EVCOS.p.A.|EVJH95|Instructionsheetver.1.0|Code104JH95E103|Page2of3|PT04/22
6.3 Activating the overboost function
Check that the keypad isn’t locked.
1. Touch the DOWN key for 1 s: the display will show a code.
2. Touch the UP or DOWN key within 15s to select “ObS”.
3. Touch the SET key.
4. Touch the ON/STAND-BY key (or take no action for 60s) to exit
the procedure.
6.4 Displaying the operating mode
Check that the keypad is not locked.
1. Touch the DOWN key: the display will show a code.
COD. DESCRIPTION
ECO economy
ObS overboost
Auto comfort
Anti
anti-legionella; if flashing, DHW tank lower temperature > “SP1 setpoint” and
> “SP2 setpoint”
dEFr defrost
in2 photovoltaic function
2. Touch the ON/STAND-BY key (or take no action for 60s) to exit
the procedure.
6.5 Displaying/deleting compressor functioning hours
Check that the keypad is not locked.
1. Touch the DOWN key for 1 s: the display will show a code.
2. Touch the UP or DOWN key within 15s to select a label.
COD. DESCRIPTION
CH display compressor working hours in hundreds
rCH delete compressor working hours
3. Touch the SET key.
4. Touch the UP or DOWN key to set “149” (to select rCH).
5. Touch the SET key.
6. Touch the ON/STAND-BY key (or take no action for 60s) to exit
the procedure.
7 SETTINGS
7.1 Setting configuration parameters
1. Touch the SET key for 4 s: the display will show the label “PA”.
2. Touch the SET key.
3. Touch the UP or DOWN key within 15s to set -19”.
4. Touch the SET key (or take no action for 15s): the display will
show the label “SP”.
5. Touch the UP or DOWN key to select a parameter.
6. Touch the SET key.
7. Touch the UP or DOWN key within 15s to set the value.
8. Touch the SET key (or take no action for 15s).
9. Touch the SET key for 4s (or take no action for 60s) to exit the
procedure.
7.2 Set the date, time and day of the week (if module EVIF23TSX, EVIF25TWX or
interface EVIF25TBX is connected)
N.B.
- Do not disconnect the device from the mains within two minutes since the setting
of the time and day of the week.
- if the device communicates with the EVconnect app, the date, time and day of the
week will be automatically set by the smartphone or tablet.
Check that the keypad is not locked.
1. Touch the UP key.
2. Touch the UP or DOWN key within 15s to select the label “rtc”.
3. Touch the SET key: the display will show the label “yy” followed
by the last two figures of the year.
4. Touch the UP or DOWN key within 15 s to set the year.
5. Repeat actions 3. and 4. to set the next labels.
LAB. DESCRIPTION OF THE NUMBERS FOLLOWING THE LABEL
n month (01… 12)
d day (01… 31)
h time (00… 23)
n minute (00… 59)
6. Touch the SET key: the display will show the label for the day of
the week.
7. Touch the UP or DOWN key within 15 s to set the day of the
week.
LAB. DESCRIPTION
Mon Monday
tuE Tuesday
UEd Wednesday
thu Thursday
Fri Friday
Sat Saturday
Sun Sunday
8. Touch the SET key: the device will exit the procedure.
9. Touch the ON/STAND-BY key to exit the procedure beforehand.
7.3 Restoring factory settings (default)
N.B.
- check that the factory settings are appropriate; see the section CONFIGURATION
PARAMETERS.
1. Touch the SET key for 4 s: the display will show the label “PA”.
2. Touch the SET key.
3. Touch the UP or DOWN key within 15s to set “149”.
4. Touch the SET key (or take no action for 15s): the display will
show the label “dEF”.
5. Touch the SET key.
6. Touch the UP or DOWN key within 15s to set “1”.
7.
Touch the SET key (or take no action for 15 s): the display will
show “- - -” flashing for 4 s, after which the device will exit the
procedure.
8. Disconnect the device from the power supply.
9. Touch the SET key for 1s before action 6 to exit the procedure
beforehand.
