DSC 3G2055 User manual

3G2055
HSPA/3G Wireless Alarm Communicator
SCW 3G Communicator – North America
TL2553G
Ethernet/Internet and HSPA/3G Dual-Path Alarm Communicator
SCW 3G / Ethernet Communicator - North America
Installation Manual
v5.0
Warning: This manual contains information on limitations regarding product use and function
and information on the limitations as to liability of the manufacturer.


3
Warning: Installer Please Read Carefully. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Mounting Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Communicator Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
UL/ULC Installation Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Communicator Frequency Bands for North America . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Hardware Compatibility. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Communicator Pre Installation Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
C24 Communications™ Account and SIM card Activation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Encryption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Communicator Configuration with SCW. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Installation Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Installing CAT 5 Cable (TL2553G only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Inserting/Removing the SIM Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Communicator Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Establishing a Communication Channel with the SCW Panel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
SMS Command and Control Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Label Programming for SMS Message . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Communicator Placement Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
General Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Keypad Data Display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Entering Data From Keypad. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Entering ASCII Characters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
ETHERNET/Cellular Programming Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
System Options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Programming Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Communications Reporting Codes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
System Test Options [026 - 029]. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Ethernet Receiver 1 Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Ethernet Receiver 2 Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
Ethernet Options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
Cellular Receiver 1 Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
Cellular Receiver 2 Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
Cellular Options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
Command and Control Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
SMS Command and Control Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
SMS Command and Control Response . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
Receiver Diagnostic Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37
System Information (Read Only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37
System Reset Defaults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
Communicator Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
Ethernet/Cellular Programming Worksheets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
End User Licence Agreement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
Table of Contents

4
WARNING: INSTALLER PLEASE READ CAREFULLY
Note to Installers
The Warnings on this page contain vital information.
As the only individual in contact with system users, it
is the installer’s responsibility to bring each item in
this Warning to the attention of all users of this
system.
System Failures
This system has been carefully designed to be as
effective as possible. There are circumstances,
however, involving fire, burglary, or other types of
emergencies where it may not provide protection.
Any alarm system of any type may be compromised
deliberately or may fail to operate as expected for a
variety of reasons. Some, but not all, of the reasons
may be:
Access by Intruders
Intruders may enter through an unprotected access
point, circumvent a sensing device, evade detection
by moving through an area of insufficient coverage,
disconnect a warning device, or interfere with or
prevent the proper operation of the system.
Component Failure
Although every effort has been made to make this
system as reliable as possible, the system may fail to
function as intended due to the failure of a
component.
Compromise of Radio Frequency (Wireless) Devices
Signals may not reach the receiver under all
circumstances which could include metal objects
placed on or near the radio path or deliberate jamming
or other inadvertent radio signal interference.
Criminal Knowledge
This system contains security features which were
known to be effective at the time of manufacture. It is
possible for persons with criminal intent to develop
techniques which reduce the effectiveness of these
features. It is important that your security system be
reviewed periodically to ensure that its features
remain effective and that it is updated or replaced if it
is found that it does not provide the protection
expected.
Failure of Replaceable Batteries
This system’s wireless transmitters have been
designed to provide several years of battery life under
normal conditions. The expected battery life is a
function of the device environment, usage, and type.
Ambient conditions such as high humidity, high or low
temperatures, or large temperature fluctuations may
reduce the expected battery life. While each
transmitting device has a low battery monitor which
identifies when the batteries need to be replaced, this
monitor may fail to operate as expected. Regular
testing and maintenance will keep the system in good
operating condition.
Inadequate Installation
A security system must be installed properly in order
to provide adequate protection. Every installation
should be evaluated by a security professional to
ensure that all access points and areas are covered.
Locks and latches on windows and doors must be
secure and operate as intended. Windows, doors,
walls, ceilings and other building materials must be of
sufficient strength and construction to provide the
level of protection expected. A reevaluation must be
done during and after any construction activity. An
evaluation by the fire and/or police department is
highly recommended if this service is available.
Inadequate Testing
Most problems that would prevent an alarm system
from operating as intended can be found by regular
testing and maintenance. The complete system
should be tested weekly and immediately after a
break-in, an attempted break-in, a fire, a storm, an
earthquake, an accident, or any kind of construction
activity inside or outside the premises. The testing
should include all sensing devices, keypads, consoles,
alarm indicating devices, and any other operational
devices that are part of the system.
Insufficient Time
There may be circumstances when the system will
operate as intended, yet the occupants will not be
protected from an emergency due to their inability to
respond to the warnings in a timely manner. If the
system is remotely monitored, the response may not
occur in time to protect the occupants or their
belongings.
Motion Detectors
Motion detectors can only detect motion within the
designated areas as shown in their respective
installation instructions. They cannot discriminate
between intruders and intended occupants. Motion
detectors do not provide volumetric area protection.
They have multiple beams of detection and motion
can only be detected in unobstructed areas covered
by these beams. They cannot detect motion which
occurs behind walls, ceilings, floor, closed doors,
glass partitions, glass doors or windows. Any type of
tampering whether intentional or unintentional such
as masking, painting, or spraying of any material on
the lenses, mirrors, windows or any other part of the
detection system will impair its proper operation.
Passive infrared motion detectors operate by sensing
changes in temperature. However their effectiveness
can be reduced when the ambient temperature rises
near or above body temperature or if there are
intentional or unintentional sources of heat in or near
the detection area. Some of these heat sources could

