Dorma EMR Series User manual

GENERAL DESCRIPTION
Each 8900 EMR series unit contains a door closer, hold
open electromagnet and smoke detector. The unit can be
used as a single installation or as a series of singles
powered from one or more power supplies. When a
series of 8900 EMR units are wired together in a run,
groups of up to 5 units may be interconnected.
Interconnection is accomplished through terminals #4
and #15 and results in all units alarming when any one
of them senses smoke. In turn, all associated hold
open electromagnets are de-energized. Within any run of
detectored units, it is permissible to form as many
interconnected groups as the total power supply
amperage will allow; but, again no more than 5 units
can be interconnected together.
Any detectored 8900 EMR series unit can be connected
to an auxiliary EMF non-detectored unit, or remote
detector, or both. It can be a single installation or part
of any of the multiple arrangements described above.
An auxiliary unit (double door applications) is a
companion to the main unit, and its electromagnet
de-energizes along with the main unit. A remote open
area detector sensing smoke alarms the 8900 EMR to
which it is connected and any other 8900 EMR to which
it is interconnected.
Single installations or groups of installations can be
connected to the alarm initiation circuit of a compatible
UL/ULC listed fire alarm control unit in 4-wire or 6-wire
configurations.
Additional functions are provided to separately power
the hold open electromagnets directly from the alarm
control panel as well as connections for a remote alarm
indicator lamp.
8900 EMR
(WITH DETECTOR)
INSPK NO. 08279530 Rev 08/13
INSTALLATION
1. Read entire instruction sheet prior to installation
and refer to NFPA 72E. Standards may be obtained
from THE NATIONAL FIRE PROTECTION
ASSOCIATION, Batterymarch Park, Quincy,
MA 02269.
2. Reference unit carton for unit mounting type.
3. Prepare door and frame for fasteners using the
appropriate template. Mark, drill, and tap holes as
indicated. If surface wiring is used, omit 7/8" hole
for wire access.
NOTE:
If installing the optional bypass switch, install assembly
on the end of track as shown. Fasten track to door frame
with the screw provided (T mount uses a cylindrical spacer).
Fasten the end cap assembly with metal or wood screws
provided. Connect the switch with wire nuts and slide the
cover in place. For T mount, place end cap in extension
piece and fasten to frame with screw provided.
Optional Bypass Switch - PT Mount
Optional Track Bypass Switch - T Mount
www.dorma-usa.com 1-800-523-8483
INS NO.
Rev.
08280990
08/13
PAGE
1 of 14

4
(2) 1/4-20 x 2" metal or (2) No. 14 x 2-3/4" wood screws.
Install with detector cut out toward latch edge of door using
Install track to frame.
8900T and 8900DE
8900PT
END CAP
END CAP
Install with detector cutout toward hinge edge of door using
(2) 1/4-20 x 2" metal or (2) No. 14 x 2-3/4" wood screws.
5
C HINGE
Install detector.
Slide detector slot under standoff
T & DE (RH)
T & DE (LH)
NOTE: NO TOP PLUG
ON PT MOUNTS
Remove (1) wire access plug according to
the installation type.
6
NOTE:
If construction is still being completed near detector installation "DO NOT"
install detector at this time or protect the detector from construction dust
contaminants.
(SURFACE CONDUIT)
C HINGE
NOTE:
Three access wire
holes on optional
surface wired units only.
and attach with (4) screws.
STANDOFF
SLOT
QTY
(2) (2)
QTY
QTY
(2) (2)
QTY
INS NO.
PAGE
Rev.
08280990
2 of 14
08/13

Install closer to door.
8900T AND 8900DE
8900PT
7
(RIGHT HAND DOOR)
(LEFT HAND DOOR)
(LEFT HAND DOOR)
(RIGHT HAND DOOR)
8
8900T
(RIGHT HAND DOOR)
(LEFT HAND DOOR)
Attach main arm to door closer.
(4)
QTY
METAL FRAMES
WOOD FRAMES
(4)
QTY
Place arm on top pinion as shown @ 45° angle. Secure with pinion screw.
6mm HEX KEY
6mm HEX KEY
QTY
(1)
INS NO.
PAGE
Rev.
08280990
3 of 14
08/13