8 CONFIGURATION PARAMETERS
No. PAR. DEF. SETPOINT MIN... MAX.
1 SP1 52.0
setpoint in economy mode r3... r4
2 SP2 60.0
setpoint in comfort mode r1... r2
3 SP3 40.0
overboost activation threshold 10 °C/°F... r2
4 SP5 52.0
heat pump switch-off threshold r1... SP2
5 SP6 70.0
photovoltaic system setpoint 40... 100 °C/°F
6 SP7 5.0 setpoint in antifreeze mode 0... 40 °C/°F
7 SP8 40.0
setpoint in green mode 0... 100 °C/°F
8 SP9 -7.0 cold evaporator alarm threshold -25... 25 °C/°F
9
SPA
-25
evaporator failure alarm
threshold -50... 25 °C/°F
No. PAR. DEF. ANALOGUE INPUTS MIN... MAX.
10 CA1 0.0 DHW tank upper probe offset -25... 25 °C/°F
11 CA2 0.0 DHW tank lower probe offset -25... 25 °C/°F
12 CA3 0.0 evaporator probe offset -25... 25 °C/°F
13
P0
1
type of probe
0 = PTC 1 = NTC
2 = Pt 1000
14 P1 1 enable decimal point °C 0 = no 1 = yes
15 P2 0 temperature measurement unit 0 = °C 1 = °F
16
P3
1
enabled probes
0 = DHW tank upper probe
+ high pressure input
1 = DHW tank upper and
lower probe
17
P4
2
evaporator probe function
0 = disabled (defrost every
d18 minutes)
1 = defrost activation and
defrost end
2 = defrost activation
18
P5
0
value displayed
0 = DHW tank upper
temperature
1 = setpoint in comfort
mode
2 = DHW tank lower
temperature
3 = evaporator temperature
19 P8 5 display refresh time 0... 250 s: 10
No. PAR. DEF. REGULATION MIN... MAX.
20 r0 2.0 setpoint differential 1... 30 °C/°F
21
r1
20.0
minimum setpoint in comfort
mode 10 °C/°F... r2
22
r2
60.0
maximum setpoint in comfort
mode r1... 100 °C/°F
23
r3
20.0
minimum setpoint in economy
mode 10 °C/°F... r4
24
r4
52.0
maximum setpoint in economy
mode r3... 100 °C/°F
25
r5
0
enable setpoint blocking in
economy and comfort modes 0 = no 1 = yes
26
r6
0.0
heater threshold in comfort
mode 0... 50 °C/°F
27
r7
15.0
heater threshold differential in
comfort mode 1... 30 °C/°F
28
r8
20.0
support heater threshold
differential in comfort mode r7... 30 °C/°F
No. PAR. DEF. COMPRESSOR MIN... MAX.
29
C0
3
compressor on delay from
power-on 0... 240 min
30
C1
3
minimum time between two
power-ons of compressor 0... 240 min
31 C2 3 minimum compressor-off time 0... 240 min
32 C3 0 minimum compressor-on time 0... 240 s
33
C10
0
compressor hours for
maintenance 0... 999 h x 100
0 = disabled
34
C11
120
interval for cold evaporator
control 0... 999 min
35
C12
60
compressor-on delay from fan
on for cold evaporator control 0... 240 s
36
C13
20
compressor-on delay from green
multi-purpose input reset 0... 240 min
37
C14
20
compressor-on consecutive time
for evaporator failure control -1... 240 min
-1 = disabled
No. PAR. DEF. DEFROST MIN... MAX.
38
d1
3
type of defrost
0 = electric
1 = hot gas
2 = compressor stopped
3 = hot gas balancing the
pressure
39 d2 3.0 defrost end threshold -50... 50 °C/°F
40
d3
3
defrost duration
0... 99 min
0 = defrost disabled
If P4 = 1, maximum duration
41
d17
-2.0
evaporation threshold for defrost
interval count -50... 50 °C/°F
42
d18
30
defrost interval
0... 240 min
0 = manual only
No. PAR. DEF. ALARMS MIN... MAX.
