HBM MP70DP User manual

A0658-7.2 en
Profibus interface
for the PME
MP70DP
MP70DPS7,
MP70S7
Operating manual


3
PME-MP70DP
HBMA0658-7.2 en
Contents Page
Safety instructions 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1 Introduction 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1 Scope of supply and accessories 10. . . . . . . . . . . . . . . . . . . . . . . . . .
1.2 General information on MP70DP and variants 10. . . . . . . . . . . . . . .
2 Select amplifier settings with DIP switches 12. . . . . . . . . . . . . . . . . . . .
3 Mounting/dismounting the MP70DP 15. . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1 Linking several modules 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4 Connections 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1 Functional overview of MP70DP 17. . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2 Supply voltage and control inputs/outputs 18. . . . . . . . . . . . . . . . . . .
4.2.1 External supply voltage for the control outputs 19. . . . . . . . . .
4.3 Profibus 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.4 CAN interface 20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.5 Synchronisation 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5 How to connect to a PLC 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.1 Configuring and assigning parameters 23. . . . . . . . . . . . . . . . . . . . . .
6 Putting into service 25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7 Setting up and operation (MP70DP) 27. . . . . . . . . . . . . . . . . . . . . . . . . . .
7.1 Operating philosophy 27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.2 Overview of all groups and parameters 30. . . . . . . . . . . . . . . . . . . . .
7.2.1 Setting all the parameters 31. . . . . . . . . . . . . . . . . . . . . . . . . . . .
8 Description of the essential parameters 35. . . . . . . . . . . . . . . . . . . . . . .
9 CAN interface description 41. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.1 General 41. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.2 Cyclical measured value transmission 41. . . . . . . . . . . . . . . . . . . . . .
9.3 Parameter assignment 42. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.4 Object directory: communications profile range
as per CAN-open (CiA-DS301) 44. . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.5 Object directory: manufacturer−specific objects 47. . . . . . . . . . . . . .

4PME-MP70DP
HBM A0658-7.2 en
9.6 Manufacturer−specific objects in FLOAT data format 56. . . . . . . . .
9.7 Examples 57. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10 Settings for Profibus 58. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10.1 Profibus parameter assignment 58. . . . . . . . . . . . . . . . . . . . . . . . . . . .
10.1.1 Parameters for the MP30, MP55, MP60, MP70 modules 59.
10.1.2 Parameters for module MP01 59. . . . . . . . . . . . . . . . . . . . . . . .
10.2 Profibus configuration 60. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10.2.1 Configuration for MP30, MP55, MP60, MP70 modules 61. . .
10.2.2 Configuration for module MP01 62. . . . . . . . . . . . . . . . . . . . . . .
10.3 Cyclical data exchange 63. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10.3.1 Inputs 63. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10.3.2 Outputs 64. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10.4 Profibus diagnosis 64. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10.5 Assigning parameters with decimal and hexadecimal
values 66. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10.5.1 Defining internal configuration combinations 67. . . . . . . . . . . .
11 Error messages/operational status (LED) 71. . . . . . . . . . . . . . . . . . . . . .
12 Keyword index 75. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5
PME-MP70DP
HBMA0658−7.2 en
Safety instructions
Before connecting the device, make sure that the mains voltage and current
type specified on the type plate correspond to the mains voltage and current
type at the site of installation and that the current circuit used is sufficiently
safe.
Due to the fact that the device has not been equipped with a proper
mains switch, the connected supply cable must not be directly
connected to the mains. The maximum permissible supply voltage is
18...30 V.
According to a VDE recommendation these devices must be equipped
with a switching device (e.g. with a mains switch) for disconnection
from the mains. Make sure, that the device can quickly be disconnected
from the mains at any time.
The supply connection, as well as the signal and sense leads, must be
installed in such a way that electromagnetic interference does not adversely
affect device functionality (HBM recommendation: ”Greenline shielding
design”, downloadable from the Internet at http://www.hbm.com/Greenline).
Automation equipment and devices must be covered over in such a way that
adequate protection or locking against unintentional actuation is provided
(such as access checks, password protection, etc.).
When devices are working in a network, these networks must be designed in
such a way that malfunctions in individual nodes can be detected and shut
down.
Safety precautions must be taken both in terms of hardware and software, so
that a line break or other interruptions to signal transmission, such as via the
bus interfaces, do not cause undefined states or loss of data in the
automation device.

6PME-MP70DP
HBM A0658−7.2 en
Appropriate use
The MP70DP module and its connected transducers may be used for mea-
surement tasks only and directly related control tasks. To ensure safe opera-
tion, the transducer may only be used as specified in the operating manual. It
is also essential to follow the respective legal and safety regulations for the
application concerned during use. The same applies to the use of accesso-
ries.
Each time, before starting up the equipment, you must first run a project
planning and risk analysis that takes into account all the safety aspects of
automation technology. This particularly concerns personal and machine
protection.
Additional safety precautions must be taken in plants where malfunctions
could cause major damage, loss of data or even personal injury. In the event
of a fault, these precautions establish safe operating conditions.
This can be done, for example, by mechanical interlocking, error signaling,
limit value switches, etc.
General dangers due to non-observance of the safety instructions
The MP70DP module complies with the state of the art and is safe to operate.
If the equipment is used and operated inappropriately by untrained personnel,
residual dangers may arise.
Anyone responsible for installing, starting up, maintaining or repairing the
equipment needs to have read and understood the operating manual and in
particular the safety instructions.
Conditions on site
Protect the devices from moisture or atmospheric influences such as rain,
snow, etc.
Protect the device from direct sunlight. Ensure sufficient ventilation.
Maintenance and cleaning
The MP70DP module is maintenance-free. Please note the following points
when cleaning the housing:
−Before cleaning, disconnect the devices from the power supply.
−Clean the housing with a soft, slightly damp (not wet!) cloth. You should
never use solvent, since this could damage the labelling on the front panel
and the display.
−When cleaning, ensure that no liquid gets into the device or connections.