8900PT
(LEFT HAND DOOR)
(RIGHT HAND DOOR)
With door in closed position, rotate spindle 45° with wrench. Place arm on spindle.
Open door and secure with pinion screw.
C HINGE HINGE C
Attach arm to slide shoe. Use 3/16 inch hex head wrench.
9
ROTATE
PINION
45°
6mm HEX KEY
ROTATE
PINION
45°
6mm HEX KEY
10
BACKCHECK OR DELAYED ACTION
NOTE: DELAYED ACTION IS AN OPTIONAL FEATURE.
DECREASE
Adjust sweep, latch and backcheck valves.
CAUTION: DO NOT REMOVE VALVES.
LATCH
RANGE
BACKCHECK
BACKCHECK RANGE
RANGE
ACTION
SWEEP (SPEED)
INCREASE
DELAYED ACTION
RANGE
LATCH
(SPEED)
(TIME)
11
DELAYED
SWEEP
DECREASE
SWEEP & LATCH
POSITIONING VALVE
(INTENSITY)
INCREASE
Adjust spring tension, if required, using a 1/4" wrench.
NOTE:
8956 supplied with size 6 setting.
CRITICAL
8916 supplied with size 3 spring setting.
-
+
SPRING TENSION
ADJUSTER
SPRING
DOOR WIDTH
INTERIOR
8956
4'-0"
CLOSER
8916
TYPE
3'-6"
3'-6"
3'-0"
2'-6"
+6 6+
Adjust according to chart.
0
+16
+8
OF SPRING
FULL TURNS
ADJUSTER
0
6
6
4
5
SIZE
MAX.
125
150
WEIGHT
DOOR
200
200
ULC LABELED UNITS ONLY
ADJUST SPRING TENSION ACCORDING TO THE FOLLOWING CHART.
8916
8956
CLOSER
TYPE
ADJUSTING NUT
5
+8
6
6
0
+16
SPRING
SIZE
4
OF SPRING
FULL TURNS
0
250
6+ +6
NOTE: DO NOT ADJUST SPRING LOWER THAN SIZE 3
6mm HEX KEY
6mm HEX KEY
Place arm on top pinion as shown @ 45° angle. Secure with pinion screw.
Attach main arm to door closer.
8905DE
INS NO.
PAGE
Rev.
08280990
4 of 14
08/13

The following six pages contain wiring options. Wire the units according to building and system
DETECTOR CONNECTION LIST
FUNCTION
AC/DC 24V INPUT
ALARM CONTACTS (NORMALLY OPEN)
ELECTROMAGNET
REMOTE ALARM INDICATOR LAMP +
REMOTE ALARM INDICATOR LAMP -
INTERCONNECT +
INTERCONNECT -
TROUBLE CONTACTS (NORMALLY CLOSED)
24 VDC OUTPUT (UNFILTERED) +
IF JUMPER WIRE J11/J12 IS CUT,
TERMINALS 8, 9 AND 10 ARE
CHANGED TO FORM C RELAY
CONTACTS, RAIL OUTPUT IS
LOST, AND HOLD OPEN ELECTROMAGNETS
MUST BE POWERED FROM A SEPARATE
SOURCE. CONSULT FACTORY
IF REMOTE DETECTORS ARE USED
IN THIS APPLICATION.
TERMINAL
3, 14
1, 2
6, 9
8
7
15
4
5,13
10
N.O. 8
N.C. 9
COM 10
ELECTRICAL SPECIFICATIONS
Voltage input:
Maximum input current:
Maximum output to Remote
Contact ratings:
24 VDC +10% - 15%
24 VAC +10% - 15%
@24 VDC- 161 mA (1 solenoid), 310 mA (2 solenoids)
@24 VAC- 161 mA (1 solenoid), 310 mA (2 solenoids)
300 mA
Alarm and or accessory contacts-
1.25 A at 24 VDC or .3 A at 120 VAC
resistive, maximum.
resistive maximum .
Trouble contacts- 500 mA at 24VDC
12
requirements. Observe all applicable codes.
NOTE: Excludes accessories
NOTE: 120 Volt applications require optional external
transformer.
Alarm Indicator Lamp:
LED & TEST
1
2
3
4
5
6
7
15
14
13
12
11
10
9
8
SD-2
INS NO.
PAGE
Rev.
08280990
5 of 14
08/13

