DSC neo HS2032 User manual

Quick Setup
1Plan Plan the installation including all alarm detection devices,
zone expanders, keypads and other required modules.
2Mount Decide on a location for the alarm panel and secure it to the
wall using suitable mounting hardware.
3Wire Complete all wiring including modules, zones, bells/sirens,
telephone line connections and ground connections. Record
module serial numbers on page 19.
4Power Connect the battery and power up the system. The battery
must be connected.
5Enroll
First
Keypad
Hardwired: Wire the keypad to the Corbus, power up the
alarm panel then press any button on the keypad. Wireless:
Wire the HSM2Host to the Corbus, then power up the alarm
panel and a wireless keypad. Press any button on the keypad to
enroll it. The HSM2Host is then enrolled on the alarm panel.
Alternately, enroll an RF keypad.
6Enroll
modules
[*][8][Installer Code][902] subsection [000]. Press [*] to
begin auto-enrollment. Module slots are automatically
assigned. Use scroll keys to view slots. Change slot by typing a
2-digit number.
7Enroll
wireless
devices
[*][8][Installer Code][804] subsection [000]. Note: An
HSM2HOST or RF keypad must be enrolled first.
8Program Basic programming: [*][8][installer code] [001]/[002]> Zone
Type/Zone Attribute [005]>[001] Partition 1 Timers: – Entry
Delay 1 – Entry Delay 2 – Exit Delay [301]>[001] Phone #1
[310]>[000] System Account Code.
9Test Test the panel completely to ensure that all features and
functions operate as programmed. – [901] Walk Test – [904]
[000] Wireless Placement Test.
Compatible Devices
Throughout this document, x in the model number represents the
operating frequency of the device as follows: 9 (912-919 MHz), 8
(868MHz), 4 (433MHz).
Table 1-1 Compatible Devices
Modules
Wireless keypads: HS2LCDWFx
HS2LCDWFPx
HS2LCDWFPVx
Hardwired keypads with 2-way wireless
integration module:
HS2LCDRFx
HS2LCDRFPx
HS2ICNRFx
HS2ICNRFPx
Hardwired keypads: HS2LCD
HS2LCDP
HS2ICN
HS2ICNP
HS2LED
Touchscreen Keypad HS2TCHP
2-way wireless integration module: HSM2HOSTx
8-zone expander: HSM2108
8-output expander: HSM2208
Power supply: HSM2300
4 high current output expander: HSM2204
Alternate communicator: 3G2080E
3G2080RE
TL280E
TL280RE
TL2803GE
TL2803GRE
PCL-422
Hardwired Devices
2-wire smoke detectors: FSA-210x
FSA-210xT
FSA-210xS
FSA-210xST
FSA-210xLST
FSA-210xR
FSA-210xRT
FSA-210xRS
FSA-210xRST
FSA-210xLRST
y= A, B, or C
A: ULC listed models
B: UL listed models
C: European and Australian models
4-wire smoke detectors: FSA-410x
FSA-410xT
FSA-410xS
FSA-410xST
FSA-410xLST
FSA-410xR
FSA-410xRT
FSA-410xRS
FSA-410xRST
FSA-410xLRST
y= A, B, or C
A: ULC listed models
B: UL listed models
C: European and Australian models
CO detectors: CO-12/24
12-24SIR
FW-CO12
FW-CO1224
CO1224
Wireless Devices
Wireless PG smoke detectors PGx926
Wireless PG smoke and heat detector PGx916
Wireless PG CO detector: PGx913
Wireless PG PIR motion detectors: PGx904(P)
Wireless PG PIR + camera motion detector PGx934(P)
Wireless PG curtain motion detector PGx924
Wireless PG dual tech motion detector PGx984(P)
Wireless PG mirror motion detector PGx974(P)
Wireless PG outdoor motion detector PGx994
Wireless PG glass break detector: PGx912, PGx922
Wireless PG shock detector: PGx935
Wireless PG flood detector: PGx985
Wireless PG temperature detector (indoor use): PGx905
Outdoor temperature probe (requires PGx905) PGTEMP-PROBE
Wireless PG keys: PGx939
PGx929
Wireless PG panic key PGx938
Wireless PG 2-button key PGx949
Wireless PG sirens: PGx901
PGx911
Wireless PG repeater: PGx920
Wireless PG door/window contacts: PGx975
Wireless PG door/window contact w/ AUX PGx945
Central Station Receivers
SG-System I, II, III, IV, 5
Enclosures
PC5003C, PC4050CR, PC4050CAR, CMC-1, PC4051C. Other enclosures are available to suit a variety
of system configurations.
WARNING: This manual contains information on limitations regarding product use and function and information on
the limitations as to liability of the manufacturer. The entire manual should be carefully read.
To download the full installation and user manuals and register your product, please visit:
www.DSC.com/m/29009812 or scan the QR code to the right.
PowerSeries Neo Alarm Control Installation Guide

PowerSeries Neo Installation Guide
Safety Instructions for Service Personnel
Warning: When using equipment connected to the telephone network, always follow the
basic safety instructions provided with this product. Save these instructions for future
reference. Inform the end-user of the safety precautions that must be observed when
operating this equipment.
Before Installing The Equipment
Ensure your package includes the following items:
lInstallation and User manuals, including the SAFETY INSTRUCTIONS.
READ and SAVE these instructions!
Follow all WARNINGS AND INSTRUCTIONS specified within this
document and/or on the equipment.
lHS2016/HS2016/2032/2064/2128 alarm controller
lPower Supply, direct plug-in
lMounting hardware
Selecting A Suitable Location For The Alarm Controller
Use the following list as a guide to find a suitable location to install this equipment:
lLocate near a telephone socket and power outlet.
lSelect a location free from vibration and shock.
lPlace alarm controller on a flat, stable surface and follow the installation
instructions.
Do NOT locate this product where people may walk on the secondary circuit
cable(s).
Do NOT connect alarm controller to electrical the same circuit as large
appliances.
Do NOT select a location that exposes your alarm controller to direct
sunlight, excessive heat, moisture, vapors, chemicals or dust.
Do NOT install this equipment near water. (e.g., bath tub, kitchen/laundry
sink, wet basement, near a swimming pool).
Do NOT install this equipment and accessories in areas where risk of
explosion exists.
Do NOT connect this equipment to electrical outlets controlled by wall
switches or automatic timers.
AVOID interference sources.
AVOID installing equipment near heaters, air conditioners, ventilators, and
refrigerators.
AVOID locating equipment close to or on top of large metal objects (e.g., wall
studs).
See "Locating Detectors and Escape Plan" on page 20 for information on locating smoke
and CO detectors.
SAFETY Precautions Required During Installation
lNEVER install this equipment and/or telephone wiring during a lightning
storm.
lNEVER touch uninsulated telephone wires or terminals unless the telephone
line has been disconnected at the network interface.
lPosition cables so that accidents can not occur. Connected cables must NOT
be subject to excessive mechanical strain.
lUse only the power supply provided with this equipment. Use of unau-
thorized power supplies may cause damage.
lFor direct plug-in versions, use the transformer supplied with the device.
WARNING: THIS EQUIPMENT HAS NO MAINS ON/OFF SWITCH. THE PLUG OF
THE DIRECT PLUG-IN POWER SUPPLY IS INTENDED TO SERVE AS THE
DISCONNECTING DEVICE IF THE EQUIPMENT MUST BE QUICKLY
DISCONNECTED. IT IS IMPERATIVE THAT ACCESS TO THE MAINS PLUG AND
ASSOCIATED MAINS SOCKET/OUTLET IS NEVER OBSTRUCTED.
IMPORTANT NOTE FORINTERNATIONALMARKET (EU,
AUS, NZ)!
This equipment is stationary-fixed and must be installed by Service
Persons only (Service Person is defined as a person having the appropriate
technical training and experience necessary to be aware of hazards to
which that person may be exposed in performing a task and of measures to
minimize the risks to that person or other persons). It must be installed and
used within an environment that provides the pollution degree max 2, over
voltages category II, in non-hazardous, indoor locations only. When using
equipment connected to the mains and/or to the telecommunication
network, there are basic safety instructions that should always be
followed. Refer to the safety instructions provided with this product and
save them for future reference. To reduce the risk of fire, electric shock
and/or injury, observe the following: Do not attempt to service this product
yourself. Opening or removing the cover may expose you to dangerous
voltage or other risk. Refer servicing to qualified service persons. Never
open the device yourself. Use authorized accessories only with this
equipment. DO NOT leave and/or deposit ANY object on the top of the
cabinet of this equipment! The cabinet as it is installed on the wall is not
designed to support any supplementary weight! Do not spill any liquids on
the cabinet. Do not touch the equipment and its connected cables during an
electrical storm; there may be a risk of electric shock. Never touch
uninsulated wires or terminals unless the equipment has been disconnected
from the mains supply and from the telecommunication network! Ensure
that cables are positioned so that accidents cannot occur. Connected cables
must not be subject to excessive mechanical strain. Do not spill any type of
liquid on the equipment. Do not use the Alarm system to report a gas leak
if the system is near a leak. Do not subject the connected cables to an
excessive mechanical strain. These safety instructions should not prevent
you from contacting the distributor and/or the manufacturer to obtain any
further clarification and/or answers to your concerns.
Installation
Mounting the Enclosure
Locate the panel in a dry area, preferably near an unswitched AC power
source and the incoming telephone line. Complete all wiring before
applying AC or connecting the battery.
Terminal Descriptions
The following terminals are available on the PowerSeries Neo alarm
controller.
Terminal Description
BAT+,
BAT-
Battery terminals. Use to provide backup power and additional current
when system demands exceed the power output of the transformer, such
as when the system is in alarm.
Do not connect the battery until all other wiring is complete.
AC Power terminals.
Connect the battery before connecting the AC. Do not connect the battery
or transformer until all other wiring is complete.
AUX+,
AUX-
Auxiliary terminals. Use to power modules, detectors, relays, LEDs, etc.
(700mA MAX). Connect the positive side of device to AUX+, the
negative side to AUX-.
BELL+,
BELL-
Bell/Siren power (700mA MAX). Connect the positive side of any alarm
warning device to BELL+, the negative side to BELL-.
RED, BLK,
YEL, GRN
Corbus terminals. Use to provide communication between the alarm
controller and connected modules. Each module has four Corbus
terminals that must be connected to the Corbus.
PGM1 to
PGM4
Programmable output terminals. Use to activate devices such as LEDs.
(PGM1, PGM3, and PGM4: 50mA PGM2: 300mA or can be configured
as an input)
Z1 to Z8
COM
Zone input terminals. Ideally, each zone should have one detection
device; however, multiple detection devices can be wired to the same
zone.
EGND Earth ground connection.
TIP, RING,
T-1, R-1
Telephone line terminals.
PCLINK_1 DLS/SA
PCLINK_2 DLS/SA, Alternate Communicator
Corbus Wiring
The RED and BLK Corbus terminals are used to provide power while
YEL and GRN are used for data communications. The 4 Corbus terminals
of the alarm controller must be connected to the 4 Corbus terminals or
wires of each module.
The following conditions apply:
lCorbus should be run with minimum 22 gauge quad, two pair
twisted preferred.
- 2 -