5
be heaters, radiators, stoves, barbeques, fireplaces,
sunlight, steam vents, lighting and so on.
Power Failure
Control units, intrusion detectors, smoke detectors
and many other security devices require an adequate
power supply for proper operation. If a device
operates from batteries, it is possible for the batteries
to fail. Even if the batteries have not failed, they must
be charged, in good condition and installed correctly.
If a device operates only by AC power, any
interruption, however brief, will render that device
inoperative while it does not have power. Power
interruptions of any length are often accompanied by
voltage fluctuations which may damage electronic
equipment such as a security system. After a power
interruption has occurred, immediately conduct a
complete system test to ensure that the system
operates as intended.
Security and Insurance
Regardless of its capabilities, an alarm system is not a
substitute for property or life insurance. An alarm
system also is not a substitute for property owners,
renters, or other occupants to act prudently to prevent
or minimize the harmful effects of an emergency
situation.
Smoke Detectors
Smoke detectors that are a part of this system may
not properly alert occupants of a fire for a number of
reasons, some of which follow. The smoke detectors
may have been improperly installed or positioned.
Smoke may not be able to reach the smoke
detectors, such as when the fire is in a chimney, walls
or roofs, or on the other side of closed doors. Smoke
detectors may not detect smoke from fires on
another level of the residence or building.
Every fire is different in the amount of smoke
produced and the rate of burning. Smoke detectors
cannot sense all types of fires equally well. Smoke
detectors may not provide timely warning of fires
caused by carelessness or safety hazards such as
smoking in bed, violent explosions, escaping gas,
improper storage of flammable materials, overloaded
electrical circuits, children playing with matches, or
arson.
Even if the smoke detector operates as intended,
there may be circumstances when there is
insufficient warning to allow all occupants to escape
in time to avoid injury or death.
Telephone Lines
If telephone lines are used to transmit alarms, they
may be out of service or busy for certain periods of
time. Also an intruder may cut the telephone line or
defeat its operation by more sophisticated means
which may be difficult to detect.
Warning Devices
Warning devices such as sirens, bells, horns, or
strobes may not warn people or waken someone
sleeping if there is an intervening wall or door. If
warning devices are located on a different level of the
residence or premise, then it is less likely that the
occupants will be alerted or awakened. Audible
warning devices may be interfered with by other
noise sources such as stereos, radios, televisions, air
conditioners, other appliances, or passing traffic.
Audible warning devices, however loud, may not be
heard by a hearing-impaired person.

6
MOUNTING CONSIDERATIONS
The Cellular/Ethernet Communicator is a fixed, wall-mounted unit and shall be
installed in the location specified in these instructions. The equipment enclosure
must be fully assembled and closed, with all the necessary screws/tabs and it must
be secured to a wall before operation.
Internal wiring must be routed in a manner that prevents:
• Excessive strain on wire and on terminal connections,
• Interference between power limited and non power limited wiring,
• Loosening of terminal connections, or
• Damage of conductor insulation.
Warning: Never install this equipment during a lightning storm!
The Installer must instruct the System user on each of the following items:
• This manual shall be used in conjunction with the Alarm controller manual; All the
safety instructions specified within that manual shall be observed.
• Do not attempt to service this product. Opening or removing covers may expose
the user to dangerous voltages or other risks.
• Any servicing shall be referred to trained service person only.
• Use authorized accessories only with this equipment.
Cellular Coverage for Alarm Communicator Operation
The HSPA/3G performance of the 3G2055 and TL2553G Alarm Communicators
depends greatly on Cellular network coverage. The SCW (with internal Alarm Com-
municator) should not be mounted in the final location without first ensuring that Cel-
lular radio reception is adequate for communication using the HSPA/3G paths.
Perform the “Communicator Placement Test” on page 15.
GENERAL INFORMATION
All versions of the HSPA/3G and Ethernet Alarm Communicator, operate on a HSPA/
3G network and are housed inside the Self Contained Wireless (SCW) 9055/9057.
The Communicators use an Internal Antenna only.
Each version of Alarm Communicators covered by this Installation Manual are
described below:
3G2055: A High Speed Packet Access/Global System for Mobile (HSPA/3G) wireless
Alarm Communicator that sends alarm communication to Sur-Gard System I-IP, II, III
(SG-DRL3IP), IV (SG-DRL4IP) and System 5 (DRL5-IP) central station receivers via a
HSPA/3G digital cellular network.
TL2553G: Is a dual-path Cellular/Ethernet Alarm Communicator that sends alarm
communication to Sur-Gard System I-IP, II, III, IV and 5 central station receivers
through Ethernet/Internet or a HSPA/3G digital cellular network.
The dual path Communicator can be used as either a backup or primary Communica-
tor. The Communicator supports Internet Protocol (IP) transmission of panel and
internal events over Ethernet/Internet and/or HSPA/3G.
NOTE: For North America the following model names are available: 3G2055-NA and
TL2553G-NA.
COMMUNICATOR TECHNICAL SPECIFICATIONS