SD-2
15
7
5
14
13
12
11
10
9
1
6
4
3
2
8
SD-2
15
7
5
14
13
12
11
10
9
1
6
4
3
2
8
SD-2
15
7
5
14
13
12
11
10
9
1
6
4
3
2
8
POWER SUPPLY
Insulate all connections. Observe all local codes.
120 VAC, 50/60 HZ
24V AC/DC
24V AC/DC WITH REMOTE DETECTORS
NOTE: FOR ULC INSTALLATIONS, TRANSFORMER
MUST INSTALL IN 4" X 4" ELECTRICAL
BOX X 3" DEEP MINIMUM.
EXTERNAL
(OPTIONAL)
120 VAC, 50/60 HZ: Connect the 120 VAC incoming voltage wires to the primary wires of the transformer.
Connect the secondary transformer wires to terminals #3 and #14 of the detector module.
This connection is not polarity dependent.
PRIMARY
TRANSFORMER
WIRES
STEP
DOWN
TRANSFORMER
120VAC
POWER
INPUT
SECONDARY
TRANSFORMER
WIRES
24V AC/DC NOTE: The step down transformer is not used in this connection. Connect 24V AC/DC
power to terminals #3 and #14 on the detectors. These connections are not polarity dependent.
If the unit is connected to a second unit, connect terminal #3 of the first unit to terminal #3 of the
second unit and connect terminal #14 of the first unit to terminal #14 of the second unit.
Continue this process for any subsequent units to be powered from the same power supply.
24 VAC/DC
POWER SUPPLY
(1)(2)
(3)
+
-
SD-2
15
7
5
14
13
12
11
10
9
1
6
4
3
2
8
SD-2
15
7
5
14
13
12
11
10
9
1
6
4
3
2
8
SD-2
15
7
5
14
13
12
11
10
9
1
6
4
3
2
8
SD-2
15
7
5
14
13
12
11
10
9
1
6
4
3
2
8
-
+
-
+
-
+
+
-
REMOTE
DETECTOR
24VAC/DC
POWER SUPPLY
REMOTE
DETECTOR
REMOTE
DETECTOR
24V AC/DC WITH REMOTE DETECTORS NOTE: The step down transformer is not used in this connection.
Perform wiring connections as illustrated below. Additional units are wired in the same manner as unit #2.
Installations using a combination of SD-2 modules with and without remote area detectors can be
wired accordingly by substituting the wiring diagram section from unit #1, #2, or #3 in step #3 above
instead of unit #1, #2, or #3 below with remote detector. The vertical dashed lines indicate where one
diagram would be exchanged for another.
NOTE: Input voltage must match detector voltage.
(1)(2)
(3)
INS NO.
PAGE
Rev.
08280990
6 of 14
08/13

SD-2
15
7
5
14
13
12
11
10
9
1
6
4
3
2
8
WIRE GAUGE
SD-2 DETECTOR TO MAIN SOLENOID CONNECTION
MAIN
HOLD OPEN
ELECTROMAGNET
Strip approximately 1/4" of plastic insulation from the end of the two solenoid wires supplied. Connect
one end each of the electromagnet wires to terminals 6 & 9 of the SD-2 detector as shown.
SD-2
15
7
5
14
13
12
11
10
9
1
6
4
3
2
8
No. OF
ELECTRO-
MAGNET
(E4)
No. OF
ELECTRO-
MAGNET
(E3)
No. OF
ELECTRO-
MAGNET
(E2)
No. OF
ELECTRO-
MAGNET
(E1)
POWER
SUPPLY
TO NEXT HOLD
OPEN ELECTROMAGNET
WIRE LENGTH
TO E4
(D4)
WIRE LENGTH
TO E3
(D3)
WIRE LENGTH
TO E2
(D2)
WIRE LENGTH
TO E1
(D1)
WIRE GAUGE: The maximum wire gauge for wiring the SD-2 detector module is #18 AWG. The method for
determining wire gauge is given below. NOTE: A minimum of 20.4 VDC must be supplied to each solenoid
in the run.
S1, S2, S3 etc. are the number of solenoids at each subsequent station. D1 is the distance from the
power supply to the first solenoid station. D2, D3, D4 etc. are the distances from the previous solenoid
station to the next solenoid station in the run. To determine the correct wire gauge multiply E1 times D1.
Add that quantity to E2 times D2. Repeat the same procedure for each electromagnet to test the last unit in
the run. Compare the quantity calculated to the chart below. The calculated value must be less than or
equal to the value corresponding to the appropriate wire gauge.
10 GAUGE-11,788 12 GAUGE-7,407 14 GAUGE-4,669 16 GAUGE-2,997 18 GAUGE-1,843
The procedure described above can be expressed in the following equation: (E1xD1) + (E2xD2) + (E3xD3)
....(EnxDn) The above values correspond to the wire gauge to be used. If the calculated value is 1,843
#18 AWG wire can be run and connected directly to the detector module. If the calculated value exceeds
1,843 larger wiring will be required. Since the detector will only accept #18 AWG wire, a wiring splice will
be necessary as illustrated below.
#16-#12#16-#12
#16-#12#16-#12
#18
#18
NOTE: FOR ULC INSTALLATIONS, 18 GAUGE
WIRE IS REQUIRED TO DETECTOR
INS NO.
PAGE
Rev.
08280990
7 of 14
08/13