PowerSeries Neo Installation Guide
lThe modules can be home run to the panel, connected in series or
can be T-tapped.
lDo not use shielded wire for Corbus wiring.
Note: Any module can be connected anywhere along the Corbus. Separate
wire runs for keypads, zone expanders etc. are not necessary.
Note: No module can be more than 1,000'/305m (in wire length) from the
panel. Do not use shielded wire for Corbus wiring.
Figure 1-1 Corbus Wiring
Module (A) is wired correctly as it is within 1,000'/305m of the panel, in
wire distance. Module (B) is wired correctly as it is within 1,000'/305m of
the panel, in wire distance. Module (C) is NOT wired correctly as it is
farther than 1,000'/305m from the panel.
Current Ratings
In order for the system to operate properly, the power output of the alarm
controller and power supply modules cannot be exceeded. Use the
following data to ensure that the available current is not exceeded.
Table 1-1 System Output Ratings
Device Output Rating (12VDC)
HS2016
HS2032
HS2064
HS2064 E
HS2128
HS2128 E
AUX: 700mA. Subtract the listed rating for each keypad, expansion
module and accessory connected to AUX or Corbus. At least
100mA must be reserved for the Corbus.
BELL: 700mA. Continuous rating. 2.0A. short term. Available only
with standby battery connected. Not for UL/ULC or EN cer-
tified applications.
HSM2208 AUX: 250mA. Continuous rating. Subtract for each device con-
nected. Subtract the total load on this terminal from the alarm
panel AUX/Corbus output.
HSM2108 AUX: 100mA. Subtract for each device connected. Subtract the total
load on this terminal from the panel AUX/Corbus output.
Alarm Control Panel
AUX - 700mA available for devices connected to the AUX and PGM
terminals, and modules connected to Corbus terminals. At least 100mA
must be reserved for the Corbus.
Alarm Controller Current Calculation
Panel Calculation
Maximum (Standby or Alarm)
AUX (700mA max. including PGMs 1-4)
Corbus (700mA max.)***
PCLink+ (Alt. Com.:125mA)
Total (must not exceed 700mA)
***See Corbus Current Calculation Chart.
For UL, ULC and Commercial Listed applications, the total standby and
alarmcurrent cannot exceed 700mA.
Table 1-2 Corbus Current Calculation Chart
Item Current
(mA)
x Quantity Total
(mA)
HS2016/HS2032/HS2064/HS2064
E/HS2128/HS2128 E
85 x 1 85
HS2LCD 105 x
HS2ICN 105 x
HS2LED 105 x
HS2LCDP 105 x
HS2ICNP 105 x
HS2LCDRF 105 x
HS2ICNRF 105 x
HS2ICNRFP 105 x
HS2TCHP 160 x
Current required for connected devices =
HSM2108* 30 x
AUXoutput current of HSM2108
HSM2208* 40 x
AUXoutput current of HSM2208
HSM2300/2204* 35 x
HSM2HOSTx 35 x
HSM2955** x
3G2080(R)/TL2803G(R)/TL280(R) 125
(PCLINK)
x
Total Corbus Current =
*These units draw current from the Corbus to power devices external to
the module. This current must be added to the total Corbus current. See
manufacturer's specifications for the current draw of each device.
** For HSM2955 current draw refer to HSM2955 installation manual.
- 3 -

PowerSeries Neo Installation Guide
Capacitance Limits
An increase in capacitance on the Corbus affects data transmission and
causes the system to slow down. Capacitance increases for every foot of
wire added to the Corbus. The capacitance rating of the wire used will
determine the maximum length of the Corbus.
Table 1-3 Wire Capacitance
Wire Capacitance per 1000’
(300m)
Total Corbus Wire Length
15nF 5300’/1616m
20nF 4000’/1220m
25nF 3200’/976m
30nF 2666’/810m
35nF 2280’/693m
40nF 2000’/608m
AC (International Installations)
Primary: 220V-240Vac, 50/60Hz, 200mA
Secondary: 16.5VAC/40VA
Warning: Do not connect the battery or transformer until all other
wiring is complete.
Batteries
Connect the RED battery lead to the positive battery terminal and the
BLACK battery lead to the negative battery terminal.
Note: Refer to "Aux Loading and Battery Selection" on page 21.
Additional Wiring
Zone Wiring
Power down the alarm controller and complete all zone wiring.
Zones can be wired to supervise normally open devices (e.g., smoke
detectors) or normally closed devices (e.g., door contacts). The alarm panel
can also be programmed for single end-of-line or double end-of-line
resistors.
Zone programming is done using the following programming sections:
l[001] selects zone definition
l[013] Opt [1] for normally closed or EOL; Opt [2] for SEOL or
DEOL
l[201 - 208] partition assignment.
Observe the following guidelines when wiring zones:
lFor UL listed installations use SEOL or DEOL only
lMinimum 22 AWG wire, maximum 18 AWG
lDo not use shielded wire
lDo not exceed 100Ωwire resistance. Refer to the following table:
Table 1-4 Burglary Zone Wiring Chart
Wire Gauge Maximum Length to EOL Resistor (ft/-
meters)
22 3000 / 914
20 4900 / 1493
19 6200 / 1889
18 7800 / 2377
Figures are based on maximum wiring resistance of 100Ω.
Aux Power Wiring
These terminals provide 11.3-12.5VDC/700mA of current (shared with
PGM outputs). Connect the positive side of any device to the AUX+
terminal, the negative side to GND. The AUX output is protected; if too
much current is drawn from these terminals (wiring short) the output is
temporarily shut off until the problem is corrected.
Note: If using a 12V, 14Ah battery, maximum AUX capacity for 24-hour
standby is 470mA.
PGM Wiring
Min/max operating voltages for devices, sensors and modules is 9.5VDC
- 14VDC.
PGMs switch to ground when activated from the alarm controller. Connect
the positive side of the device to the AUX+ terminal and the negative side
to a PGM terminal.
PGM 1, 3, 4 supply up to 50mA; PGM 2 supplies up to 300mA.
A relay is required for current levels greater than 50mA or 300mA. PGM2
can also be used for 2-wire smoke detectors, 24-hr burglary input alarm.
Note: Use SEOL resistors on Fire zones only.
Figure 1-2 LED Output with Current Limiting Resistor and
Optional Relay Driver Output.
Single End-of-Line (SEOL) Resistor
When SEOL resistors are installed at the end of a zone loop, the alarm
panel detects if the circuit is secure, open, or shorted. The SEOL resistor
must be installed at the end of the loop for proper supervision.
To enable SEOL supervision, program section [013], options [1] and [2]
to OFF.
Note: This option should be selected if either normally closed or normally
open detection devices or contacts are used.
Figure 1-3 SEOL Wiring
- 4 -

PowerSeries Neo Installation Guide
Double End of Line (DEOL) Resistors
When double end-of-line (DEOL) resistors are installed at the end of a
zone loop, the second resistor enables the panel to determine if the zone is
in open, closed, tampered or faulted.
Note: Any zone programmed for Fire or 24-hr Supervisory must be wired
with a SEOL resistor regardless of the type of zone wiring supervision
selected for the panel. If you change the zone supervision options from
DEOL to SEOL or from NC to DEOL, power the system down
completely, then power it back up for correct operation.
To enable DEOL supervision, program section [013], option [1] to OFF
and option [2] to ON.
Figure 1-4 DEOL Wiring
Bell Wiring
These terminals supply 700mA of current at 10.4 - 12.5VDC for
commercial/ residential installations. To comply with NFPA 72 Temporal
Three Pattern requirements, section [013] Opt [8] must be ON. Note that
steady, pulsed alarms are also supported.
Figure 1-5 Bell Wiring
The Bell output is supervised and power limited by 2A thermistor. If
unused, connect a 1000Ωresistor across Bell+ and Bell- to prevent the
panel from displaying a trouble.
Telephone Line Wiring
Wire the telephone connection terminals (TIP, Ring, T-1, R-1) to an RJ-
31x connector as indicated in the following diagram. For connection of
multiple devices to the telephone line, wire in the sequence indicated. Use
26 AWG wire minimum for wiring.
Figure 1-6 Telephone Line Wiring
Telephone format is programmed in option [350]. Telephone call
directions are programmed in options [311]- [318].
Ground Wiring
Figure 1-7 Ground Installation
Note: Using an insulated green wire (minimum 22AWG), connect the
EGND terminal on the Corbus and the grounding wire from the building
electrical installation to any of the available holes on the back or side of the
metal cabinet. See the diagram attached to the cabinet for suggested GND
point location and hardware recommendations.
Note: Wire and installation hardware not included.
Enrollment
All optional modules and devices must be enrolled on the system. During
enrollment, the electronic serial number (ESN) of each device is identified
to the control panel and zones are assigned. A wireless transceiver
HSM2HOST or an RF keypad must be enrolled first before wireless
devices can be enrolled.
Enrolling Modules
During automatic and manual enrollment, if an attempt is made to enroll
more than the maximum number of modules, an error tone sounds and a
message is displayed on LCD keypads.
Table 1-5 Module Capacity
Module HS2016 HS2032 HS2064/
HS2064 E
HS2128/HS2128 E
HSM2108 8 Zone expander 1 3 7 15
HSM2208 8 Output expander 2 4 8 16
Wireless Keypad:
HS2LCDRF(P)4
HS2ICNRF(P)4
HS2LCDWF(P)(V)4
8 8 8 16
HS2TCHP Touchscreen
Keypad
8 8 8 16
HSM2300 Power Supply 1A 3 3 3 4
HSM2204 4 High-current
Output
1 1 3 4
HSM2HOSTx Transceiver 1 1 1 1
HSM2955 1 1 1 1
Modules can be enrolled automatically or manually using section [902] of
Installer programming.
- 5 -