43
A0
0
select value for low temperature
alarm
0 = DHW tank upper
temperature
1 = DHW tank lower
temperature
2 = evaporator temperature
44 A1 10.0
low temperature alarm threshold
0... 50 °C/°F
45
A2
0
low temperature alarm type
0 = disabled
1 = absolute
46
A3
0
select value for high
temperature alarm
0 = DHW tank upper
temperature
1 = DHW tank lower
temperature
2 = evaporator temperature
47
A4
75.0
high temperature alarm
threshold 0... 199 °C/°F
48
A5
1
high temperature alarm type
0 = disabled
1 = absolute
49
A6
1
high temperature alarm delay
from power-on 0... 240 min
50
A7
15
high/low temperature alarm
delay 0... 240 min
51
A10
0
power failure duration for alarm
recording 0... 240 min
52
A11
10.0
high/low temperature alarm
reset differential 1... 30 °C/°F
No. PAR. DEF. FAN MIN... MAX.
53 F0 1 enable fan 0 = no 1 = yes
No. PAR. DEF. ANTI-LEGIONELLA MIN... MAX.
54
H0
30
anti-legionella interval
0... 99 d (days)
0 = none
55 H1 65.0
anti-legionella thermal threshold 10... 199 °C/°F
56
H3
2
anti-legionella thermal threshold
maintenance duration 0... 240 min
0 = function disabled
No. PAR. DEF. DIGITAL INPUTS MIN... MAX.
57
i0
1
multi-purpose input function
0 = disabled
1 = pressure switch
2 = green
58
i2
5
compressor-on delay from
pressure switch alarm reset 0... 120 min
59 i3 1 enable photovoltaic system 0 = no 1 = yes
60
i4
0
photovoltaic system input
activation 0 = with contact closed
1 = with contact open
61
i5
0
high pressure input activation
0 = with contact closed
1 = with contact open
62
i8
3
number of pressure switch
alarms for unit blocked alarm 0... 15
0 = disabled
63
i9
240
counter reset time for pressure
switch alarms 1... 999 min
64
i10
24
pressure switch alarm delay
from compressor-on 0... 240 sx10
65
i11
60
time pre opening hot gas defrost
valve 0... 240 s
66
i12
0
fan off during pressure
switch/unit blocked alarm 0 = no 1 = yes
No. PAR. DEF. DIGITAL OUTPUTS MIN... MAX.