SD-2
15
7
5
14
13
12
11
10
9
1
6
4
3
2
8
SD-2
15
7
5
14
13
12
11
10
9
1
6
4
3
2
8
SD-2 DETECTOR TO AUXILIARY SOLENOID CONNECTION
SOLENOID ATTACHMENT TO UL/ULC LISTED ALARM CONTROL PANEL
SD-2 DETECTOR INTERCONNECTION
NOTE: Make this connection the same time as the main hold open solenoid
connection. Strip approximately 1/4" of plastic insulation from the ends
of the wires. Connect auxilliary hold open solenoid wires to
9&6 of SD-2 detector.
Some applications may require input power to the hold open
electromagnet to be supplied through a UL/ULC listed alarm control
panel so the hold open electromagnet functions separately from the
internal detector module. This application requires the alarm
contacts of the SD-2 detector and any remote detectors
to be connected to the alarm contacts of the control panel. An alarm indication to
the panel results in the loss of power to the hold open electromagnets in the related
zone, which allows the doors to close. Wire main electromagnet to alarm control panel as
illustrated.
POWER IN
PANEL
CONTROL
LISTED ALARM
UL/ULC
24VOLT ONLY
ELECTROMAGNET
HOLD OPEN
OPEN ELECTROMAGNET
AUXILIARY HOLD
14
7
2
1
3
9
8
10
4
5
6
11
12
13
15
SD-2
ELECTROMAGNET
MAIN HOLD
OPEN
SD-2
15
7
5
14
13
12
11
10
9
1
6
4
3
2
8
SD-2
15
7
5
14
13
12
11
10
9
1
6
4
3
2
8
SD-2
15
7
5
14
13
12
11
10
9
1
6
4
3
2
8
SD-2
15
7
5
14
13
12
11
10
9
1
6
4
3
2
8
1. Up to (5) SD-2 detectors, with or without connection to an auxiliary unit or remote area detector may
be interconnected. This limitation applies only to interconnected units and assumes a power supply large
enough to handle this load if the power supply is common to all units interconnected. Separate power
supplies may be used for each SD-2 detector while permitting the units to be interconnected.
2a. For units without connection to remote detectors, connect terminal #15 (+) between the units to be
interconnected. Connect terminal #4 (-) between the units to provide a common for the interconnection.
Additional units are wired in the same manner as unit #2 but no more than five (5) units can be
interconnected.
2b. For units used in conjunction with remote area detectors, complete wiring connections as illustrated
below. Heed caution note in SD-2 DETECTOR TO REMOTE AREA DETECTOR section of instruction sheet.
Additional units are wired in the same manner as unit #2 but no more than five (5) units can be
interconnected. Installations using a combination of SD-2 detector modules with or without remote area
detectors can be wired accordingly by substituting the wiring diagram from unit 1, 2, or 3 in step 2a.
above for unit 1, 2, or 3 below. The vertical dashed lines indicate where one (1) diagram would be
exchanged for another.
C
NO NO
C
NO
C
REMOTE
DETECTOR
REMOTE
DETECTOR
REMOTE
DETECTOR
(1)
(2)
(3)
(1)
(2)
(3)
INS NO.
PAGE
Rev.
08280990
8 of 14
08/13