7
CAUTION :
• Do not stay close to the equipment during device operation and to do not touch
any exposed wires and other conductive surfaces,
• Recycle the battery according to the local rules and regulations.
NOTE: Prior to installation of the 3G2055 or TL2553G Communicator, confirm with
your local carrier that the HSPA/3G network is available and active in the area where
the Communicator will be installed, and that the location provides a radio signal
strength that is adequate for uninterrupted service.
FEATURES
• 128-bit Advanced Encryption Standard (AES) encryption via HSPA/3G and
Ethernet/Internet.
• Activating, initializing and remote programming through C24 Communications.
• Back up or primary HSPA/3G/2G alarm communication.
• Does not require an external HSPA/3G/2G antenna.
• Ethernet LAN/WAN 10/100 BaseT (TL2553G only).
• Full event reporting to central station.
• Fully redundant Ethernet/Internet and HSPA/3G/2G Dual-path Alarm
Communication (TL2553G only).
• Individual Ethernet and/or HSPA/3G periodic test transmission.
• 2-way audio (listen-in feature) provided over Cellular.
• Integrated call routing.
• Remote Firmware upgrade capability of the Communicator and Panel Firmware via
Ethernet and/or HSPA/3G radio.
• Dual-Band Operation: 850 MHz, and 1900 MHz. (North America only)
• CID and SIA format reporting.
• Subscriber Identity Module (SIM) card included with Communicator. (North
America only)
• Supervision heartbeats via HSPA/3G/2G and/or Ethernet/Internet.
UL/ULC INSTALLATION REQUIREMENTS
• For ULC Residential fire and burglary applications the 3G2055/TL2553G can be
used as primary communication channel via either Cellular or Ethernet (as
applicable) or as a back-up in conjunction with the Digital Alarm Communicator
Transmitter (DACT). Test transmission every 24hours shall be enabled on each
channel.
• For UL Residential fire and burglary applications the 3G2055/TL2553G can be
used as primary communication channel via either Cellular or Ethernet, or as a
back-up in conjunction with the DACT. (30 day test transmission is required on each
channel).
COMMUNICATOR FREQUENCY BANDS FOR NORTH AMERICA
Table 1: 2G Frequency Bands
Transmit Direction Cellular 850 North America PCS 1900 North America
Transmit Frequency 824 MHz to 849 MHz 1850 MHz to 1910 MHz
Receive Frequency 869 MHz to 894 MHz 1930 MHz to 1990 MHz
Table 2: 3G Frequency Bands
Transmit Direction UMTS 850 North America,
International UMTS 1900 North America
Transmit Frequency 824 MHz to 849 MHz 1850 MHz to 1910 MHz
Receive Frequency 869 MHz to 894 MHz 1930 MHz to 1990 MHz

8
RATINGS
HARDWARE COMPATIBILITY
Products or components of products, which perform communications functions only
shall comply with the requirements applicable to communications equipment as
specified in UL60950 or CAN/CSA-C22.2 No. 60950-1, Information Technology Equip-
ment - Safety - Part 1: General Requirements. Where network interfaces are internal
to the control unit or receiver, compliance to CAN/CSA-C22.2 No. 60950-1 is ade-
quate. Such components include, but are not limited to: hubs; routers; NIDs; Third
party communications service providers; DSL modems; and Cable modems.
Table 3: Communicator Electrical Ratings
Model 3G2055
Cellular Only TL2553G
Ethernet and Cellular
Power Supply Ratings
Input Voltage 3.5 / 3.9 / 4.2 VDC (min / NOM / MAX) from the SCW panel
Current Consumption 75 mA 100 mA
Standby Current (@ 3.7V) 75 mA 100 mA
Alarm (Transmitting) Current) 400 mA @ 3.7V during transmission
Antenna Specifications
Dual band Antenna See Table 1 and Table 2
Environmental Specifications
Operating Temperature
0°C - 49°C (32°F- 120°F)
Humidity 5% ~ 85% relative humidity, non-condensing
Mechanical Specifications
Board Dimensions (mm) 109 x 110
Weight (grams) 60 65
Table 4: Compatibility
Communicator Receiver/
ControlPanel Description
3G2055
TL2553G
Receiver
SG System I-IP, v1.14+
SG System II, v2.11+
SG-DRL3-IP, v2.3+
SG-DRL4-IP, v1.2+
SG-DRL5-IP, V1.0+
Control Panel SCW9055/SCW9057 V1.00

9
C24 COMMUNICATIONS™1ACCOUNT AND SIM CARD ACTIVATION
(Before Installation)
Installation of the Communicator requires activation with Connect24 before opera-
tion. Dealer application forms and additional information on the Connect24 Voice
Response Unit (VRU) and graphical user interface (GUI) can be found at http://
www.Connect24.com or by telephone at: USA 1-888-251-7458 or CANADA 1-888-
955-5583.
IMPORTANT: Prior to installing a 3G2055 or TL2553G Communicator, contact your
monitoring station to determine if it is a master re-seller or visit http://www.Con-
nect24.com to become an authorized dealer. In either instance, you will require a Pro-
file Number, Installer ID Number, and an Installer Password. Perform the following
pre installation:
1. Retrieve the installer account and password from the master reseller, or from
Connect24 directly.
2. Connect your browser to the Connect 24 website at: http://
www.Connect24.com or use the mobile website m.connect24.com.
3. Log in to the Connect24 website using your installer account and password.
4. Perform the following steps in a Connect24 session to activate the SIM card and
initialize programming:
a. Navigate to the Initialize an account section.
b. Select Profile (This information will be provided by the master reseller or by
Connect24).
c. Select Product Module.
d. Enter the SIM card number.
e. Click Next then enter in all relevant information as required.
f. Confirm all information is entered correctly before submitting.
5. Repeat Step 4 to program another SIM card (i.e. another Subscriber), or log out
from Connect24.
6. When you are at the physical installation site, the Communicator will automatically
connect and download its programming from Connect24 once the unit is
initialized.
NOTE: Following initial installation, you can log in to the Connect24 website at any
time to re-configure the Communicator remotely, using the account created for this
installation. For more information, refer to the Connect24 website.
Before leaving the installation site, the Communicator TL2553G shall be
connected via an APPROVED (acceptable to the local authorities) Network
Interface Device (NID) (e.g., for UL Installations, U60950 listed NID). All wiring
shall be performed according to the local electrical codes.
ENCRYPTION
The Communicator uses 128 Bit AES Encryption. Encryption can only be enabled
from the monitoring station receiver. Each receiver can independently have encryp-
tion enabled or disabled. When encryption is enabled, the central station will config-
COMMUNICATOR PRE INSTALLATION CONFIGURATION
1. Connect24, DSC, and DLS IV are Registered Trademarks of Tyco International Ltd. and its respective Com-
panies. All Rights Reserved.