PowerSeries Neo Installation Guide
To confirm that a module has been successfully enrolled, use Installer
Programming section [903].
Enroll Wireless Devices
Wireless devices are enrolled via the wireless transceiver module and
Installer Programming section [804][000].
Auto Enrollment
To enroll a wireless device using this method, press and hold the Enroll
button on the device for 2-5 seconds until the LED lights then release the
button. The alarm panel automatically recognizes the device and the keypad
displays a confirmation message. The device ID and next available zone
number are displayed. Press [*] to accept or scroll to another available
zone number. Batteries must be installed in the wireless device in order to
enroll.
Pre-Enrollment
Pre-enrollment is a two step process. The first step requires entering each
device ID ([804][001]-[716]). Every wireless device has an ID printed on
the sticker attached to the device. The format is XXX-YYYY where:
lXXX identifies the type or model of the device
lYYYY is a short encrypted ID used by the system to identify the
specific device
Pre-enrollment can be done at a remote location and using DLS/SA. The
second step is to press the enrollment button on the device, usually done
on location. Installer Programming does not have to be entered at this step.
Both steps must be performed in order to complete the enrollment.
Programming Methods
The alarm system can be programmed using the following methods:
Table 1-6 Programming Methods
Method Description Procedure
Template
programming
Use pre-defined templates to
quickly apply basic programming
and to set up DLS downloading.
Press [899] at the
“Enter Section”
screen.
See Template
Programming below
for details.
DLS
programming
Download and apply programming
using DLS 5 v1.3 for Neo v1.0
panels and DLS 5 v1.4+ for Neo
v1.0 and up products.
For local DLS, use a
PC-Link cable and
laptop with DLS-5
software installed.
For remote DLS, use
a telephone line,
cellular network or the
Internet.
Installer
programming
Manually program all alarm system
and device options.
Press [*][8][installer
code] while the
system is disarmed.
Viewing Programming
Programming sections can be viewed from any system keypad. The
method for viewing and selecting programming options using LCD, LED
and ICON keypads depends on the keypad type used. See below for
specific instructions on programming with each keypad type.
Generally, programming options are accessed in the following way:
1. Enter Installer Programming mode ([*][8]).
2. Navigate to a specific programming section.
3. Select an option to view or change its programming.
All programming options are numbered and can be accessed by navigating
through the menu (LCD) or by keying in the program section number. For
toggle options, the name of the option is displayed (LCD) or LEDs 1-8 are
illuminated (LED and ICON).
Use the keypad numbers to toggle options on or off. Sections requiring
data input, such as phone numbers, display the full data in fields up to 32
characters long (LCD). To input data, use the scroll keys to select a
character then press the keypad button corresponding to the number/letter
required. Scroll to the next character and repeat the procedure as needed.
Press the [#] key to save changes and exit the program section.
Minimum Required Programming
Once basic installation of the alarm panel is complete, the following
general configuration options can be set.
[000] Language Selection
(LCD keypads only)
Use this section to set the language displayed by LCD keypads. To select a
language:
1. Enter Installer Programming: [*][8][Installer Code].
2. Enter programming section [000]>[000].
3. Key in the 2-digit number corresponding to the language required. See
below:
01 = English 11 = Swedish 22 = Bulgarian
02 = Spanish 12 = Norwegian 23 = Latvian
03 = Portuguese 13 = Danish 24 = Lithuanian
04 = French 14 = Hebrew 25 = Ukrainian
05 = Italian 15 = Greek 26 = Slovakian
06 = Dutch 16 = Turkish 27 = Serbian
07 = Polish 18 = Croatian 28 = Estonian
08 = Czech 19 = Hungarian 29 = Slovenian
09 = Finnish 20 = Romanian
10 = German 21 = Russian
Time and Date
Use this section to program the alarm system clock.
Menu: [*][6][Master Code] > Time and Date
Keypad: [*][6][Master Code] + 01
Enter time and date using the following format: (HH:MM); (MM-DD-
YY). Valid time entries are 00-23 hours, 00-59 minutes. Valid date entries
are 01-12 months, 01-31 days.
Setting Up a Partition
Partitions are added or removed from the system by applying or removing
a partition mask via Installer Programming section [200]. The number of
available partitions depends on the alarm panel model.
Bell/Siren Operation
Each partition must have a siren. The system siren connected to the bell
output of the alarm controller can be mounted in a central location within
hearing range of all partitions. Each partition can also have wireless sirens
activated only on the assigned partition.
Keypad Partition Setup
Keypads can be configured to control an individual partition or all
partitions. In general, a partition keypad controls the partition it is assigned
to. A Global keypad controls all partitions. Global keypads should be
- 6 -

PowerSeries Neo Installation Guide
placed in common areas of the premises, such as points of entry or
reception areas, where the ability to arm and disarm more than one
partition at a time is required.
Partition keypads can also be temporarily loaned to other partitions.
To select a keypad operating mode:
1. Enter Installer Programming: [*][8][installer code].
2. Select [861]-[876] to program keypads 1-16.
lPress [000] for partition assignment.
lFor Global operation, key in 00.
lTo assign a keypad to a partition, key in 01-08 for partition 1-8.
3. Press the [#] and reapeat step 2 for next keypad. When finished
programming all keypads, press the [#] key twice to exit
programming.
Users are assigned partition access rights via the [*][5] menu.
Assign sirens to partitions:
[804]>[000]>[551]-[556]>[000]
Set up partition account codes:
[310]>[001]-[008]
Set up partition timers:
lEntry/exit delay, settle delay – [005]>[001]-[008]
lAutomatic arming/disarming schedule – [151]-[158]>[001]/[002]
lAuto disarming holiday schedule – [151]-[158]>[003]
lNo activity arming – [151]-[158]>[006]
lAutomatic clock adjust – [005]>[000], option 6
lDelay between dialing attempts – [377]>[012]
Assign Zone Types
A zone type defines how a zone operates within the system and how it
responds when triggered.
000 - Null Zone 040 - 24-Hour Gas
001 - Delay 1 041 - 24-Hour CO
002 - Delay 2 042 - 24-Hour Holdup*
003 - Instant 043 - 24-Hour Panic
004 - Interior 045 - 24-Hour Heat
005 - Interior Stay/Away 046 - 24-Hour Medical*
006 - Delay Stay/Away 047 - 24-Hour Emergency
007 - Delayed 24-Hour Fire 048 - 24-Hour Sprinkler*
008 - Standard 24-Hour Fire 049 - 24-Hour Flood
009 - Instant Stay/Away 051 - 24-Hour Latching Tamper
010 - Interior Delay 052 - 24-Hour Non-Alarm
011 - Day Zone 056 - 24-Hour High Temperature
012 - Night Zone 057 - 24 Hour Low Temperature
016 - Final Door Set 060 - 24-Hour Non-Latching Tamper
017 - 24-Hour Burglary 066 - Momentary Keyswitch Arm
018 - 24-Hour Bell/Buzzer 067 - Maintained Keyswitch Arm
023 - 24-Hour Supervisory 068 - Momentary Keyswitch Disarm
024 - 24-Hour Supervisory Buzzer 069 - Maintained Keyswitch Disarm
025 - Auto Verified Fire 071 - Door Bell
027 - Fire Supervisory 072 - Push to Set
* Not UL evaluated
Assign zone attributes:
[002]>[001]-[128]>Select one of the following zone attributes:
1 – Bell Audible
2 – Bell Steady
3 – Chime Function
4 – Bypass Enabled
5 – Force Arm
6 – Swinger Shutdown
7 – Transmission Delay
8 – Burglary Verification
9 – Normally Closed EOL
10 – Single EOL
11 – Double EOL
12 – Fast/Normal Loop Response
13 – Zone 2-way Audio Activation
14 – Hold Up Verification
Create labels:
[000]>[001]-[821] 2 x 14 ASCII characters.
Add access codes:
To program an access code: [006] then one of the following:
[001] – Installer code
[002] – Master code
[003] – Maintenance code
Access codes are either 4, 6 or 8 digits in length, depending on the setting
of programming section [041]. Duplicate codes are not valid.
Alternate Communicator Setup
The alternate communicator is an optional wireless or ethernet
communications device that can be used as a backup to the PSTN
connection or as a primary means of communication between the alarm
panel and the central monitoring station. The alternate communicator
communicates via 3G (HSPA) or Ethernet.
The following configuration steps are required to set up the alternate
communicator:
lInstall the alternate communicator and wire it to the alarm panel
(use PCLINK_2 header)
lEnroll the alternate cellular communicator with Connect 24
lSet the communication path: [300]
lEnable the alternate communicator: [382] option 5
lEnable event reporting: [307]/[308]
lProgram communication delay timer: [377]
lProgram DLS access: [401] option 07
Refer to the 3G2080(R)/ TL2803G(R)/ TL280(R) installation manual for
details.
[300] Panel/Receiver Communication Paths
This section is used to select the path of communications between the
alarm system and the central station.
To use PSTN as the communications path, program section [300] options
001 through 004 as [01] PSTN 1.
To use the alternate communicator to establish a communications path,
program two of the receivers (section [300] options 001, 002, 003 or 004)
as [03] and [04] for Ethernet, and two of the receivers as [05] and [06] for
cellular.
Testing the System
Installer Walk Test
Walk test enables the installer to test the operation of each detector by
tripping zones, causing an actual alarm. Enter section [901] to initiate a
walk test. When a zone is tripped, all system sirens emit a tone to indicate
that the zone is working correctly.
- 7 -

PowerSeries Neo Installation Guide
After 15 minutes without zone activity, the walk test terminates
automatically. To manually exit walk test mode, enter [901] again.
Viewing the Event Buffer
The event buffer contains logs of events that have occurred on the alarm
system beginning with the most recent. The capacity of the event buffer is
scalable and can hold 500/1000 events (depending on panel model) before
rolling over. The buffer displays events according to their time stamp,
beginning with the most recent. The event buffer can be uploaded using
DLS.
Each event displays the time and date, a description of the event, the zone
label, access code number or any other pertinent information. To view the
event buffer, press [*][6][Master Code][*].
Troubleshooting
LCD programmable-message keypad:
lPress [*][2] followed by access code if required to view a trouble
condition
lThe trouble light flashes and the LCD displays the first trouble
condition
lUse the arrow keys to scroll through all trouble conditions present
on the system
Note: When additional information is available for a specific trouble
condition, a [*] is displayed. Press the [*] key to view the additional
information.
LED and ICON keypads:
lPress [*][2] to view a trouble condition
lThe trouble light flashes
lRefer to the trouble summary list below to determine the trouble
condition(s) present on the system
[*][2] Trouble Display
This feature is used to view system troubles. If a trouble is present, the
keypad Trouble indicator illuminates and an audible indication is emitted
(two short beeps every 10 seconds, except while in AC failure). Silence
the audible indicator by pressing [#].
Troubles may be viewed while the system is armed or disarmed. The
system may be programmed to show all troubles while armed or only fire
troubles.
The system can be configured to require a user code to view [*][2] system
troubles. See section [023] option 5.
To view trouble conditions:
lPress [*][2] to enter the Trouble menu.
lOn an LCD keypad, scroll to a trouble type then press [*] to view
the specific trouble. The zone name and trouble condition for each
trouble are displayed on the screen.
lOn LED/ICON keypads, zone indicator lights illuminate to
identify existing trouble types (e.g., Zone light 1 represents Ser-
vice Required trouble type). Press the number key corresponding
to a zone light to view the specific trouble. Lights 1-12 illuminate
to indicate the trouble as follows:
Table 1-7 : Trouble Indications
Trouble 01 –Service Required:
[01] Bell Circuit Trouble: The bell circuit is open.
[02] RF Jam: The HSM2HOSTx has detected an RF Jam condition.
[03] Aux Supply Trouble: The alarm controller, HSM2204 or HSM2300 has an
overcurrent condition on Aux.
[04] Loss of Clock: System time and date require programming.
[05] Output 1 Fault: An HSM2204 module has detected an open condition on output
#1.
Trouble 02 – Battery Trouble:
[01] Panel Low Battery Trouble: The battery voltage (under load) is below 11.5V.
Restores at 12.5V.
[02] Panel No Battery: No battery connected to alarm controller.
[04] HSM2204 01 - 04 Low Battery: An HSM2204 has a battery voltage less than
11.5V.
[05] HSM2204 01 - 04 No Battery: No battery connected to HSM2204.
[07] HSM2300 01 - 04 Low Battery: An HSM2300 has a battery voltage less than
11.5V
[08] HSM2300 01 - 04 No Battery: No battery connected to HSM2300.
Trouble 03 – Bus Voltage:
[01] HSM2HOSTx Bus Low Voltage: The HSM2HOSTx module has measured less
than 6.3V on its Aux input.
[02] Keypad 01 - 16 Bus Low Voltage: A hardwired keypad has a bus voltage of less
than 6.9V for ICON/LCD (RF version) and 7.7V for non-RF models.
[04] HSM2108 01 - 15 Bus Low Voltage: A zone expander has a bus voltage of less
than 5.9V.
[05] HSM2300 01 - 04 Bus Low Voltage: A power supply has a bus voltage of less
than 6.9V.
[06] HSM2204 01 - 04 Bus Low Voltage: A high current output module has a bus
voltage of less than 6.9V.
[08] HSM2208 01 - 16 Bus Low Voltage: The low current output module has detected
a voltage less than 5.9V on its aux input.
[09] HSM2955 Bus Low Voltage: The audio module has detected a voltage less than
9.65V on its aux input.
Trouble 04 – AC Troubles:
[01] Zone 001 - 128 AC Trouble: An AC trouble has been detected on a PGX934 PIR
+ Camera.
[03] Siren 01 - 16 AC: A siren has an AC trouble.
[04] Repeater 01 - 08 AC: A wireless repeater has an AC trouble.
[05] HSM2300 01 - 04 AC: An HSM2300 has an AC trouble.
[06] HSM2204 01 - 04 AC: An HSM2204 has an AC trouble.
[07] Panel AC: The alarm controller has an AC failure condition.
Trouble 05 – Device Faults:
[01] Zone 001 - 128: A zone is in fault. Additional information displayed on LCD
keypads for the following troubles: Fire Trouble (2-W Smoke, PGX916, PGX926),
Freeze (PGX905), Self Test (PGX984), CO (PGX913), and Probe Disconnected
(PGX905). Also generated by a short on hardwired zones when DEOL is used or by a
wireless supervisory fault.
[02] Keypad 01 - 16: A wireless or hardwired keypad is in fault.
[03] Siren 01 - 16: A siren is in fault.
[04] Repeater 01 - 08: A wireless repeater is in fault (supervisory or loss of AC/DC).
Trouble 06 – Device Low Battery:
[01] Zone 001- 128: Wireless zone has a low battery.
[02] Keypad 01-16: Keypad has a low battery.
[03] Siren 01 - 16: Siren has a low battery.
[04] Repeater 01 - 08: Repeater has a low battery.
[05] User 01 - 1000: Wireless Key has a low battery.
- 8 -

