Ta = 30Cor less
5years 5years
Ta = 40C
5years 5years
A,B,C,D
and E Forced air
AC85 - 264V
Ta = 70C
5years 3years
Table 5.10 Warranty (KHEA120F, KHNA120F)
Mounting
method
Cooling
method
Input
voltage
Average ambient
temperature (year)
Warranty term
Load factor
Io[75%
Load factor
75%<Io[100%
A
Convection
AC85 - 170V
Ta = 50Cor less
5years 5years
Ta = 60C
5years 3years
AC170 - 264V
Ta = 50Cor less
5years 5years
Ta = 60C
5years 4years
B
Convection
AC85 - 170V
Ta = 40Cor less
5years 5years
Ta = 50C
5years 5years
AC170 - 264V
Ta = 40Cor less
5years 5years
Ta = 50C
5years 5years
C,D and E
Convection
AC85 - 170V
Ta = 20Cor less
5years 5years
Ta = 30C
5years 5years
AC170 - 264V
Ta = 40Cor less
5years 5years
Ta = 50C
5years 3years
A,B,C,D
and E Forced air
AC85 - 264V
Ta = 70C
5years 3years
Table 5.11 Warranty (KHEA240F, KHNA240F)
Mounting
method
Cooling
method
Input
voltage
Average ambient
temperature (year)
Warranty term
Load factor
Io[75%
Load factor
75%<Io[100%
A
Convection
AC85 - 170V
Ta = 40Cor less
5years 5years
Ta = 50C
5years 3years
AC170 - 264V
Ta = 50Cor less
5years 5years
Ta = 60C
5years 3years
B
Convection
AC85 - 170V
Ta = 30Cor less
5years 5years
Ta = 40C
5years 5years
AC170 - 264V
Ta = 40Cor less
5years 5years
Ta = 50C
5years 5years
C,D and E
Convection
AC85 - 170V
Ta = 20Cor less
5years 5years
Ta = 30C
5years 5years
AC170 - 264V
Ta = 40Cor less
5years 5years
Ta = 50C
5years 3years
A,B,C,D
and E Forced air
AC85 - 264V
Ta = 70C
5years 3years
Table 5.12 Warranty (KHEA480F, KHNA480F)
Mounting
method
Cooling
method
Input
voltage
Average ambient
temperature (year)
Warranty term
Load factor
Io[75%
Load factor
75%<Io[100%
A
Convection
AC85 - 170V
Ta = 40Cor less
5years 4years
Ta = 45C
5years 3years
Ta = 50C
4years 2years
AC170 - 264V
Ta = 50Cor less
5years 4years
Ta = 55C
5years 3years
Ta = 60C
4years 2years
B
Convection
AC85 - 170V
Ta = 10Cor less
5years 5years
Ta = 20C
5years 5years
AC170 - 264V
Ta = 20Cor less
5years 5years
Ta = 30C
5years 5years
C
Convection
AC85 - 170V
Ta = 15Cor less
5years 5years
Ta = 25C
5years 5years
AC170 - 264V
Ta = 30Cor less
5years 5years
Ta = 40C
5years 3years
D
Convection
AC85 - 170V
Ta = 10Cor less
5years 5years
Ta = 20C
5years 5years
AC170 - 264V
Ta = 20Cor less
5years 5years
Ta = 30C
5years 5years
E
Convection
AC85 - 170V
Ta = 10Cor less
5years 5years
Ta = 20C
5years 3years
AC170 - 264V
Ta = 20Cor less
5years 5years
Ta = 30C
5years 3years
A,B,C,D
and E Forced air
AC85 - 264V
Ta = 70C
5years 3years
AC-DC Power Supplies DIN Rail Type Instruction Manual
KH-28 June 29, 2020

6 Applicable Electric
Cable
¡Input terminals, Output terminals
¿ KHEA30F/60F/90F/120F/240F
Table 6.1 Applicable Wire
Input terminals Output terminals
Solid wire Diameter 0.5 mm to 2.6 mm (AWG.24 to AWG.10)
Stranded wire 0.2mm2to 5.2mm2(AWG.24 to AWG.10)
Conductor diameter more than 0.18mm
Sheath strip length 8mm
¿ KHEA480F
Table 6.2 Applicable Wire
Input terminals Output terminals
Solid wire Diameter 0.8 mm to 2.6 mm (AWG.20 to AWG.10)
Stranded wire 0.5mm2to 5.2mm2(AWG.20 to AWG.10)
Conductor diameter more than 0.18mm
Sheath strip length 8mm
¡RC terminals
¿ KHEA120F/240F/480F,
KHNA120F/240F/480F
Table 6.3 Applicable Wire
RC terminals
Solid wire Diameter 0.5 mm to 1.3 mm (AWG.24 to AWG.16)
Stranded wire 0.2 mm2to 1.5 mm2 (AWG.24 to AWG.16)
Sheath strip length 8mm
7 Option
7.1 Outline of option
¿ -C
-Option -C models have coated internal PCB for better moisture
resistance.
¿ -E
(KHEA90F, KHNA90F)
-Option -E models acquires NEC Class2.
¿ -N2
(KHEA120F/240F/480F, KHNA120F/240F/480F)
-Option -N2 models have attachment with screw mounting in-
stead of DIN rail mounting.
Mounting holes pitch are shown in Table 7.1.
4-f4.5
B
A
Fig.7.1 Image of option -N2 Fig.7.2 Mounting place
(screw holes)
Table 7.1 Mounting holes pitch
No. Model A B
1 KHEA120F, KHNA120F 23mm 133mm
2 KHEA240F, KHNA240F 34mm 133mm
3 KHEA480F, KHNA480F 54mm 133mm
7.2 Others
¡While turning on the electricity, and for a while after turning off,
please don’t touch the inside of a power supply because there are
some hot parts in that.
¡When a mass capacitor is connected with the output terminal
(load side), the output might become the stop or an unstable oper-
ation. Please contact us for details when you connect the capaci-
tor.
AC-DC Power Supplies DIN Rail Type Instruction Manual
KH-29
June 29, 2020
This manual suits for next models
11
Table of contents
Other Cosel Power Supply manuals

Cosel
Cosel LDA10F User manual

Cosel
Cosel ADA600F User manual

Cosel
Cosel TUHS3 User manual

Cosel
Cosel PBA300F User manual

Cosel
Cosel LCA10S User manual

Cosel
Cosel HCA3500TF-48 User manual

Cosel
Cosel LFP100F User manual

Cosel
Cosel LGA50A User manual

Cosel
Cosel SNA-01 User manual

Cosel
Cosel KL Series User manual

Cosel
Cosel STA5000T-R User manual

Cosel
Cosel FETA2500B User manual

Cosel
Cosel TUHS3F User manual

Cosel
Cosel LCC30A User manual

Cosel
Cosel PLA100F User manual

Cosel
Cosel KLEA120F User manual

Cosel
Cosel PLA30F User manual

Cosel
Cosel AME600F User manual

Cosel
Cosel LGA100A User manual

Cosel
Cosel SPLFA30F User manual