iIn installation positions that are not easily accessible, turn the operating mode switch to
position PC after commissioning and performing a function test. Subsequent changes to
the device settings can thus be carried out with the aid of the eNet-Server without involving
excessive installation work.
oMount the cover.
5.2 Commissioning
DANGER!
Electrical shock when live parts are touched.
Electrical shocks can be fatal.
During commissioning, cover the parts carrying voltage on radio transmitters
and actuators and in their surrounding area.
iThe actuator can also be commissioned with eNet server as an alternative to the
commissioning described here.
Connecting actuator to radio transmitters
Load is switched off.
oPress the Prog button for longer than 4 seconds.
The load switches on.
The status LED flashes after 4 seconds and the load switches off. The actuator is in
programming mode for approx. 1 minute.
oSwitch radio transmitter to programming mode (see radio transmitter instructions).
oTrigger telegram on the radio transmitter.
The status LED of the actuator lights up for 5 seconds.
The actuator is connected to the radio transmitter. The actuator and radio transmitter exit
the programming mode automatically.
iIf the status LED of the actuator flashes 3 times at 1-second intervals for approx.
5 seconds, then the programming operation was not successful. All the memory locations
in the actuator or radio transmitter are occupied.
iAll On and All Off buttons of a radio transmitter are connected to the actuator automatically
as soon as the first connection to the radio transmitter takes place.
iScene buttons must be connected separately.
Disconnecting connection to a radio transmitter
oCarry out the same steps as when connecting (see Connecting actuator to radio
transmitters).
The status LED flashes quickly for 5 seconds. The actuator is disconnected from the radio
transmitter. The actuator and radio transmitter exit the programming mode automatically.
iIf there several connections or scene buttons for a radio transmitter, all connections must
be disconnected individually.
iAll On and All Off buttons of a radio transmitter are disconnected automatically as soon as
the last connection of the corresponding output to the radio transmitter is disconnected.
Manual disconnection is not possible.
Resetting the device to the factory setting
All connections to radio transmitters are disconnected and parameters are reset to default
setting. If the operating mode switch is on PC, the operating mode switching is set.
iThe connections in the radio transmitters are preserved and must be deleted separately.
Load is switched off.
oPress the Prog button for at least 20 seconds.
The load switches on.
The status LED flashes after 4 seconds and the load switches off. The status LED flashes
faster after 20 seconds.
32581212 10499450 09.05.2016 5/11
eNet
Wireless switching/momentary-contact actuator, 1-gang Mini, Wireless
switching/momentary-contact actuator, 1-gang Mini, zero-voltage