PowerSeries Neo Installation Guide
Trouble 07 – Device Tampers:
[01] Zone 001 - 128 Tamper: A wireless or hardwired zone configured for DEOL
operation is in tamper.
[02] Keypad 01 - 16 Tamper: A hardwired or wireless keypad is in tamper.
[03] Siren 01 - 16 Tamper: A wireless siren is in tamper.
[04] Repeater 01 - 08 Tamper: A wireless repeater is in tamper.
[05] Audio Station 01 - 04 Tamper: An audio station connected to an HSM2955 is in
tamper.
Trouble 08 – RF Delinquency Trouble:
[01] Zone 001 - 128 RF Delinquency: No response from a wireless zone for 13
minutes. This trouble prevents arming until acknowledged or cleared using [*][2].
[02] Keypad 01 - 16 RF Delinquency: No response from a wireless keypad for 13
minutes.
[03] Siren 01 - 16 RF Delinquency: No response from a wireless siren for 13 minutes.
[04] Repeater 01 - 16 RF Delinquency: No response from a wireless repeater for 13
minutes.
Trouble 09 – Module Supervisory Trouble:
[01] HSM2HOSTx not responding.
[02] Keypad 01 - 16 not responding.
[04] HSM2108 01 - 15 not responding.
[05] HSM2300 01 - 04 not responding.
[06] HSM2204 01 - 04 not responding.
[08] HSM2208 01 - 16 not responding.
[09] HSM2955 is not responding.
Trouble 10 – Module Tamper:
[01] HSM2HOSTx Tamper.
[02] Keypad 01 - 16 Tamper.
[04] HSM2108 01 - 15 Tamper.
[05] HSM2300 01 - 04 Tamper.
[06] HSM2204 01 - 04 Tamper.
[08] HSM2208 01 - 16 Tamper.
[09] HSM2955 Tamper
Trouble 11 – Communications:
[01] TLM: Telephone line disconnected from control panel.
[02] Receiver 01-04 FTC Trouble: Failure to communicate using programmed receiver
paths.
[03] Alt. Comm SIM Lock: SIM card has incorrect or unrecognized PIN.
[04] Alt. Comm Cellular: Radio or SIM card failure, low signal strength detected, or
cellular network fault.
[05] Alt. Comm Ethernet: Ethernet connection unavailable. A valid IP address is either
not programmed or the module was unable to get an IP with DHCP.
[06] Receiver 01-04 Absent: Alternate communicator unable to initialize a receiver.
[07] Receiver 01-04 Supervision: Alternate communicator unable to communicate with
a receiver.
[09] Alt. Comm Fault: The alternate communicator has stopped responding.
[10] Alt Comm FTC Trouble: The alternate communicator has failed to communicate
an internal event not generated by the panel.
Trouble 12 – Not Networked Troubles:
[01] Zone 001-128 Not Networked Trouble: Generated when a zone becomes out of
sync with the wireless network or has not been synchronized with the network after
enrollment.
[02] Keypad 01-16 Not Networked Trouble: Generated when a keypad becomes out of
sync with the wireless network or has not been synchronized with the network after
enrollment.
[03] Siren 01-16 Not Networked Trouble: Generated when a siren becomes out of sync
with the wireless network or has not been synchronized with the network after
enrollment.
[04] Repeater 01-08 Not Networked Trouble: Generated when a repeater becomes out
of sync with the wireless network or has not been synchronized with the network after
enrollment.
[05] User 01 - 1000 Not Networked Trouble: Generated when a wireless key becomes
out of sync with the wireless network or has not been synchronized with the network
after enrollment.
IMPORTANT!
Ensure you have the following information available before contacting
Customer Support :
lAlarm controller type and version, (e.g., HSM2064 1.0):
Note: Version number can be accessed by entering [*][Installer Code]
[900] on any LCD keypad. This information is also located on a sticker on
the printed circuit board.
lList of modules connected to control panel, (e.g., HSM2108,
HSM2HOSTx etc.) .
Zone Configuration
l16, 32, 64, or 128 wireless zones supported and up to 8 hard-
wired zones available on the controller
l40 zone types and 14 programmable zone attributes
lZone configurations available: normally closed, single EOL and
DEOL supervised
lHardwired zone expansion (fully supervised) available using the
model HSM2108 (eight zone expander module)
lWireless zone expansion (fully supervised) available using the
HSM2Host 2-way wireless integration module operating at
915MHz (North America), 433MHz (Europe) and 868MHz (inter-
national)
- 9 -

PowerSeries Neo Installation Guide
Access Codes
lUp to 1002 access codes: 1000 (level 2-EN), one installer code
(level 3-EN), and one maintenance code
lProgrammable attributes for each user code
lWhen using 8-digit access codes, the minimum number of vari-
ations are:
HS2016: 2083333
HS2032: 1388888
HS2064/HS2128: 1052631
HS2064 E: 200000
HS2128 E: 100000
Warning Device Output
lIntegral sounder capable of 85 dB @ 3m, self-powered type Z
l2 remote, wireless indoor/outdoor warning devices supported:
models PGX901 (indoor), PGX911 (outdoor) (X=4, 8, or 9)
lProgrammable as steady, pulsed or temporal three (as per
ISO8201) and temporal four (CO alarm) output
lWarning device sounds alarms in the following priority: fire, CO,
burg
Memory
lCMOS EEPROM memory
lRetains programming and system status on AC or battery failure
for 20 years min.
Power Supply - International
lInput ratings: 220V-240Vac, 50/60Hz, 200mA
lTransformer required, mounted in the same enclosure,
permanently connected
lTransformer secondary ratings: 16.5Vac, 40VA min.
Note: For installations using the transformer mounted inside the cabinet,
replace fuse only with the same type (20mm) rated 250V/315mA.
Regulated power supply:
l1.7A regulated, supervised and integral to the control unit
lType A as per EN50131-6 Standard
l700mA auxiliary supply, 12V DC
lPositive temperature coefficient (PTC) for Bell, Aux+ and Battery
terminals
lReverse battery detection/protection
lSupervision for AC power and low battery
lNormal and high current battery charge options
lSupervised battery charging circuit
Current draw (panel):
l85mA (nominal) 2A(Max)
Bell Output:
l12V, 700mA supervised (1k Ohm) bell output (current limited at
2 amps)
lSteady, Pulsed, Temporal 3 fire, Temporal 4 CO alarm cadences
lBell short detection (software + hardware)
Aux+:
lVoltage range = 9.6V - 13.8V DC
lCurrent = 700mA (shared with Corbus R(ed))
lOutput ripple voltage: 270mVp-p max.
lOnboard programmable outputs:
lPGM 1 - 50mA switched programmable output
lPGM 2 - 300mA current-limited switched programmable
output. 2-Wire smoke detectors (90mA current limited)
are supported using this PGM
lPGM 3 - 50mA switched programmable output
lPGM 4 - 50mA switched programmable output
lHardware PGM over current protection
Battery
l12V sealed lead acid, rechargeable
lBattery capacity:
l12 hours (EN50131),
l24 hours INCERT [Belgium]
Note: For T 014 compliance (INCERT certification), only 14Ah
(2x7Ah) batteries were tested and are accepted for INCERT
certified systems.
lMaximum standby time: 24 hours (with 14Ah battery and Aux
current limited to 470mA)
lRecharging time to 80% 72 hours
lRecharging rate: 240mA (12 hours max.), 480mA (24 hour
backup)
lBackup time: 24 hours
lBattery lifespan: 3-5 years
lLow battery trouble indication threshold 11.5VDC
lBattery restore voltage 12.5V
lMain board current draw (battery only):
lHS2016/32/64/128 (no alternate communicator) standby
85mA DC
lHS2016/32/64/128, (including alternate communicator)
standby 190mA DC
lTransmit (alternate communicator module) 195mA DC
lResettable fuses (PTC) used on circuit board
lSupervision for loss of primary power source (AC fail), battery
loss or battery low voltage (battery trouble) with indication
provided on the keypad
lInternal clock locked to AC power frequency
Operating Environmental Conditions
lTemperature range: EN= -10°C to 55°C (50°F-131°F)
lRelative humidity: <93% non condensing
Alarm Transmitter Equipment (ATE) Specification
lDigital dialer integral to the main control board
lSupports SIA and Contact ID
lComplies with TS203 021-1, -2, -3 Telecom equipment require-
ments and EN50136-1-1, EN50136-2-1, EN50136-2-3 ATS 2
lOptional Dual IP/Cellular communicators (3G2080(R)/ TL2803G
(R)/ TL280(R)) can be installed in the same enclosure and con-
figured as primary or back-up, with AES 128-bit encryption
lCompliant with EN50136-1-1, EN50136-2-1 ATS2 requirements
System Supervision Features
The PowerSeries Neo continuously monitors a number of possible trouble
conditions and provides audible and visual indication at the keypad.
Trouble conditions include:
lAC power failure
lZone trouble
lFire trouble
lTelephone line trouble
lCommunicator trouble
lLow battery condition
lRF jam
lAUX power supply fault
lFailure to communicate
lModule fault (supervisory or tamper)
Additional Features
l2-way wireless device support
lVisual verification (images + audio)
- 10 -

PowerSeries Neo Installation Guide
lProximity tag support
lPGM scheduling
lQuick arming
lUser, partition, module, zone and system labels
lSoak test
lProgrammable system loop response
lKeypad and panel software versions viewable through keypad
lDoorbell zone type
lLow battery PGM type
- 11 -