SD-2
15
7
5
14
13
12
11
10
9
1
6
4
3
2
8
SD-2
15
7
5
14
13
12
11
10
9
1
6
4
3
2
8
SD-2 DETECTOR TO REMOTE AREA DETECTOR
SD-2 DETECTOR TO AUDIBLE SIGNAL APPLIANCE
A remote open area detector can only be connected to a unit whose trouble relay contacts
(#5 & #13) are connected in a circuit for the purpose of obtaining an audible trouble signal
in the event of a circuit fault. In the event that the unit is used for releasing service only,
the trouble contacts are connected to the trouble circuit of a UL/ULC listed alarm control
panel. This condition is satisfied by the four (4) and six (6) wire supervisory connections in
the alarm initiation wiring section. Perform wiring connections as illustrated below. NOTE: The
SD-2 is wired as the E.O.L. (end of line) device for the remote detector. Therefore, it
must act as the last item in the loop.
CONTROL UNIT
-
+
24VAC/DC
POWER SUPPLY
UL/ULC LISTED AUDIBLE
SIGNAL APPLIANCE OR
REMOTE
DETECTOR
CAUTION:
SD-2
15
7
5
14
13
12
11
10
9
1
6
4
3
2
8
SD-2
15
7
5
14
13
12
11
10
9
1
6
4
3
2
8
SD-2
15
7
5
14
13
12
11
10
9
1
6
4
3
2
8
1. Connect terminals #5 & #13 of a singular unit directly to a UL/ULC listed audible signal
appliance or alarm control panel.
CONTROL UNIT
UL/ULC LISTED AUDIBLE
SIGNAL APPLIANCE OR
2. Installations with multiple units in a run must be connected to a UL/ULC listed audible signal
appliance or alarm control panel as illustrated below.
SIGNAL APPLIANCE OR
UL/ULC LISTED AUDIBLE
CONTROL UNIT
INS NO.
PAGE
Rev.
08280990
9 of 14
08/13

SD-2
15
7
5
14
13
12
11
10
9
1
6
4
3
2
8
SD-2
15
7
5
14
13
12
11
10
9
1
6
4
3
2
8
SD-2
15
7
5
14
13
12
11
10
9
1
6
4
3
2
8
SD-2 DETECTOR TO REMOTE ALARM INDICATOR LAMP
ALARM INITIATION WIRING (4 WIRE CLASS B & 6 WIRE CLASS A)
CONTINUED ON PAGE 11
REMOTE
ALARM
INDICATOR
LAMP
Connect the positive wire of the remote alarm indicator lamp to terminal #8 of the detector module.
Connect the negative terminal of the indicator lamp to terminal #7 of the SD-2 detector.
-
+
*EOL
+
-
*EOL USED IN 4 WIRE APPLICATIONS ONLY
UL/ULC
LISTED
INITIATING
CIRCUIT
CONNECTIONS FOR SIX (6)
WIRE INSTALLATION
RETURN
LOOP
+
-
ALARM RELAY
*EOL USED IN 4 WIRE APPLICATIONS ONLY
REMOTE
DETECTOR
INITIATING
CIRCUIT
UL/ULC
LISTED
1. Make all connections as outlined previously for all units required by the job specifications.
2. Make all signal initiating connections as illustrated in the appropriate figure below. Note wiring differences
for units with remote detectors vs. units without remote detectors. Dashed lines to return loop represent
wires required for six (6) wire applications. These wires are omitted in four (4) wire applications.
3. Connections to only one (1) SD-2 are shown below.
LOOP
RETURN
WIRE INSTALLATION
CONNECTIONS FOR SIX (6)
+
-
*EOL
INS NO.
PAGE
Rev.
08280990
10 of 14
08/13