10
ure the device to encrypt communications the next time the Communicator module
performs a communication to that receiver.
NOTE: Packets will start being encrypted only after the next event is sent to that
receiver, or if the unit is restarted.
NOTE: The Alarm Communicator is installed in the SCW prior to shipment by Digital
Security Controls (DSC). The Factory Installation includes insertion of the SIM card.
The SCW should not be mounted in its final location without performing a
Communicator Test to ensure adequate HSPA/3G coverage for the 3G2055 and
TL2553G Alarm Communicators
INSTALLATION LOCATION
The Communicator shall be installed in an indoor location only.
This HSPA/3G/Ethernet Communicator shall be installed by Service Persons only.
(Service Person is defined as a person having appropriate technical training and expe-
rience necessary to be aware of hazards to which that person may be exposed in per-
forming a task and of measures to minimize the risks to that person or other
persons). The Communicator shall be installed and used within an environment that
provides the pollution degree max 2, over voltages category II, in non-hazardous,
indoor locations only. This manual shall be used with the Installation Manual of the
alarm control panel which is connected to the HSPA/3G/Ethernet Communicator. All
instructions specified within the control panel manual must be observed.
All the local rules imposed by local electrical codes shall be observed and respected
during installation.
COMMUNICATOR CONFIGURATION WITH SCW
+++
FIDB1
M1
C198
U15
C202
CON11
L2
C107
U4
U17
C110
L7
U16
T1
MH1
SH13
C193
C190
MH4
SH1
Q6
R63
R60
R68
R9
U11
U9
R5
Q5
C134
C13
5
C137
C115
C149
SH2
C138
R72
R1
R75
C1
L3
C12
6
R73
R61
C2
SH12
R56
L1
SH3
R2
XTL1
Q8
R109
C30
C207
SH4
C101
C44
U8
C48
U2
C50
R21
R85
R27
MH3
FIDB4
SH10
SH9
SH7
SH6
TH1
1
TH2
R32
C60 C61
U10
D5
U1
SH
8
TVS1 TVS3
U18
BR1
SH1
4
C205
SH15
SH17
XTL2
SH18
BR2
C192TVS10
C191
C148
R69
TVS9
U6
C139 C136
R62
R74
C99
R50
R104
C32
C93
C46
R64C92
R8
R28
R26
MH2
SH11
SH5
FIDB3
C62
SH16
C140 R111
R110 C206
INHIBIT
INHIBIT
AREA
ROUT
AREA
INHIBIT
ROUT
ROUT
AREA
LOCK LOCK
Figure 1: Communication Board Connection Points

11
INSTALLING CAT 5 CABLE (TL2553G ONLY)
A Category 5 (CAT 5) ethernet cable must
be run from a source with Ethernet/Inter-
net connectivity to the Communicator
module, inside the Self Contained Wire-
less Control Panel cabinet. The Communi-
cator end of the cable must have an RJ-45
plug, which connects to the Communica-
tor’s RJ-45 jack. All requirements for instal-
lation of CAT5 ethernet cable must be
observed for correct operation of the Com-
municator, including, but not limited to, the
following:
• Do NOT strip off cable sheathing more
than required for proper termination.
• Do NOT kink/knot cable.
• Do NOT crush cable with cable ties.
• Do NOT untwist CAT5 pairs more than
1.2cm (½”).
• Do NOT splice cable.
• Do NOT bend cable at right angles or make any other sharp bends.
NOTE: CAT5 specification requires that any cable bend must have a minimum 5 cm (2
in.) bend radius. Maximum length of CAT 5 cable is 100m (328 ft.).
NOTE: The Ethernet cable shall not be visible when the installation is complete
unless the install is a surface mount installation.
INSERTING/
REMOVING THE SIM
CARD
1. Remove the front
cover of the SCW
Control Panel to
access SIM card
holder.
2. Remove power from
the SCW and
disconnect the backup battery connections.
3. On the SIM card holder push gently to slide the cover towards OPEN as indicated
by the arrow on SIM holder. This will unlatch the SIM card holder on the side
furthest from edge of the Communicator. See Figure 1.
4. Lift up the SIM card holder from the side that is not hinged.
NOTE: The SIM card can be damaged by bending or scratching contacts. Use caution
when handling the SIM card.
5. Insert or remove the SIM card, noting the orientation of the notches on the SIM
card and the SIM card holder.
6. When inserting a SIM card, insert the card in the proper orientation and gently
push the SIM card holder down and slide the holder as indicated by the arrow on
SIM holder, to LOCK.
RJ-45 Connector
DG0009635
Figure 2: RJ-45 Pinout
SIM Card Pinouts
DG0009396
Figure 3: SIM Card Pinouts