Programming Directory
This section provides a list of all available programming options in numerical order. To program, access Installer Programming mode by keying in [*][8]
[Installer Code]. Use the scroll keys < > to navigate through the menus or jump directly to a specific section by keying in a section number and pressing
[*]. Programming consists of toggling on and off options in each section or by populating data fields. Press [*] to select options and [#] to exit to the
previous menu. For descriptions of all programming options and programming worksheets, refer to the PowerSeries Neo Reference Manual.✔= Default
Label Programming
000 Label Programming
000 – Language Selection (01)
001 – Zone Labels
- 12 -
001-128 – Zone Labels 1-128
051 – Zone Tamper Label
052 – Zone Fault Label
064 – CO Alarm Message
065 – Fire Alarm Message
066 – Fail to Arm Event Message
067 – Alarm When Armed Event
Message
100 – System Label
101-108 – Partition 1-8 Labels
201- 208 – Partition 1-8 Command
Output Labels
001-004 – Command output 1-
4 Labels
601-604 – Schedule 1- 4 Labels
801 – Keypad Labels
001-016 Keypad 1-16 Labels
802 – Zone Expander Labels
001-015 – Zone Expander 1-
15 Labels
803 – Output Expander Labels
001 Output Expander 1 Label
806 – HSM2HOST Label
808 – HSM2955 Label
809 – Power Supply Label
001-004 Power Supply 1-4
Label
810 – High Current Output Supply
Label
001-004 Power Supply 1-4
Label
815 – Alternate Communicator
Label
820 – Siren Label
001-016 Siren 1-16 Label
821 – Repeater Label
001-008 Repeater 1-8 Label
999 – Default Labels
Zone Type
001 Zone Type
001-128 Zone Types (000)
000 – Null Zone
001 – Delay 1
002 – Delay 2
003 – Instant
004 – Interior
005 – Interior Stay/Away
006 – Delay Stay/Away
007 – Delayed 24-Hour Fire
008 – Standard 24-Hour Fire
009 – Instant Stay/Away
010 – Interior Delay
011 – Day Zone
012 – Night Zone
016 – Final Door Set
017 – 24-Hour Burglary
018 – 24-Hour Bell/Buzzer
023 – 24-Hour Supervisory
024 – 24-Hour Supervisory
Buzzer
025 – Auto Verify Fire
027 – Fire Supervisory
040 – 24-Hour Gas
041 – 24-Hour CO
042 – 24-Hour Holdup
043 – 24-Hour Panic
045 – 24-Hour Heat
046 – 24-Hour Medical*
047 – 24-Hour Emergency
048 – 24-Hour Sprinkler
049 – 24-Hour Flood
051 – 24-Hour Latching
Tamper
052 – 24-Hour Non-Alarm
056 – 24-Hour High
Temperature
057 – 24 Hour Low
Temperature
060 – 24-Hour Non-Latching
Tamper
066 – Momentary Keyswitch
Arm
067 – Maintained Keyswitch
Arm
068 – Momentary Keyswitch
Disarm
069 – Maintained Keywsitch
Disarm
071 – Doorbell Zone
072 – Push to Set
002 – Zone Attributes
001-0128 (see PowerSeries Neo
reference manual for defaults)
1 – Bell Audible
2 – Bell Steady
3 – Door Chime
4 – Bypass Enabled
5 – Force Arm
6 – Swinger Shutdown
7 – Transmission Delay
8 – Burglary Verification
9 – Normally Closed EOL
10 – Single EOL
11 – Double EOL
12 – Fast Loop/Normal Loop
Response
13 – Zone 2-way Audio
Activation
14 – Holdup Verification
System Times
005 System Times
000 – System Area
Bell Cutoff (004 min.)
Bell Delay Time (000 min.)
Burglary Verification Timer
(060 sec.)
Holdup Verification Timer
(008 sec.)
Zone Loop Response (250 ms)
Automatic Clock Adjust (060
sec.)
001 – 008 System Times - Partition
1-8
Entry Delay 1 (030 sec.)
Entry Delay 2 (045 sec.) (CP-
01 030 sec.)
Exit Delay (120 sec.) (CP-01
060 sec.)
Settle Delay (010 sec.) (CP-
01 000 sec.)
900 – Bell Delay Partition Mask
(Y,Y,Y,Y,Y,Y,Y,Y)
901 – Daylight Savings Begin:
Month (003)(AUS 010)(NZ
009)(SA004)(FRA 004)
Week (005)(AUS 005)(NZ
005)(SA 001)(CE 005)(C 005)
(FRA 001)(UK 005)
Day (000)
Hour (001)(CE 001)(C 001)
(UK001)
Increment (001)
902 – Daylight Savings End
Month (010)(AUS 003)(NZ
004)(SA010)(C 010)(FRA
010)(UK010)
Week (005)(AUS 005)
(SA005)(FRA 005)(UK005)
Day (000)
Hour (002)(001)(NZ 003)(CE
001)(C 001)(UK 001)
Decrement (001)
Access Codes
006 Installer Defined Access Codes
(4-digit decimal)
001 – Installer Code (55555555)
002 – Master Code (12345678)
003 – Maintenance Code
(AAAAAAAA)
004 – Guard Code
(AAAAAAAA)
005 - Code Version (000)
PGM Programming
007 – PGM Programming
000 – Main Bell Partition
Assignment
1 – Partition 1
2 – Partition 2
3 – Partition 3
4 – Partition 4
5 – Partition 5
6 – Partition 6
7 – Partition 7
8 – Partition 8
001-164 – PGM 1-164 Partition
Assignment (default: partition 1)
1-8 – Partition 1-8
008 – PGM Timer Programming
000 – PGM Timer-Minutes or
Seconds (seconds)
001-164 – PGM 1-164 Timer (005)
009 – PGM Types
001-164 – PGM 1-164 Type
Assignment (default: PGM1=121,
PGM2=156, 3-164=101)
100 – Null PGM
101 – Burg and Fire Bell
Follower
102 – Delayed Fire and Burg
103 – Sensor Reset [*][7][2]
104 – 2-Wire Smoke
109 – Courtesy Pulse
111 – Keypad Buzzer Follow
114 – Ready To Arm
115 – System Armed Status
116 – Away Armed Status
117 – Stay Armed Status
120 – Away Armed with no
Zone Bypass Status
121 – Command Output 1
122 – Command Output 2
123 – Command Output 3
124 – Command Output 4
129 – Partition Status Alarm
Memory
132 – Holdup Output
134 – 24Hr Silent Input
135 – 24Hr Audible Input
146 – TLM and Alarm
147 – Kissoff
148 – Ground Start
149 – Alternate
Communicator
155 – System Trouble
156 – Latched System Event
157 – System Tamper
161 – DC Trouble
165 – Prox Used
166 – Partition Prox Used
175 – Bell Status and
Programming Access Output
176 – Remote Operation
184 – Open After Alarm
200 – Zone Follower
201 – Follower-Zones 1-8
202 – Follower-Zones 9-16
203 – Follower-Zones 17-24
✔= Default

PowerSeries Neo Installation Guide
204 – Follower-Zones 25-32
205 – Follower-Zones 33-40
206 – Follower-Zones 41-48
207 – Follower-Zones 49-56
208 – Follower-Zones 57-64
209 – Follower-Zones 65-72
210 – Follower-Zones 73-80
211 – Follower-Zones 81-88
212 – Follower-Zones 89-96
213 – Follower-Zones 97-104
214 – Follower-Zones 105-112
215 – Follower-Zones 113-120
216 – Follower-Zones 120-128
010 PGM Attributes
000 – Main Bell Mask
Fire Alarm ✔
CO Alarm ✔
Burglary Alarm ✔
24-Hour Flood Alarm ✔
Bell Squawks ✔
001-164 PGM 1-164 Attributes
100 – Null PGM
101 – Fire and Burglary
01 – True Output ✔
03 – Code Required ✔
102 – Delay Fire and Burglary
01 – True Output
103 – Sensor Reset [*][7][2]
03 – Code Required
109 – Courtesy Pulse
01 – True Output
111 – Keypad Buzzer Follow
01 – True Output ✔
02 – Timed Output
09 – Entry Delay ✔
10 – Exit Delay ✔
11 – Door Chime ✔
12 – Keypad Buzzer Zone ✔
13 – Audible Exit Fault ✔
14 – Auto-Arm Pre-Alert ✔
114 – Ready To Arm
01 – True Output ✔
115 – Armed Status
01 – True Output ✔
116 – Armed Away Mode
01 – True Output ✔
117 – Armed Stay Mode
01 – True Output ✔
121 - 124 – Command Output 1-4
01 – True Output ✔
02 – Timed Output ✔
03 – Code Required ✔
(NZoff)
129 – Partition Status Alarm
Memory
01 – True Output ✔
132 – Holdup Output
01 – True Output ✔
02 – Timed Output
146 – TLM and Alarm
01 – True Output ✔
147 – Kissoff Output
01 – True Output ✔
148 – Ground Start
01 – True Output ✔
149 – Alternate Communicator
01 – True Output ✔
02 – Timed Output ✔
04 – Fire Alarm
05 – Panic Alarm
06 – Burglary Alarm
07 – Open/Close
08 – Zone Auto Bypass
09 – Medical Alarm
10 – Burglary Verified
11 – Open after Alarm
12 – Emergency Alarm
13 – Duress Alarm
14 – Holdup Verified
155 – System Trouble
01 – True Output ✔
02 – Timed Output
04 – Service Required ✔
05 – Loss of Clock ✔
06 – AC Fail ✔
07 – DC Fail ✔
08 – TLM ✔
09 – FTC ✔
10 – Ethernet ✔
11 – Zone Fault ✔
12 – Zone Tamper ✔
13 – Zone Low Battery ✔
156 – Latched System Event
01 – True Output ✔
02 – Timed Output
04 – Fire Alarm ✔
05 – Panic Alarm ✔
06 – Burglary Alarm ✔
07 – Medical Alarm ✔
08 – Supervisory ✔
09 – Priority Event ✔
10 – Holdup ✔
11 – Duress ✔
12 – Emergency ✔
13 – Fire Supervisory ✔
14 – Fire Trouble ✔
15 – CO Alarm ✔
157 – System Tamper
01 – True Output ✔
02 – Timed Output
09 – Module Tamper ✔
10 – Zone Tampers ✔
161 – DC Trouble
01 – True Output ✔
02 – Timed Output
09 – Battery Low ✔
10 – Battery Absent ✔
165 – Prox Used
01 – True Output ✔
166 – Partition Prox Used
01 – True Output ✔
175 – Bell Prog Access
01 – True Output ✔
176 – Remote Operation
01 – True Output ✔
184 – Open After Alarm
01 – True Output ✔
02 – PGM Timer ✔
200 Zone Follower – Single Zone
01 – True Output ✔
02 – Timed Output
03 – Code Required
04 – Latching
05 – Follow Alarm
201-216 Zone Follow Zones 1-128
01 – True Output ✔
02 – Timed Output
04 – Latching
05 – Follow Alarm
09-016 – Zone Terminal 1-16
011 PGM Configuration Options
001-164 – PGM 1-164
Configuration
Zone Follower by Zone
Proximity Tag Used
Command Output Schedules
012 System Lockout (attempts/min.)
Keypad Lockout Attempts
(000)
Keypad Lockout Duration
(000)
Remote Lockout Attempts
(006)
Remote Lockout Duration
(060)
System Options
013 System Options 1
1 – NC Loop/EOL
2 – DEOL/SEOL
3 – Show All Troubles when
Armed ✔
4 – Tamper/Faults Do Not show as
open
5 – Auto-Arm Schedule in [*][6]
✔
6 – Audible Exit Fault ✔
7 – Event Buffer Follows Swinger
✔
8 – Temporal Three Fire Signaling
014 System Options 2
1 – Bell Squawk
2 – Bell Squawk Auto-Arm
3 – Bell Squawk on Exit
4 – Bell Squawk on Entry
5 – Bell Squawk on Trouble
6 – Not Used
7 – Exit Delay Termination
8 – Fire Bell Continues
015 System Options 3
1 – [F] Key ✔
2 – [P] Key Annunciation
3 – Quick Exit
4 – Quick Arming/Function Key
✔
5 – Not Used
6 – Master Code Not User
Changeable
7 – Telephone Line Monitor
Enable ✔
8 – TLM Audible When Armed
016 System Options 4
1 – AC Trouble Display ✔
2 – AC Trouble Light Flashes
3 – Keypad Blanking
4 – Keypad Blanking Requires
Code
5 – Keypad Backlighting ✔
6 – Power Save Mode
7 – Bypass Display When Armed
8 – Keypad Tampers Enabled
017 System Options 5
1 – Chime On Opening
2 – Chime On Closing
3 – RF Jam Audible
4 – Multi-Hit
5 – Late to Close
6 – Daylight Savings Time
7 – Silence Chime During Quick
Exit Delay
8 – Bell Squawk on Away
Arm/Disarm Only
018 System Options 6
1 – Test Transmission Exception
2 – Real-Time Bypass Reporting
3 – Armed State PGM ON at End
of Exit Delay
4 – Not Used
5 – Keypad Buzzer Alarm
6 – Not Used
7 – Exit Delay Restart (CP-01
✔)
8 – AC Fail Trouble Beeps ✔
019 System Options 7
1 – Audible Wireless Zone Fault
2 – Latching Troubles (UK ✔)
3 – Not Used
4 – R-Button
5 – Audible Bus Fault (UK ✔)
6 – Duress Codes
7 – Temperature in Celsius ✔
8 – Reset After Zone Activation
020 System Options 8
1 – Access Code Entry During
Entry Delay
2 – EU Entry Procedure (UK ✔)
3 – [*][8] Access While Armed
4 – Remote Reset
5 – Engineer's Reset
6 – Keyswitch Disarming During
Entry Delay
7 – Installer Access and DLS
8 – Troubles Inhibits Arming (UK
✔)
021 System Options 9
1 – Trbl Display
2 – Keypad Blanking while armed
(UK ✔)
3 – Auto-Arming Bypass
4 – Ready Display
5 – PGM Keypad Blanking
6 – Armed Display
7 – Open Cancels Arming (UK
✔)
8 – Audible Exit Delay for Stay
Arming
022 System Options 10
1 – [F] Key Option
2 – Not Used
3 – Not Used
4 – Test Transmission Counter in
Hours
5 – Away to Stay Toggle
6 – 2-Way Full Duration ✔
7 – Trouble Beeps Are Silent
8 – Keyswitch Arms in Away
Mode (UK ✔)
023 System Options 11
- 13 -
✔= Default