SD-2
15
7
5
14
13
12
11
10
9
1
6
4
3
2
8
SD-2
15
7
5
14
13
12
11
10
9
1
6
4
3
2
8
SD-2
15
7
5
14
13
12
11
10
9
1
6
4
3
2
8
SD-2
15
7
5
14
13
12
11
10
9
1
6
4
3
2
8
SD-2
15
7
5
14
13
12
11
10
9
1
6
4
3
2
8
SD-2
15
7
5
14
13
12
11
10
9
1
6
4
3
2
8
ALARM INITIATION WIRING CON'T.
resistor specified by the fire alarm control panel used. The E.O.L. resistor is only installed in the first
6. In four (4) wire installations, it is the responsiblity of the installer to supply and connect the E.O.L.
WIRE INSTALLATION
CONNECTIONS FOR SIX (6)
as shown for unit 2. The last unit in the run must be connected in the same manner as unit 3.
5. More than three (3) SD-2 detectors are connected by inserting additional units with connections
to detector (3) in the same manner as it is shown connected to detector (2). Detector (2) would
4. Connections for two (2) SD-2 detectors would consist of detector (1) in figure below connected
unit of the run as illustrated.
*EOL USED IN 4 WIRE APPLICATIONS ONLY
*EOL USED IN 4 WIRE APPLICATIONS ONLY
ALARM RELAY
REMOTE
DETECTOR
(3)
(3)
be deleted.
REMOTE
DETECTOR
ALARM RELAY
(2)
DETECTOR
REMOTE
ALARM RELAY
(2) (1)
*EOL
*EOL
(1)
CIRCUIT
LISTED
UL/ULC
INITIATING
LOOP
RETURN
-
+
+
CONNECTIONS FOR SIX (6)
CIRCUIT
INITIATING
UL/ULC
-
+
LISTED
-
WIRE INSTALLATION
RETURN
+
-
LOOP
INS NO.
PAGE
Rev.
08280990
11 of 14
08/13

SD-2 DETECTOR SENSITIVITY TEST (ULC REQUIREMENT ONLY)
FINAL INSTALLATION AND TEST
engages with hold open assembly.
Open door so slide shoe
Loosen set screws using 3/32 inch hex wrench. Slide hold open device to desired position.
GREATER HOLD
Retighten set screws securely.
Hold open position is preset at approximately 90°.
OPEN ANGLE
HOLD OPEN SET SCREWS - 3/32 HEX
HOLD OPEN DEVICE
OPEN ANGLE
Install detector cover.
Slide tab of cover under end of detector and
TAB
DETECTOR
SCREW
rotate into possession. Insert (1) 4-40 screw
ROTATE
and tighen.
13
14
15
16
17
18
LESS HOLD
HOLD OPEN FORCE ADJUSTMENT -5/32 HEX
CLOCKWISE = STRONGER
With power applied to the detector, connect a volt meter to the two test terminals.
Voltage output terminals are provided to measure the sensitivity of the smoke detector.
The normal range is between 1.27 - 3.38 Vdc.
SENSITIVITY TEST TERMINALS
to ten (10) seconds to indicate the unit is
connections. The LED will blink every seven (7)
After installation is completed, check all
LED
operating properly.
The LED should remain continually red and allow
Turn counterclockwise and hold for ten seconds.
into the slot in the light pipe of the detector.
To test the detector, insert a small screwdriver
the door to close.
Turn light pipe clockwise to reset the detector.
The LED will go off. Turn the light pipe to the
normal position and the unit will resume blinking
every seven (7) to ten (10) seconds to indicate
that it is reset and functioning properly.
INS NO.
PAGE
Rev.
08280990
12 of 14
08/13

Place tab in cover slot opposite main arm.
Place cover over closer and fasten securely with
screws provided.
TAB
NOTE: LEFT HAND INSTALLATION SHOWN. RIGHT
HAND IS A MIRROR IMAGE.
QTY
(2)
IMPORTANT: THE UNIT MUST BE TESTED AFTER THE
INSTALLATION, BY THE END USER, TO ASSURE
THAT THE DOOR CLOSER UNITS FUNCTION PROPERLY
WHEN THE ALARM SYSTEM IS ACTIVATED. THE ENTIRE
SYSTEM MUST ALSO BE TESTED PERIODICALLY AFTER
THE INITIAL INSTALLATION TEST, IN CONJUNCTION WITH
THE TESTING OF THE FIRE ALARM SYSTEM. THE END
USER IS ALSO RESPONSIBLE FOR THE ADJUSTMENTS
AND MAINTENANCE TO RETAIN THE SYSTEM IN
WORKING ORDER.
SD-2 DETECTOR MAINTENANCE
The SD-2 Detector has been designed to be as
maintenance-free as possible. Normal air-borne
dust, however, can accumulate in the detector
sensing chamber and cause it to become more
sensitive. All detectors must be tested and cleaned
at least once a year. Detectors in dusty environ-
ments must be tested and cleaned more often.
Detectors must also be tested and cleaned imme-
diately after a fire. Failure to maintain detectors
may result in needless false alarms.
21
20
3
An auxiliary door stop (by others) must be
installed to limit the maximum degree of door
swing. Failure to do so may result in damage
to the unit.
19
1
SNAP VALVE ADJUSTMENT
WRENCH INSIDE COVER
RP1 & RP2. This voltage is a small signal, DC
voltage. Set meter to the 2 volt scale.
RP2
RP1
Measure and record test voltage at test points
2
the first time.
straight up. Cover may be difficult to remove
screwdriver in slot (both sides) and pulling it
First, vacuum or blow off any loose debris on
cover and screen assembly by rotating a flat
outside of cover. Then, remove the detector
CHAMBER
FINS
reassembling the detector, be sure all parts are
COVER
free of debris.
UNDER
COVER
SCREEN
PHOTO
off same areas with compressed air. Before
Vacuum all areas illustrated below, and then blow
INS NO.
PAGE
Rev.
08280990
13 of 14
08/13