12
7. Apply AC power to panel, and replace the panel cover.
NOTE: If two way audio is enabled you will NOT be able to swap the SIM card with
another card.
COMMUNICATOR RESET
The Communicator can be reset by cycling the power on the SCW.
ESTABLISHING ACOMMUNICATION CHANNEL WITH THE SCW PANEL.
The Communicator interfaces to the SCW through a keyed 16 pin Ribbon cable. See
Table 5 . The key prevents incorrect connection of the ribbon cable connector to the
SCW and Communicator. The pinout for the Ribbon cable is provided in the Table
below:
Establishing a communication channel between the Communicator and the SCW is
critical to ensuring the desired operation of the two units. The following steps must
be completed during the on-site installation. Program the following to ensure that the
Communicator and the panel will work together as intended.
Initial Programming of Communicator and SCW
1. Enter
[*][8][Installer Code] [Section Number]
for panel programming. Record any
values that are modified from their default, in the appropriate Programming
Worksheets.
NOTE: When programming Toggle Options, the toggle is ON when the number is
displayed and OFF when the number is not dis played. (e.g., [1 - - - 5 - - - ], Toggle
Options 1 and 5 are ON, all others are OFF).
2. Panel Section [167] Cellular/Ethernet Interface Communications ‘Wait for ACK’:
Default value is: 060 seconds.
3. When the communicator is installed with the SCW panel, 4 telephone numbers
are available to backup one another. You can set up these 4 telephone numbers to
perform in one of two ways: Backup dialling or Alternate dialling.
a. Backup dialling: each of the 4 telephone numbers will make 5 dialling attempts
in turn, before an FTC trouble is displayed on the keypad.
b. Alternate dialling: each telephone number makes 1 dialling attempt before
moving on to the next number, cycling through each of the 4 numbers for a total
of 5 times each. If all 4 numbers fail the 5 attempts, an FTC trouble is displayed
on the keypad.
4. Panel Sections [301], [302], [303], and [305] can be configured as Primary
communication paths.
a. Panel Sections [302], [303], and [305] may also be configured for backup or
redundant communications by using Panel Section(s) [383] or [351] - [376].
Refer to the SCW panel Installation Manual for more information.
Table 5: Communicator Ribbon cable to SCW
Pin # Signal Pin # Signal
1PC-LinkTX 2PC-LinkRX
3GND 4Vref
5Vref 6GND
7 AUD-OUT_N 8 AUD-OUT_P
9 AUD-IN_P 10 AUD-IN_N
11 GND 12 SI
13 GND 14 SO
15 GND 16 Wall Tamper

13
If a valid telephone number is programmed, communications will use Public Switched
Telephone Network (PSTN). Entering a 4 digit hexadecimal value for a telephone num-
ber will change the call routing to the Communicator, as determined by the number
programmed:
DCAAF:Internal (All Receivers). Signals will be routed depending on Section [851]
[006] programming.
DCBBF:Ethernet Receiver 1 (Primary). (Not available for 3G2055).
DCCCF:Ethernet Receiver 2 (Backup). (Not available for 3G2055).
DCDDF:Cellular Receiver 1 (Primary).
DCEEF:Cellular Receiver 2 (Backup).
NOTE: Add a single ‘F’ as a suffix to the 4 digit hex number to populate the unused
remainder of the 32 character field.
5. Panel Section [350]: If any of the phone numbers have been programmed as
DCAA, DCBB, DCCC, DCDD, or DCEE, panel Section [350] must be set to [04] if
SIA format or [03] if Contact ID (CID) format is used by control panel.
6. Panel Section [382]: Toggle Option [5], ‘GS/IP Module Enabled’, must be set to
ON.
7. Panel Section [401]: Toggle Option [1] must be set to ON in order to perform panel
DLS session through Cellular or Ethernet data channel.
8. Panel section [310], account code, auto syncs with the communicator account
code in section [021]. The panel account code ([*][8][installer code] [310]), will
overwrite the communicator account code section ([*][8][installer code] [850]
[021]) if programmed differently.
NOTE: Keep a record of the SIM card telephone number, it is required by users for
SMS Command and Control functions. (The number can be recorded in the
Programming Worksheets Section of this document, under Option [996]). Due to the
nature of the SIM card activation process with Cellular network carriers, it can take up
to 24 hours for SIM card activation to be complete.
SMS COMMAND AND CONTROL FUNCTIONS
SMS Command and Control is available on SCW9055/57 panels. Users can send
SMS text messages from their mobile phone to the GSM phone number assigned to
their system. Commands are only accepted from telephone numbers that have been
programmed in Sections [311]-[318]. The system will reject messages sent from tele-
phone numbers that are not on the programmed list.
When the received SMS text matches a valid Section message, the function is per-
formed on the control panel. Text messages are not case sensitive and extra spaces
are ignored. A User Access Code may be required for some SMS messages.
The SMS Message format is in 3 parts: Command, Partition Label (or only the parti-
tion number), and Access Code.
If an Access Code is included in the message, it is sent to the control panel for valida-
tion, along with the requested function.
If the panel is configured to require an Access Code and the code is not sent (or
invalid) the panel will fail the function (unsuccessful).
If the panel fails the function, an SMS response message is sent to the user. The
SMS response will echo the command sensat, followed by the label “unsuccessful”.
(e.g., “night arm partition 2 1234 unsuccessful”).
The partition label or partition number may be excluded from the SMS request in a
single partition system (e.g., disarm 9123).