67
u1
0
relay K5 configuration
0 = disabled
1 = circulation pump
2 = support heaters
68
u2
60
compressor on delay from
circulation pump on and
circulation pump off delay from
compressor off
0... 240 s
0 = on if device on
69 u9 1 enable alarm buzzer 0 = no 1 = yes
N. PAR. DEF. CLOCK MIN... MAX.
70 Hr0 0 enable clock 0 = no 1 = yes
71
Hd1
1
time for switch on on Monday
1 = with On1 e OF1
2 = with On2 e OF2
72
Hd2
1
time for switch on on Tuesday
1 = with On1 e OF1
2 = with On2 e OF2
73
Hd3
1
time for switch on on
Wednesday 1 = with On1 e OF1
2 = with On2 e OF2
74
Hd4
1
time for switch on on Thursday
1 = with On1 e OF1
2 = with On2 e OF2
75
Hd5
1
time for switch on on Friday
1 = with On1 e OF1
2 = with On2 e OF2
76
Hd6
2
time for switch on on Saturday
1 = with On1 e OF1
2 = with On2 e OF2
77
Hd7
2
time for switch on on Sunday
1 = with On1 e OF1
2 = with On2 e OF2
78
HOn1
- - -
time for time band 1 on
00:00... 23:59 h:min
00:00 = disabled
79
HOF1
- - -
time for time band 1 off
00:00... 23:59 h:min
00:00 = disabled
80
HOn2
- - -
time for time band 2 on
00:00... 23:59 h:min
00:00 = disabled
81
HOF2
- - -
time for time band 2 off
00:00... 23:59 h:min
00:00 = disabled
82
Ant
- - -
time anti-legionella on
00:00... 23:59 h:min
00:00 = disabled
N. PAR. DEF. SAFETIES MIN... MAX.
83 PA1 426 level 1 password -99... 999
84 PA2 824 level 2 password -99... 999
N. PAR. DEF. DATA-LOGGING EVLINK MIN... MAX.
85
bLE
1
enable Bluetooth
0 = no 1 = sì
>1 reserved
86 rE0 15 data-logger sampling interval 0... 240 min
87
rE1
1
recorded temperature
0 = nessuna
1 = DHW tank upper
2 = DHW tank lower
3 = evaporator
4 = DHW tank upper and
lower
5 = tutte
N. PAR. DEF. MODBUS MIN... MAX.
88 LA 247 MODBUS address 1... 247
89
Lb
2
MODBUS baud rate
0 = 2.400 baud
1 = 4.800 baud
2 = 9.600 baud
3 = 19.200 baud
90
LP
2
parity
0 = none 1 = odd
2 = even
9 ALARMS
CODE
DESCRIPTION RESET TO CORRECT
Pr1
DHW tank upper probe
alarm automatic
- check P0
- check probe integrity
- check electrical connection
Pr2
DHW tank lower probe
alarm automatic
Pr3 evaporator probe alarm automatic
rtc clock alarm manual set date, time and day of the week
AL low temperature alarm automatic check A0, A1 and A2
AH high temperature alarm automatic check A3, A4 and A5
PF
power failure alarm
manual
- touch a key
- check electrical connection
LHP
pressure switch/unit
blocked alarm automatic/
manual - switch the device off and on
- check i0, i8 and i9
HP
high pressure alarm
manual
- switch the device off and on
- check P3
FiL
compressor maintenance
alarm
automatic
check C10
by silencing the buzzer you delete the
compressor functioning hours
UtL
evaporator failure alarm
manual
- switch the device off and on
- check SPA and C14
10 TECHNICAL SPECIFICATIONS
Purpose of the control device
Function controller
Construction of the control device
Built-in electronic device
Container black, self-extinguishing.
Category of heat and fire resistance
D
Mounting methods for the control device
front installation on a plastic or metal panel
(with elastic holding flaps)
Degree of protection provided by the
covering
IP65 (front)
Connection method
Fixed screw terminal blocks for wires up to
2.5 mm² (removable screw terminal blocks
for wires up to 2,5 mm² by request)
Pico-Blade connector
Maximum permitted length for connection cables
Power supply: 10 m (32.8 ft)
Analogue inputs: 10 m (32.8 ft)
Digital inputs: 10 m (32.8 ft) Digital outputs: 10 m (32.8 ft)
Operating temperature
From -5 to 55 °C (from 23 to 131 °F)
Storage temperature
From -25 to 70 °C (from -13 to 158 °F)
Operating humidity
Relative humidity without condensate from
10 to 90%
Pollution status of the control device
2
Conformity
RoHS 2011/65/CE
WEEE 2012/19/EU
REACH (EC) Regulation
1907/2006
EMC 2014/30/UE LVD 2014/35/UE
Power supply
115... 230 VAC (+10% -15%), 50/60 Hz (±3
Hz), max. 6 VA insulated
Earthing methods for the control device
None
Rated impulse-withstand voltage
2.5 KV
Over-voltage category
II
Software class and structure
A
Analogue inputs
2 for PTC, NTC or Pt 1000 probes (DHW tank
upper probe and evaporator probe)
PTC probes
Sensor type
KTY 81-121 (990 @ 25 °C, 77 °F)
Measurement field
From -50 to 150 °C (from -58 to 302 °F)
Resolution
0.1 °C (1 °F)
NTC probes
Sensor type
ß3435 (10 K@ 25 °C, 77 °F)
Measurement field
From -40 to 105 °C (from -40 to 221 °F)