PowerSeries Neo Installation Guide
1 – Ready LED Flash for Force
Arm
2 – Not Used
3 – Tamper/Fault Detection
4 – Access Code Required for [*]
[1]
5 – Access Code Required for [*]
[2]
6 – Access Code Required for [*]
[3]
7 – Access Code Required for [*]
[4]
8 – [*][6] Accessibility
024 System Options 12
1– 50Hz AC / 60 Hz AC (EN ✔)
(AUS ✔)(NZ ✔)(CHN ✔)(SA
✔)(CE✔)(FRA ✔)(UK ✔)
2 – Crystal Timebase
3 – AC/DC Inhibits Arming(UK
✔)
4 – Tamper Inhibit Arm
5 – Real Time Clock Option
6 – Not Used
7 – Option 7 (AC Brownout
Detection) This option must be
enabled for UL/ULC Commercial
Fire Installations.
8 – DLS Disconnect
025 System Options 13
1 – European Dial(EN ✔)(AUS
✔)(BRAZIL ✔)(SA ✔)
(CE✔)
2 – Force Dial ✔
3 – Test Transmission Counter in
Minutes
4 – Not Used
5 – ID Tone
6 – Tone Generated-2100Hz
7 – 1 Hour DLS Window
8 – FTC Audible Bell
040 User Authentication
01 – User Code or Proximity Tag
✔
02 – User Code and Proximity Tag
041 Access Code Digits
00 – 4-Digit Access Codes ✔
01 – 6-Digit Access Codes
02 – 8-Digit Access Codes
042 Event Verification
01 – Burglary Verified Counter
(002)(UK 003)
02 – Holdup Counter (002)
03 – Burglary Verification
Selection
001 – Police Code ✔
002 – Cross Zoning
003 – EU Sequential
Detection (UK ✔)
151-158 Partition 1-8 Auto-
Arm/Disarm
001 – Auto-Arming Times (9999)
24-Hour
Sunday
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
002 – Auto-Disarm Times (9999)
24-Hour
Sunday
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
003 – Auto-Disarming Holiday
Schedule
Holiday 1
Holiday 2
Holiday 3
Holiday 4
004 – Auto-Arming Pre-Alert
(004)
005 – Auto-Arming Postpone
Timer (000)
006 – No Activity Arming Timer
(000)
007 – No Activity Arming Pre-
Alert Timer (001)
200 Partition Mask
001 – Partition 1 to 8 Enable Mask
1 – Partition 1 ✔
2 – Partition 2
3 – Partition 3
4 – Partition 4
5 – Partition 5
6 – Partition 6
7 – Partition 7
8 – Partition 8
201-208 Partition 1-8 Zone
Assignment
001 – Zone 1-8 ✔
002 – Zn 9-16 ✔
003 – Zn 17-24
004 – Zn 25-32
005 – Zn 33-40
006 – Zn 41-48
007 – Zn 49-56
008 – Zn 57-64
009 – Zn 65-72
010 – Zn 73-80
011 – Zn 81-88
012 – Zn 89-96
013 – Zn 97-104
014 – Zn 105-112
015 – Zn 113-120
016 – Zn 121-128
300 Panel/Receiver Communications
Path
001 – 004 Receiver 1-4
01 – Phone Line ✔
02 – Alt Comm Auto Routing
03 – Alt Comm Rec 1-
Ethernet
04 – Alt Comm Rec 2-
Ethernet
05 – Alt Comm Rec 3-
Cellular
06 – Alt Comm Rec 4-
Cellular
301 Phone Number Programming
001 – 004 Phone Number 1 -4
Programming (DFFF...32-digit)
304 Call Waiting Cancel String
(DB70EF)
Event Reporting
307 Zone Reporting
001-128 Zone Reporting for Zones
1-128
01 – Alarm ✔
02 – Alarm Restore ✔
03 – Tamper ✔
04 – Tamper Restore ✔
05 – Fault ✔
06 – Fault Restore ✔
308 Event Reporting
001 – Miscellaneous Alarm 1
01 – Duress Alarm ✔
02 – Opening After Alarm ✔
03 – Recent Closing Alarm ✔
04 – Zone Expander
Supervisory Alarm ✔
05 – Zone Expander
Supervisory Alarm Restore
✔
06 – Burglary Verified ✔
07 – Burg Not Verified Alarm
✔
08 – Alarm Cancel ✔
002 – Miscellaneous Alarm 2
01 – Holdup Verified Alarm
✔
011 – Priority Alarms
01 – Keypad Fire Alarm-F
Key ✔
02 – Keypad Fire Restore ✔
03 – Keypad Medical Alarm-
M Key ✔
04 – Keypad Medical Restore
✔
05 – Keypad Panic Alarm (P)
✔
06 – Keypad Panic Restore ✔
07 – Auxiliary Input Alarm
✔
08 – Aux Input Alarm Restore
✔
021 – Fire Alarms 1
03 – PGM 2 2-Wire Alarm ✔
04 – PGM 2 2-Wire Restore
✔
101 – Tamper Events
03 – Module Tamper ✔
04 – Module Tamper Restore
✔
05 – Keypad Lockout ✔
07 – Remote Lockout ✔
201 – Open/Close Events 1
01 – User Closing ✔
02 – User Opening ✔
03 – Future Use
04 – Future Use
05 – Special Closing ✔
06 – Special Opening ✔
07 – Keyswitch Opening ✔
08 – Keyswitch Closing ✔
202 – Open/Close Events 2
01 – Automatic Closing ✔
02 – Automatic Disarm ✔
03 – Auto Arm
Cancellation/Postpone ✔
211 – Miscellaneous Open/Close
Events
01 – Late to Close ✔
02 – Late to Open ✔
05 – Exit Fault ✔
221 – Bypass Events
01 – Auto Zone Bypass
02 – Auto Zone Unbypass
03 – Partial Closing ✔
301 – Panel Events 1
01 – Panel AC Fail Trouble
✔
02 – Panel AC Fail Restore
✔
03 – Panel Low Battery ✔
04 – Panel Low Battery
Restore ✔
05 – Panel Battery Absent ✔
06 – Panel Battery Absent
Trouble Restore ✔
302 – Panel Events 2
01 – Bell Circuit Trouble ✔
02 – Bell Circuit Restore ✔
03 – Telephone Line Trouble
✔
04 – Telephone Line Trouble
Restore ✔
05 – Auxiliary Trouble ✔
06 – Auxiliary Trouble
Restore ✔
305 – Panel Events 5
03 – PGM 2 2-Wire Trouble
✔
04 – PGM 2 2-Wire Restore
✔
311 – Maintenance Events 1
01 – RF Jam Trouble ✔
02 – RF Jam Trouble Restore
✔
03 – Fire Trouble ✔
04 – Fire Trouble Restore ✔
05 – Cold Start ✔
06 – Delinquency ✔
07 – Self Test Trouble ✔
08 – Self Test Trouble
Restore ✔
312 – Maintenance Events 2
01 – Installer Lead IN ✔
02 – Installer Lead OUT ✔
03 – DLS Lead IN ✔
04 – DLS Lead OUT ✔
05 – SA Lead IN
06 – SA Lead OUT
07 – Event Buffer 75% Full
✔
313 – Maintenance Events 3
01 – Firmware Update Begin
✔
02 – Firmware Update
Success ✔
03 – Firmware Update Fail ✔
314 – Maintenance Events 4
- 14 -
✔= Default