14
NOTE: The GSM phone number can be viewed in Section [851] [996], and/or [851]
[229] or by entering *6, then scrolling down to “SMS Programming” and scrolling
down to “Cellular phone No”.
LABEL PROGRAMMING for SMS MESSAGE
Programmable Labels can not be modified in Connect24, use DLS IV for label pro-
gramming only, if labels need to be modified. Before initiating remote programming,
record your network’s Public IP Address and port for incoming DLS IV connections.
1. Run the DLS IV software on your computer. DLS IV will connect to the unit, using
the Public IP address, and make an Ethernet connection. If the Ethernet connection
fails, DLS IV will report an error and prompt you to connect using Cellular.
NOTE: If required, download the DLS IV software from DSC: http://www.dsc.com.
If you select Cellular connection, DLS will request Connect24 to send an outgoing
SMS message to the unit.
2. Connect24 will confirm that the account has DLS service and will provide the
Public IP address and port number of the DLS server in an SMS message.
3. SMS message will establish a connection to your computer’s DLS IV software (to
change programming labels only).
4. Create an account for the panel/Communicator, select the Communicator type
(e.g., SMS - TL2553G) and enter all relevant information in SMS section.
NOTE: The Cellular telephone number will also be required by the user, to send SMS
Command and Control messages to their system.
5. Program the account information, then click Global Download and choose SMS
as the Connection Type. Click OK.
6. The download path configured in Programming Section [005] Toggle Option[4]
determines the Cellular or Ethernet path to be used.
COMMUNICATOR PLACEMENT TEST
(3G2055/TL2553G only)
1. Using the keypad enter the installer mode:
[*][8]
[installer code] [850].
2. View and record the number of bars showing on the SCW LCD.
3. Compare with the number of bars indicated in the “CSQ Levels” column shown in
Table 6 .
4. If 3 or more bars are shown, the location is GOOD and no further action is
required.
5. If the location is BAD, move the SCW to various suitable locations until 3 or more
bars are obtained.
NOTE: The communicator is capable of indicating signal strength even without an
active SIM, but signal indication may take up to 1-2 minutes.
Table 6: Communicator CSQ Levels
Signal
Strength CSQ Level Signal
Level dBm Installer Action
No Signal 0 -108.8 Check if Cellular coverage is active in your area.
1 Bar 1 to 4 -108d to -103 Location is BAD. Not suitable for Cellular operation.
2 Bars 5 to 6 -102 to -99
3 Bars 7 to 10 -98d to -91
Location is GOOD.4 Bars 11 to 13 -90 to -85
5 Bars 14 and higher -84 and higher

15
i Domain Name Service (DNS) programming is not permitted in UL/ULC listed
systems.
KEYPAD DATA DISPLAY
•Section-Toggle Options: The number is displayed when Toggle is ON. The
number is not displayed when Toggle is OFF. (e.g., Toggle Options displays: “[
--
3
-
-
6
--
]”. Options 3and 6are ON, all others are OFF). Pressing keys 1 through 8 will
alternately turn the Toggle ON and OFF.
•HEX/Decimal Data: Values that are provided with two defaults, separated by a /
character, use the format: hexadecimal followed by decimal equivalent (e.g.,
Default [0BF5/3061]). Hexadecimal numbers are shown, with all leading zeroes, to
the full field length defined for the number.
ENTERING DATA FROM KEYPAD
To enter data at the keypad, press the number key, from the table below, to select the
character that you want. Pressing the number key repeatedly will scroll through the
characters available for that key. Press the [*] key and use
[<] [>] keys to scroll to one
of the following selections: (Press [*] to select the Option.)
•ASCII Entry. Use this mode to enter ASCII characters from the keypad.
•Clear to End. This selection will clear the remainder of the display.
•Clear Display.This selection will completely erase all entries on the display.
•Change Case. Toggles between upper/lower case depending on current selection.
NOTE: The “0” on the keypad is used to delete characters.
ENTERING ASCII CHARACTERS
To enter American Standard Code for Information Interchange (ASCII) characters at
the keypad, perform the following:
1. Press [*] and use [<] [>] keys to scroll to “ASCII Entry”.
2. Press [*] to select ASCII entry mode.
3. Use the
[<] [>] keys to scroll to display the ASCII character you want to use and
press [*] to accept.
4. Press [*] to exit ASCII character entry mode and return to normal entry.
NOTE: Authorized access to Connect24 (3G2055/TL2553G) is required to modify any
Ethernet/Cellular Programming Section. Specific panel sections must be configured
for proper operation of the Communicator with the panel.
GENERAL INFORMATION
Table 7: Data Entry at Keypad
Key Value Key Value Ke
yValue
1 1-A-B-C 4 4-J-K-L 7 7-S-T-U
2 2-D-E-F 5 5-M-N-O 8 8-V-W-X
3 3-G-H-I 6 6-P-Q-R 9 9-Y-Z-0

16
The Programming Sections described in this document can be viewed at the SCW
LCD. To start programming enter: [*][8][installer code] [851][# # # ], Where # # # is
the 3 digit Section number referenced in this section. The Programming Worksheets
at the end of this document can be used to record the new values when program-
ming changes have been made from the default values.
Programming Sections are accessed through Connect24. Installers may review/
record programming Options at the panel.
NOTE: Ethernet/Cellular Programming Sections accessed through the panel are for
display purposes only. Configuration changes must be done using Connect24.
SYSTEM OPTIONS
[001] Ethernet IP Address
Default (000.000.000.000)
Enter the IP address of the Communicator. Ensure that the IP address is unique to
your Communicator on the local network. Format is 4 fields, each field is a 3 digit dec-
imal number. Valid range: 000-255. If an IP address is programmed in this Section,
the unit will operate with Static IP (DHCP disabled). Sections [002] and [003] must
also be programmed when using Static IP addresses.
NOTE: Default for this Section is Dynamic Host Configuration Protocol (DHCP)
enabled. When enabled, the DHCP Server will set values for: IP Address
[001], Subnet Mask [002], and Gateway [003]. Programming an IP address in
this Section will disable DHCP (Static IP).
[002] Ethernet IP Subnet Mask
Default (255.255.255.000)
Enter the Ethernet IP Subnet Mask of the Communicator. Format is 4 fields, each
field is 3 digits. Valid range: 000-255.
NOTE: If DHCP is enabled, the DHCP Server will assign the subnet mask for this
Section and the programmed value will be ignored.
[003] Ethernet Gateway IP Address
Default (000.000.000.000)
Enter the Ethernet Gateway IP address of the Communicator. The gateway IP
address is required when a router is used on the local network to reach the
destination IP address specified in Section [001]. Format is 4 fields, each field is a 3
digit decimal number. Valid range: 000-255.
NOTE: If DHCP is enabled, the DHCP Server will assign the Gateway IP address for
this Section and the programmed value will be ignored.
[004] Receiver Supervision Interval
Default (0087/135)
When receiver supervision is enabled (ON) in Section [005] Toggle Option [3], the unit
sends heartbeats to Ethernet Receiver 1 or Cellular Receiver 1 to test the
communications path. Use this Section to set the interval time (in seconds) when
heartbeats will be sent to the receivers. Valid range 000A-FFFF seconds. If the
programmed value is less than (000A/10) seconds, supervision is disabled.
•Receiver Window: This is the supervision timeout that must be configured at the
central station receiver.
•Recommended Values: This is the recommended heartbeat interval that should
be programmed into the Communicator.
• For ULC installations, the Daily test transmission must be enabled over each
available communication channel Sections [125] and [225]. When programming
with Connect24, the recommended intervals will be programmed automatically
when the required window is selected.
ETHERNET/CELLULAR PROGRAMMING OPTIONS