SMOKE DETECTOR TESTING
Measure and record test voltage at test points
RP1 & RP2. If the product is operating
normally, and was cleaned effectively, the test
voltage will be less than the voltage recorded
earlier. (Typical voltage for a clean device is.9
- 1.58 Vdc.)
5
Replace cover and screen assembly.
4
Adapter
Tube
If the detector is in an area where air velocities exceed 100 feet/minute, the detector may not
alarm on the first try. This could be due to the signal processing feature of the detector. Signal
processing is a feature that adds a time delay to each detector which effectively increases its
stability. If this is the case, spray in repeated bursts of 1 second at approximately 5 to 10 second
intervals. The total number of sprays should not exceed five (5). If the detector does not alarm
after 5 consecutive sprays, it will be necessary to generate larger volumes of smoke to overcome the
air flow dilution factor. This can be accomplished by burning paper or fabric in a metal can.
DORMA accepts the use of Home Safeguard Smoke Detector Tester (Models 1H and 25S) if, and only
if, it is used:
1. with the Model 1490 Accessory.
2. with the new formula aerosol as identified by a date code, located on the bottom
of the can, of 1990 or later. (This date code can be read as first numeral = last
digit of year so that a B0xxx = 1990 and B9xxx = 1989.)
3. in accordance with the instructions stated above.
If the preceding requirements are not met, the use of Smoke Detector Tester is unacceptable and
DORMA cannot guarantee the proper operation of detectors that have been subjected to this product.
Alternative methods of generating smoke/aerosol such as the Gemini 501 Smoke Generator Machine
may be used to cause alarm at the detector's installed location. Set the generator to represent a
4%/ft to 5%/ft obscuration as described in the Gemini 501 Manual and apply aerosol until the unit
alarms. If the Gemini unit is not available, cigarette, punk, or cotton wick are also acceptable
means of generating smoke to test this detector.
Aerosol testing is only a "go - no go" test and is not an acceptable means to determine the
smoke detector's sensitivity. See NFPA 72E.
REMEMBER:
Tester
Detector
Smoke
Detector
Point the Smoke Detector Tester tube at the detector and release a burst of aerosol by depressing
the nozzle for 1 second. Give the detector sufficient time to respond. This may be up to 20
seconds.
Elk Grove, IL 60007
107 Garlisch Drive
FAX (847) 427-8343
800-822-5676
HOME SAFEGUARD INDUSTRIES
INS NO.
PAGE
Rev.
08280990
14 of 14
08/13
Other manuals for EMR Series
2
This manual suits for next models
2
Table of contents
Other Dorma Door Opening System manuals

Dorma
Dorma 7300 SPA User manual

Dorma
Dorma 8600 EMR Series User manual

Dorma
Dorma 8956 T PKT 90 User manual

Dorma
Dorma 7414 ARNP User manual

Dorma
Dorma 8616 ARNP User manual

Dorma
Dorma ES 200 User manual

Dorma
Dorma 8916 PH User manual

Dorma
Dorma Manet User guide

Dorma
Dorma ED 100 Installation and operation manual

Dorma
Dorma TS 99 FLR Manual