PowerSeries Neo Installation Guide
01 – Gas Trouble ✔
02 – Gas Trouble Restore ✔
03 – Heat Trouble ✔
04 – Heat Trouble Restore ✔
05 – Freeze Trouble ✔
06 – Freeze Trouble Restore
✔
07 – Probe Disconnected ✔
08 – Probe Disconnect
Restore ✔
321 – Receiver Events
02 – Receiver 1 FTC Restore
✔
04 – Receiver 2 FTC Restore
✔
06 – Receiver 3 FTC Restore
✔
08 – Receiver 4 FTC Restore
✔
331 – Module Events 1
01 – Module AC Trouble ✔
02 – Module AC Trouble
Restore ✔
03 – Module Battery Trouble
✔
04 – Module Battery Trouble
Restore ✔
05 – Module Battery Absent
✔
06 – Module Battery Absent
Restore ✔
332 – Module Events 2
01 – Module Low Voltage ✔
02 – Module Low Voltage
Restore ✔
03 – Module Supervisory ✔
04 – Module Supervisory
Restore ✔
05 – Module Aux Trouble ✔
06 – Module Aux Trouble
Restore ✔
335 – Module Events 5
01 – Output 1 Fault ✔
02 – Output 1 Fault Restore
✔
351 – Alternate Communicator 1
01 – Alt. Comm. Module
Comm Fault ✔
02 – Alt. Comm. Module
Comm Fault Restore ✔
07 – Alt. Comm. Radio/SIM
Failure ✔
08 – Alt. Comm. Radio/SIM
Failure ✔Restore
352 – Alternate Communicator 2
01 – Alternate Comm.
Network Fault ✔
02 – Alt. Comm. Network
Fault Restore ✔
05 – Alt. Comm. Ethernet ✔
06 – Alt. Comm. Ethernet
Trouble Restore ✔
354 – Alternate Communicator 4
01 – Alt. Comm Receiver 1
✔
02 – Alt. Comm Receiver 1
Restore ✔
03 – Alt. Comm Receiver 2
✔
04 – Alt. Comm Receiver 2
Restore ✔
05 – Alt. Comm Receiver 3
✔
06 – Alt. Comm Receiver 3
Restore ✔
07 – Alt. Comm Receiver 4
✔
08 – Alt. Comm Receiver 4
Restore ✔
355 – Alternate Communicator 5
01 – Alt. Comm Receiver 1
Supervision Failure ✔
02 – Alt. Comm Receiver 1
Supervision Failure Restore
✔
03 – Alt. Comm Receiver 2
Supervision Failure ✔
04 – Alt. Comm Receiver 2
Supervision Failure Restore
✔
05 – Alt. Comm Receiver 3
Supervision Failure ✔
06 – Alt. Comm Receiver 3
Supervision Failure Restore
✔
07 – Alt. Comm Receiver 4
Supervision Failure ✔
08 – Alt. Comm Receiver 4
Supervision Failure Restore
✔
361 – Wireless Device Events
01 – Device AC Fail ✔
02 – Device AC Restore ✔
03 – Device Low Battery ✔
04 – Device Low Battery
Restore ✔
05 – Device Fault ✔
06 – Device Fault Restore ✔
401– System Test Events
01 – Walk Test Start ✔
02 – Walk Test End ✔
03 – Periodic Test
Transmission ✔
04 – Periodic Test
Transmission with Trouble ✔
05 – System Test ✔
Communications
309 System Call Direction
001– Maintenance Events
1 – Receiver 1 ✔
2 – Receiver 2
3 – Receiver 3
4 – Receiver 4
002 – Test Transmission Events
1 – Receiver 1 ✔
2 – Receiver 2
3 – Receiver 3
4 – Receiver 4
310 Account Codes
000 – System Account Code
(FFFF)
001-008 – Partition 1-8 Account
Code (FFFF)
311-318 Partition 1-8 Call Direction
001 – Partition Burglary
Alarm/Restore Call Direction
1 – Receiver 1 ✔
2 – Receiver 2
3 – Receiver 3
4 – Receiver 4
002 – Partition Tamper/Restore
Call Direction
1 – Receiver 1 ✔
2 – Receiver 2
3 – Receiver 3
4 – Receiver 4
003 – Partition Opening/Closing
Call Direction
1 – Receiver 1 ✔
2 – Receiver 2
3 – Receiver 3
4 – Receiver 4
350 Communicator Formats (04 -
SIA)
001– Communicator Format -
Receiver 1
002– Communicator Format -
Receiver 2
003– Communicator Format -
Receiver 3
004– Communicator Format -
Receiver 4
377 Communication Variables
001 – Swinger Shutdown Attempts
– Alarms and Restore (003)
(CP-01 002 sec.)
– Tampers and Restore (003)
– Maintenance and Restore
(003)
002 – Communication Delays
– Zone Delay (000 sec.)(CP-
01 030 sec.)
– AC Failure Communication
Delay (030 min./hrs.)
– TLM Trouble Delay (010
sec. x 3)
– WLS Zone Low Battery
Transmission Delay (007
days)
– Delinquency Transmission
Delay (030 hours/days)
– Communications Cancel
Window (000 (CP-01 005
min.)
003 – Periodic Test Transmission
Cycle (030 hrs./days)
004 – Periodic Test Transmission
Time of Day (9999)
011 – Maximum Dialing Attempts
(005)
012 – PSTN Delay (003 sec.)
013 – Delay Between Force
Attempts (020 sec.)
014 – Post Dial Wait for
Handshake (040 sec.)
015 – T-Link Wait for Ack (060
sec.)
016 – IP/Cellular Fault Check
Timer (010 )
380 Communicator Option 1
1 – Communications Enabled ✔
2 – Restore on Bell Timeout
3 – Pulse Dialing
4 – Pulse Dial After 5th Attempt
5 – Parallel Communications
6 – Alternate Dial ✔
7 – Reduced Dialing Attempts
8 – Activity Delinquency
381 Communicator Option 2
1 – Keypad Ringback
2 – Bell Ringback
4 – Closing Confirmation
8 – Communications Priority
382 Communicator Option 3
1 – Test Transmission Reciever
2 – Walk Test Communication
(UK✔)
4 – Call Waiting Cancel
5 – Alternate Communicator
Enable
6 – AC Failure TX in Hours
8 – Tamper Limit (UK✔)
383 Communicator Option 4
1 – Phone Number Account Code
2 – 6-Digit Account Code
5 – Communicate FTC Events
384 Communicator Backup Options
2 – Backup Options - Receiver 2
✔
3 – Backup Options - Receiver 3
4 – Backup Options - Receiver 4
385 Audio Module Talk/Listen Mask
1 – Talk/Listen on Phone Number
1
2 – Talk/Listen on Phone Number
2
3 – Talk/Listen on Phone Number
3
4 – Talk/Listen on Phone Number
4
DLS Programming
401 DLS/SA Options
1 – Double Call (C ✔)
2 – User Enables DLS ✔(C off)
3 – DLS Callback
4 – User Call Up
6 – Panel Call-Up and Baud Rate
7 – Alt. Comm DLS ✔
402 DLS Phone Number
Programming (31-digit decimal)
403 DLS Access Code (default is
based on model)
HS2128 Models ()
HS2064 Models ()
HS2032 Models ()
HS2016 Models ()
404 DLS/SA Panel ID (default is
based on model)
HS2128 Models (2128000000)
HS2064 Models (2064000000)
HS2032 Models (2032000000)
HS2016 Models (2016000000)
405 PSTN Double Call Timer (060
sec.)
406 PSTN Number of Rings to
Answer On (000)(TIS008)
407 SA Access Code (FFFFFF)
- 15 -
✔= Default

PowerSeries Neo Installation Guide
410 Automatic DLS Options
001 – Automatic DLS Toggle
Options
1 – Periodic DLS
3 – DLS on Event Buffer 75%
Full
8 – DLS On Programming
Change
002 – Periodic DLS Days (000
days)
003 – Periodic DLS Time (0000)
007 – Delay Call Window
– Delay Call Window Start
(0000)
– Delay Call Window End
(0000)
560 Virtual Inputs (000)
001 - 032 – Virtual Input 1-32
Schedule Programming
601-604 Programming Schedule 1-4
101 – Interval 1 Start Time (0000)
102 – Interval 1 End Time (0000)
103 – Interval 1 Days Assignment
01 – Sunday
02 – Monday
03 – Tuesday
04 – Wednesday
05 – Thursday
06 – Friday
07 – Saturday
104 – Interval 1 Holiday
Assignment
09 – Holiday 1
10 – Holiday 2
11 – Holiday 3
12 – Holiday 4
201 – Interval 2 Start Time (0000)
202 – Interval 2 End Time (0000)
203 – Interval 2 Days Assignment
01 – Sunday
02 – Monday
03 – Tuesday
04 – Wednesday
05 – Thursday
06 – Friday
07 – Saturday
204 – Interval 2 Holiday
Assignment
09 – Holiday 1
10 – Holiday 2
11 – Holiday 3
12 – Holiday 4
301 – Interval 3 Start Time (0000)
302 – Interval 3 End Time (0000)
303 – Interval 3 Days Assignment
01 – Sunday
02 – Monday
03 – Tuesday
04 – Wednesday
05 – Thursday
06 – Friday
07 – Saturday
304 – Interval 3 Holiday
Assignment
09 – Holiday 1
10 – Holiday 2
11 – Holiday 3
12 – Holiday 4 201 – Interval
2 Start Time (0000)
402 – Interval 4 End Time (0000)
403 – Interval 4 Days Assignment
01 – Sunday
02 – Monday
03 – Tuesday
04 – Wednesday
05 – Thursday
06 – Friday
07 – Saturday
404 – Interval 4 Holiday
Assignment
09 – Holiday 1
10 – Holiday 2
11 – Holiday 3
12 – Holiday 4
711-714 Holiday Group 1-4
001 – 099 Holiday Group 1-4 Date
1-99 (000000, MMDDYY)
Audio Station Programming
802 Audio Station Assignment
001 - 128 – Station Assignment 1 -
128 (00)
600 – 2-Way Audio Trigger Option
1
01 – Tampers
03 – [A] Key Alarm ✔
04 – [P] Key Alarm ✔
05 – Duress Alarm ✔
06 – Opening After Alarm ✔
07 – Future Use
08 – Zone Supervision Alarm
603 – 2-Way Audio Control Option
1
01 – Future Use
02 – Listen to all zones /
Listen to zones in alarm ✔
03 – Future Use
04 – Siren Active During 2-
Way Audio
05 – Hang-Up Auto Detection
06 – User Call-In
07 – Future Use
08 – 2-Way Audio Initiated by
CS ✔
605 – Record Options
01 – Audio Capture Enable ✔
02 – Erase on FTC
606 – Audio Station Record
Control Option 1
01 – Audio Station 1 Record
✔
02 – Audio Station 2 Record
✔
03 – Audio Station 3 Record
✔
04 – Audio Station 4 Record
✔
610 – Call Back / Recovery
Window Duration (05)
611 – Call Back Acknowledge
code (9999)
612 – Answering Machine Bypass
(00)
613 – Double Call Timer (030)
614 – Number of Rings to Answer
(00)
615 – Audio Duration (90 sec.)
616 – Record Time (105 sec.)
617 – Erase Timer (15 min.)
606 – Audio Station Tamper
Option 1
01 – Audio Station 1 Tamper
02 – Audio Station 2 Tamper
03 – Audio Station 3 Tamper
04 – Audio Station 4 Tamper
Wireless Programming
804 Wireless Programming
000 – WLS Device Enrollment
Zones (3-digit decimal)
Zone Type (2-digit decimal)
Partition Assignment
Zone Label (LCD only)
WLS Keys
Partition Assignment
User Assignment
Sirens
Partition Assignment
Siren Label (LCD only)
Keypads
Keypad Assignment
Keypad Label (LCD only)
Repeaters
Repeater Label (LCD only)
001 - 128 – Configure Wireless
Zones
Refer to the installation instructions
provided with the HSM2Host for
more wireless programming
options.
850 Cellular Signal Strength
851 Alternate Communicator
Programming
Refer to the installation instructions
provided with the alternate
communicator for details.
Keypad Programming
860 Keypad Slot Number
861-876 Keypad Programming
000 – Keypad Partition Mask
00 – Global Keypad
01 – Partition 1 ✔
02 – Partition 2
03 – Partition 3
04 – Partition 4
05 – Partition 5
06 – Partition 6
07 – Partition 7
08 – Partition 8
001 – Function Key 1 ()
002 – Function Key 2 ()
003 – Function Key 3 (06)
004 – Function Key 4 (22)
005 – Function Key 5 ()
00 – Null Key
02 – Instant Stay Arm
03 – Stay Arm
04 – Away Arm
05 – No Entry Arm
06 – Chime On/Off
07 – System Test
09 – Night Arm
12 – Global Stay Arm
13 – Global Away Arm
14 – Global Disarming
16 – Quick Exit
17 – Arm Interior
21-24 – Command Output 1-4
29 – Bypass Group Recall
31 – Local PGM Activate
32 – Bypass Mode
33 – Bypass recall
34 – User Programming
35 – User Functions
37 – Time/Date Programming
39 – Trouble Display
40 – Alarm Memory
61-68 – Partition Select 1-8
011 – Keypad I/O (000)
012 – Local PGM Output Timer
Pulse Time (00 minutes)
Pulse Time (05 sec.)
021 – Keypad Option 1
1 – [F] Key Enabled ✔
2 – [M] Key Enabled ✔
3 – [P] Key Enabled ✔
4 – Display Code or X's ✔
022 – Keypad Option 2
1 – Local Clock Display ✔
2 – Local Clock Display 24 Hour
3 – Auto Alarm Scroll ✔
5 – Power LED Option ✔
6 – Power LED AC Present ✔
7 – Alarms Displayed if Armed ✔
8 – Auto Scroll Open Zones ✔
023 – Keypad Option 3
1 – Armed LED Power Save*
2 – Keypad Show Arm Mode ✔*
3 – 5th Terminal is PGM
Output/Zone
4 – Prox Tag Arm/Disarm
7 – Local Display of Temp.
8 – Low Temperature Warning
030 – LCD Message (16 x 2 hex )
031 – Download LCD Message
Duration (000)
041 – Indoor Temperature Zone
Entry (000)
042 – Outdoor Temperature Zone
Entry (000)
101-228 – Door Chime Sound-Zone
1-128
00 – Disabled
01 – 6 beeps ✔
02 – "Bing-Bong" Sound
03 – "Ding-Dong" Sound
04 – Alarm Tone
05 – Zone Name
899 Template Programming
– 5-Digit Template Code (5-digit
decimal)
– Central Station Telephone
Number (32-digit decimal)
– Central Station Account Code
(4/6-digit decimal)
– Partition Account Code (4-digit
decimal)
- 16 -
✔= Default