17
[005] System Toggle Options
[1] Ethernet Receiver 1 Supervised
Default (OFF)
(TL2553G only).
ON: Ethernet Receiver 1 will be supervised and heartbeats will be sent to Ethernet
Receiver 1 based on the supervision interval programmed in Section [004].
OFF: Ethernet Receiver 1 will not be supervised. When disabled, heartbeat 1 is sent
to the Ethernet receiver once every hour, regardless of supervision type (heartbeat 1
or 2). The heartbeat is resent every 5 seconds until ACK. If no event or heartbeat ACK
is received after (Receiver Supervision Interval + 75 seconds), Supervisory trouble is
indicated.
NOTE: Ethernet Receiver 2 can not be supervised.
[2] Cellular Receiver 1 Supervised
Default (OFF)
ON: Cellular Receiver 1 will be supervised and heartbeats will be sent to Cellular
Receiver 1 based on the supervision interval programmed in Section [004]. If ACK to
heartbeat is not received, it is retransmitted every 5 seconds. Failure to ACK 2
consecutive heartbeats will reset the radio.
OFF: Cellular Receiver 1 will not be supervised. When disabled, heartbeat is not sent
to the receiver. Supervisory trouble is indicated.
NOTE: Cellular Receiver 2 can not be supervised.
[3] Supervision Type
Default (OFF)
ON: Heartbeat 1 (Commercial Supervision). This supervision type is suitable for
applications where swap detection is required on the supervisory packet.
OFF: Heartbeat 2 (Residential Supervision). This supervision type is suitable for
applications where supervision of the communication path to the receiver is required.
(no swap detection).
NOTE: Commercial supervision is more data intensive than residential supervision
and should only be used when required to meet the approval for the installation.
[4] Primary Path
Default (OFF - TL2553G) (ON - 3G2055)
ON: Cellular channel is the primary path. Ethernet channel is the secondary path, if it
exists.
OFF: Ethernet channel is the primary path in a dual Communicator. Cellular channel is
the secondary path.
[5] Redundant Communications
Default (OFF) (TL2553G only)
ON: Events will be communicated to Ethernet Receiver 1 and Cellular Receiver 1 at
the same time. Events will be communicated to Ethernet Receiver 2 and Cellular
Receiver 2 at the same time. As long as the event is successfully communicated to 1
of the 2 paths (Ethernet or Cellular) the Communicator will move on to the next
event.
NOTE: Do not configure Ethernet Receiver 1 and Cellular Receiver 1 to communicate
using a common receiver configuration (i.e., identical Receiver IP address and
Receiver Remote Port). OFF: Events will be communicated to the receivers
individually.Toggle should be OFF when guaranteed message delivery to both receivers is
required.
[6] Remote Firmware Upgrade
Default (ON)
ON: The Communicator module firmware can be remotely upgraded using the
Ethernet/Cellular paths.
OFF: The Communicator module firmware can not be remotely upgraded. Local
firmware upgrade is still possible.

18
[7] Alternate Test Transmissions
Default (OFF).
ON: When the periodic test transmission interval occurs, the test transmission will
alternate between being sent to the primary and secondary receivers with each test
transmission interval.
OFF: When the periodic test transmission interval occurs, the test transmission will
be sent to the programmed receivers, based on the settings of the periodic test
transmission reporting codes.
[8] Cellular Low Signal Trouble.
Default (OFF)
This option masks the Low Signal trouble from the Cellular trouble event.
ON: A Cellular Trouble event is transmitted to receiver when the radio signal level falls
below threshold level (average CSQ level is 4 or less).
OFF: A Cellular Trouble event is not transmitted to receiver when the radio signal
level falls below threshold level (average CSQ level is 4 or less).
[006] System Toggle Options 2
[1] Ethernet 1 Receiver Enabled.
Default (ON) (OFF for 3G2055).
ON: Ethernet Receiver 1 is enabled.
OFF: Ethernet Receiver 1 is disabled.
[2] Ethernet 2 Receiver Enabled.
Default (ON) (OFF for 3G2055).
ON: Ethernet Receiver 2 is enabled.
OFF: Ethernet Receiver 2 is disabled.
[3] Reserved. ( ).
[4] Cellular 1 Receiver Enabled.
Default (ON).
ON: Cellular Receiver 1 is enabled.
OFF: Cellular Receiver 1 is disabled.
[5] Cellular 2 Receiver Enabled.
Default (ON).
ON: Cellular Receiver 2 is enabled.
OFF: Cellular Receiver 2 is disabled.
[6] Reserved ( ).
[7] DLS Over Cellular.
Default (ON).
NOTE: Program this toggle as OFF if you want to completely disable DLS from using
the Cellular path.
ON: DLS is enabled on the Cellular path.
OFF: DLS is disabled on the Cellular path.
NOTE: If this Toggle is OFF, DLS sessions will occur on the Ethernet path only,
regardless of Primary Path set in Section [005] Toggle Option [4]. If it is ON then the
Communicator will connect to the Primary path first for DLS and if the session fails,
the Secondary path will be used.
[8] Trouble Suppression
Default (OFF)
ON: GSM, Ethernet and Receiver Supervision Trouble and Restore conditions will be
delayed for the time period programmed in section [226]. After the delay expires the
trouble conditions will be indicated and communicated.
OFF: GSM, Ethernet and Receiver Supervision Troubles will be immediately indicated
and communicated.

19
[007] DNS Server IP 1
Default (000.000.000.000)
iProgramming this Section is not permitted on a UL/ULC listed system.
Enter the IP address for DNS Server 1. Format is 4 fields, each field is a 3 digit
decimal. Valid range: 000-255.
NOTE: If no value is programmed and DHCP is used, the DHCP Server will configure
the address. If an address is programmed and DHCP is used, the address that you
program will be used instead of the DHCP address.
[008] DNS Server IP 2
iProgramming this Section is not permitted on a UL/ULC listed system.
Default (000.000.000.000)
Enter the IP address for DNS Server 2. Format is 4 fields, each field is a 3 digit
decimal. Valid range: 000-255.
NOTE: If no value is programmed and DHCP is used, the DHCP Server will assign this
value. If an address is programmed and DHCP is used, the address that you program
will be used instead of the DHCP address.
PROGRAMMING OPTIONS
[010] System Toggle Option
Default (Disable)
[1] This bit is used to enable/disable two way audio over 3G.
[011] Installer Code
Default (CAFE)
Program your installer code for this Communicator module. The installer code will be
required when programming the Communicator module. Valid range: 0000 - FFFF.
[012] DLS Incoming Port
Default (0BF6/3062)
The DLS Incoming Local Port (listening port) is the port DLS IV will use when con-
necting to the Communicator. If a router or gateway is used, it must be programmed
with a Transmission Control Protocol (TCP) port forward for this port to the Communi-
cator module IP address. Valid range: 0000 - FFFF.
[013] DLS Outgoing Port
Default (0BFA/3066)
The DLS Outgoing Port is used for outgoing session to DLS IV after an SMS request
has been sent to the Communicator. Use this Section to set the value of the local out-
going port. The value must be changed if the Communicator is located behind a fire-
wall and must be assigned a particular port number, as determined by your network
administrator. In most cases, changing the default value or configuring your firewall
with this port is not required.
Valid range: 0000-FFFF.
NOTE: If Section [006] Toggle Option [7] is ON, DLS will use the Primary path for
session. If Section [006] Toggle Option [7] is OFF DLS will use the Ethernet
path, if available.
[020] Time Zone
Default (00)
Use Column 2 (Offset Hours) to find your local Time Zone. Record the two digit HEX
value from Column 1 (HEX Value) on the same row. Program this HEX value for your
Time Zone. Valid range is 00 - FF.

20
Table 8: World Wide Time Zones
HEX
Value
Offset
Hours
Std
Abbrev Location
01 -12 BIT Baker Island Time
05 -11 NUT Niue Time
SST Somoa Standard Time
09 -10
HAST Hawaii-Aleutian Standard Time
THAT Tahiti Time
TKT Tokelau Time
CKT Cook Island Time
0B -9,5 MIT Marquesas Island Time
0D -9 AKST Alaska Standard Time
GIT Gambier Island Time
11 -8
PST Pacific Standard Time
PST Pitcarirn Standard Time
CIST Clipperton Island Standard Time
15 -7 MST Mountain Standard Time
19 -6
CST Central Standard Time
GALT Galapagos Time
PIT Peter Island Time
EAST Easter Island Standard Time
1D -5
EST Eastern Standard Time
COT Colombia Time
ECT Ecuador Time
PET Peru Time
ACT Acre Time
1F -4,5 VST Venezuela Standard Time
21 -4
AST Atlantic Standard Time
CLST Chile Standard Time
BWST Brazil Western Standard Time
SLT San Luis Time
PYT Paraguay Time
JFST Juan Fernandez Island Standard Time
GYT Guyana Time
FKST Falkland Island Standard Time
BOT Bolivia Time
23 -3,5 NST Newfoundland Standard Time
25 -3
CGT Central Greenland Time
ART Argentina Time
BRT Brazilia Time
UYT Uruguay Standard Time
SRT Suriname Time
ROTT Rothera Time
PMST St. Pierre & Miquelon Standard Time
GFT French Guiana Time
29 -2 GST South Georgia and the South
Sandwich Islands
BEST Brazil Eastern Standard Time
Other manuals for 3G2055
1
This manual suits for next models
1
Table of contents
Other DSC Security System manuals

DSC
DSC Communique VPM5580TC User manual

DSC
DSC PC5OO User manual

DSC
DSC PowerSeries PC4020 User manual

DSC
DSC Envoy NT9010 v1.0 Owner's manual

DSC
DSC PC1832 series Owner's manual

DSC
DSC iOtega User manual

DSC
DSC TL260GS User manual

DSC
DSC WLS920 User manual

DSC
DSC Power 832 User manual

DSC
DSC MAXSYS PC4020 User guide