PowerSeries Neo Installation Guide
– DLS Access Code (6-digit
decimal)
– Partition Entry Delay (000-255
sec.)
– Partition Exit Delay (000-255
sec.)
– Installer Code
System Information and
Testing
900 System Information
000 – Control Panel Version
001- 016 – Keypad 1-16 Version
Info
101-116 – 8-HSM2108 1-16
Version Info
201-216 – HSM2208 Version
Information
460 – Alternate Communicator
461 – HSM2HOST Version Info
481 – HSM2955 Version Info
501 – 504 HSM2300 1-4 Version
Info
521 – 524 HSM2204 1-4 Version
Info
901 Installer Walk Test
Module Programming
902 Add/Remove Modules
000 – Auto-Enroll All Modules
001 – Enroll Modules
002 – Slot Assignment
003 – Edit Module Slot Assignment
101 – Delete Keypads
102 – Delete HSM2108
103 – Delete HSM2208
106 – Delete HSM2HOST
108 – Delete HSM2955
109 – Delete HSM2300
110 – Delete HSM2204
903 Confirm Modules
000 – View All Modules
101 – Keypads
102 – HSM2108
103 – HSM2208
106 – HSM2HOST
108 – Confirm HSM2955
109 – HSM2300
110 – HSM2204
904 Wireless Placement Test
001-128 – Placement Test Zones
1-128
521-528 – Placement Test
Repeaters 1-28
551-566 – Placement Test Sirens
1-16
601-632 – Placement Test
Wireless Keys 1-32
701-716 – Placement Test
Wireless Keypads 1-16
912 Soak Test
000 – Zone Soak Test Duration
Default: 014
001-128 – Zone Soak Test - Zones
1-128
Battery Settings
982 Battery Settings
000– Panel Battery Settings
01– Panel High Charge
Current (SA✔)(FRA ✔)
(UK ✔)
010 – HSM2204 Battery Settings
01 – HSM2204 1 High Charge
Current (SA✔)(FRA ✔)
(UK ✔)
02 – HSM2204 2 High Charge
Current (SA✔)(FRA ✔)
(UK ✔)
03 – HSM2204 3 High Charge
Current (SA✔)(FRA ✔)
(UK ✔)
04 – HSM2204 4 High Charge
Current (SA✔)(FRA ✔)
(UK ✔)
020 – HSM2300 Battery Settings
01 – HSM2300 1 Charge
(SA✔)(FRA ✔)(UK ✔)
02 – HSM2300 2 Charge
(SA✔)(FRA ✔)(UK ✔)
03 – HSM2300 3 Charge
(SA✔)(FRA ✔)(UK ✔)
04 – HSM2300 4 Charge
(SA✔)(FRA ✔)(UK ✔)
Defaults
989 Default Master Code
990 Installer Lockout Enable/Disable
991 Default Keypads
901-916 – Default Keypad 1-16
999 – Default all Keypads
993 Default Alt Comm
996 Default HSM2HOST
998 Default HSM2955
999 Default System
* Wireless keypads only
- 17 -
✔= Default

PowerSeries Neo Installation Guide
Zone Record
Zone Label Location Type Attribute Zone Label Location Type Attribute
001 002
003 004
005 006
007 008
009 010
011 012
013 014
015 016
017 018
019 020
021 022
023 024
025 026
027 028
029 030
031 032
033 034
035 036
037 038
039 040
041 042
043 044
045 046
047 048
049 050
051 052
053 054
055 056
057 058
059 060
061 062
063 064
065 066
067 068
069 070
071 072
073 074
075 076
077 078
079 080
081 082
083 084
085 086
087 088
089 090
091 092
093 094
095 096
097 098
- 18 -

PowerSeries Neo Installation Guide
Zone Label Location Type Attribute Zone Label Location Type Attribute
099 100
101 102
103 104
105 106
107 108
109 110
111 112
113 114
115 116
117 118
119 120
121 122
123 124
125 126
127 128
Module Record
Module Type Slot Serial Number Module Type Slot Serial Number
Wireless Device Record
Device Type Zone Serial Number Device Type Zone Serial Number
Installer-Defined Access Codes
001 – Installer Code:
002 – Master Code:
003 – Maintenance Code:
System Account Code
- 19 -

PowerSeries Neo Installation Guide
Locating Detectors and Escape Plan
The following information is for general guidance only and it is recommended that local
fire codes and regulations be consulted when locating and installing smoke and CO
alarms.
Smoke Detectors
Research has shown that all hostile fires in homes generate smoke to a greater or lesser
extent. Experiments with typical fires in homes indicate that detectable quantities of
smoke precede detectable levels of heat in most cases. For these reasons, smoke alarms
should be installed outside of each sleeping area and on each storey of the home.
The following information is for general guidance only and it is recommended that local
fire codes and regulations be consulted when locating and installing smoke alarms.
It is recommended that additional smoke alarms beyond those required for minimum
protection be installed. Additional areas that should be protected include: the basement;
bedrooms, especially where smokers sleep; dining rooms; furnace and utility rooms; and
any hallways not protected by the required units. On smooth ceilings, detectors may be
spaced 9.1m (30 feet) apart as a guide. Other spacing may be required depending on
ceiling height, air movement, the presence of joists, uninsulated ceilings, etc. Consult
National Fire Alarm Code NFPA 72, CAN/ULC-S553-02 or other appropriate national
standards for installation recommendations.
lDo not locate smoke detectors at the top of peaked or gabled ceilings; the
dead air space in these locations may prevent the unit from detecting smoke.
lAvoid areas with turbulent air flow, such as near doors, fans or windows.
Rapid air movement around the detector may prevent smoke from entering the
unit.
lDo not locate detectors in areas of high humidity.
lDo not locate detectors in areas where the temperature rises above 38ºC
(100ºF) or falls below 5ºC (41ºF).
lSmoke detectors should always be installed in USA in accordance with
Chapter 11 of NFPA 72, the National Fire Alarm Code: 11.5.1.1.
Where required by applicable laws, codes, or standards for a specific type of occupancy,
approved single- and multiple-station smoke alarms shall be installed as follows:
1. In all sleeping rooms and guest rooms.
2. Outside of each separate dwelling unit sleeping area, within 6.4 m (21 ft) of any
door to a sleeping room, the distance measured along a path of travel.
3. On every level of a dwelling unit, including basements.
4. On every level of a residential board and care occupancy (small facility), including
basements and excluding crawl spaces and unfinished attics.
5. In the living area(s) of a guest suite.
6. In the living area(s) of a residential board and care occupancy (small facility).
Figure 1
Figure 2 Figure 3
Figure 3a Figure 4
Fire Escape Planning
There is often very little time between the detection of a fire and the time it becomes
deadly. It is thus very important that a family escape plan be developed and rehearsed.
1. Every family member should participate in developing the escape plan.
2. Study the possible escape routes from each location within the house. Since
many fires occur at night, special attention should be given to the escape
routes from sleeping quarters.
3. Escape from a bedroom must be possible without opening the interior door.
Consider the following when making your escape plans:
lMake sure that all border doors and windows are easily opened. Ensure that
they are not painted shut, and that their locking mechanisms operate smoothly.
lIf opening or using the exit is too difficult for children, the elderly or han-
dicapped, plans for rescue should be developed. This includes making sure
that those who are to perform the rescue can promptly hear the fire warning
signal.
lIf the exit is above the ground level, an approved fire ladder or rope should be
provided as well as training in its use.
lExits on the ground level should be kept clear. Be sure to remove snow from
exterior patio doors in winter; outdoor furniture or equipment should not
block exits.
lEach person should know the predetermined assembly point where everyone
can be accounted for (e.g., across the street or at a neighbor's house). Once
everyone is out of the building, call the fire department.
lA good plan emphasizes quick escape. Do not investigate or attempt to fight
the fire, and do not gather belongings as this can waste valuable time. Once
outside, do not re-enter the house. Wait for the fire department.
lWrite the fire escape plan down and rehearse it frequently so that should an
emergency arise, everyone will know what to do. Revise the plan as con-
ditions change, such as the number of people in the home, or if there are
changes to the building’s construction.
lMake sure your fire warning system is operational by conducting weekly tests.
If you are unsure about system operation, contact your installer.
lWe recommend that you contact your local fire department and request further
information on fire safety and escape planning. If available, have your local
fire prevention officer conduct an in-house fire safety inspection.
Figure 5
Carbon Monoxide Detectors
Carbon monoxide is colorless, odorless, tasteless, and very toxic, it also moves freely in
the air. CO detectors can measure the concentration and sound a loud alarm before a
potentially harmful level is reached. The human body is most vulnerable to the effects of
CO gas during sleeping hours; therefore, CO detectors should be located in or as near as
possible to sleeping areas of the home. For maximum protection, a CO alarm should be
located outside primary sleeping areas or on each level of your home. Figure 5 indicates
the suggested locations in the home.
Do NOT place the CO alarm in the following areas:
lWhere the temperature may drop below -10ºC or exceed 40ºC
lNear paint thinner fumes
lWithin 5 feet (1.5m) of open flame appliances such as furnaces, stoves and fire-
places
lIn exhaust streams from gas engines, vents, flues or chimneys
lIn close proximity to an automobile exhaust pipe; this will damage the
detector
PLEASE REFER TO THE CO DETECTOR INSTALLATION AND OPERATING
INSTRUCTION SHEET FOR SAFETY INSTRUCTIONS AND EMERGENCY
INFORMATION.
- 20 -
This manual suits for next models
21
Table of contents
Other DSC Security System manuals

DSC
DSC Neo User manual

DSC
DSC PC1575 User manual

DSC
DSC Power 832 PC5010 User manual

DSC
DSC PowerSeries PC1404 User manual

DSC
DSC Power8 PC5OO5 User manual

DSC
DSC MAXSYS PC4020 User manual

DSC
DSC 3G2055 User manual

DSC
DSC PowerSeries PC1404 V1.1 User manual

DSC
DSC PDigital Security PC1565 User manual

DSC
DSC PC4020 - 2 User manual

DSC
DSC PC1832 series Owner's manual

DSC
DSC WLS920 User manual

DSC
DSC Digital Security Control PC158O User manual

DSC
DSC PC5010 V2.0 User manual

DSC
DSC Power832 PC5010 User manual

DSC
DSC PowerSeries PC1832 User manual

DSC
DSC TL260 User manual

DSC
DSC PC5020 Power864 User manual

DSC
DSC Power832 User manual

DSC
DSC PC1500 User manual