7
PME-MP70DP
HBMA0658−7.2 en
Residual dangers
The scope of supply and list of components provided with the MP70DP cover
only part of the scope of measurement technique. In addition, equipment
planners, installers and operators should plan, implement and respond to the
safety engineering considerations of measurement technique in such a way
as to minimise residual dangers. Prevailing regulations must be complied with
at all times. Residual dangers connected with measurement technology need
to be pointed out.
Any risk of residual dangers when working with the MP70DP is pointed out in
this introduction by means of the following symbols:
Symbol: WARNING
Meaning: Dangerous situation
Warns of a potentially dangerous situation in which failure to comply with
safety requirements can result in death or serious bodily injury.
Symbol: CAUTION
Meaning: Possible dangerous situation
Warns of a potentially dangerous situation in which failure to comply with
safety requirements could result in damage to property or some form of
bodily injury.
Symbol: NOTE
Points out that important information about the product or its handling is being
given.
Symbol:
Meaning: Statutory marking requirements for waste disposal
National and local regulations regarding the protection of the environment and
recycling of raw materials require old equipment to be separated from regular
domestic waste for disposal.
For more detailed information on disposal, please contact the local authorities
or the dealer from whom you purchased the product.

8PME-MP70DP
HBM A0658−7.2 en
Symbol:
Meaning: CE mark
The CE mark enables the manufacturer to guarantee that the product
complies with the requirements of the relevant EC directives (the declaration
of conformity is available at http://www.hbm.com/HBMdoc).
Working safely
Error messages should only be acknowledged once the cause of the error is
removed and no further danger exists.
The device complies with the safety requirements of DIN EN 61010 Part 1
(VDE 0411 Part 1).
The device must be mounted on a support rail connected to grounded
conductor potential. Both the support rail and the MP70/MP70DP module
must be free of paint, varnish and dirt at the point of installation.
To ensure adequate immunity from interference, the bus cables (CAN an for
MP70DP, Profibus DP) must be shielded, twisted−pair lines. The transducer
cables must also be shielded. To ensure adequate immunity from
interference, use Greenline shielding only (conncect the shield of the
transducer cable to the plug housing).
The cables of the digital inputs and outputs of the MP70/MP70DP should not
be longer than 30 m or should they be routed outside the building where the
system is located. Otherwise proper functioning of the device cannot be
guaranteed. The effects of strong electromagnetic fields or lightning strike
could result in damage to the instrument.
When connecting cables (fitting and extracting terminals), measures must be
taken to prevent electrostatic discharge which could damage the electronics.
The MP70/MP70DP module must be operated with a separated extra−low
voltage (18...30 V DC supply voltage), which usually supplies one or more
consumers within a control cabinet.
Should the equipment be operated on a dc voltage network1), additional
precautions must be taken to discharge excess voltages.
1) Distribution system for electrical energy with greater physical expansion (over several control cabinets, for
example) that may possibly also supply consumers with high nominal (rated) currents.

9
PME-MP70DP
HBMA0658−7.2 en
Conversions and modifications
HBM’s express consent is required for modifications affecting the transdu-
cers’s design and safety. HBM does not take responsibility for damage resul-
ting from unauthorized modifications.
The product is delivered from the factory with a fixed hardware and software
configuration. Changes can only be made within the possibilities documented
in the manuals.
The product is delivered from the factory with a fixed hardware and software
configuration. Changes can only be made within the possibilities documented
in the manuals.
Qualified personnel
The equipment may be used by qualified personnel only; the specifications
and the special safety regulationsneed to be followed in all cases.
This means people who meet at least one of the three following requirements:
−Knowledge of the safety concepts of automation technology is a
requirement and as project personnel, you must be familiar with these
concepts.
−As automation plant operating personnel, you have been instructed how to
handle the machinery and are familiar with the operation of the equipment
and technologies described in this documentation.
−As commissioning engineers or service engineers, you have successfully
completed the training to qualify you to repair the automation systems.
You are also authorized to activate, to ground and label circuits and
equipment in accordance with safety engineering standards.
It is also essential to comply with the appropriate legal and safety regulations
for the application concerned during use. The same applies to the use of ac-
cessories.
Qualified personnel means personel familiar with the installation, fitting,
start−up and operation of the product, and trained according to their job.

10 PME-MP70DP
HBM A0658−7.2 en
1 Introduction
1.1 Scope of supply and accessories
Scope of supply:
D1 MP70DP or MP70DPS7 or MP707 module
D1x 6-pin terminal plug, coded
Order No.: 3.3312−0250
D10−pin ribbon cable connector
DAdditional spring for assembly of housing (enclosed in bag)
D1 Operating Manual module MP70DP / MP70DPS7 / MP70S7
Accessories:
DStandard ribbon cable, 10pin, 1.27 mm pitch
1.2 General information on MP70DP and variants
There are three different basic variants:
DMP70DP
DMP70DPS7
DMP70S7
MP70DP
The MP70DP module is a Profibus DP gateway for
measuring amplifiers of the PME family. As many as
8 measurement modules (MP01, MP30, MP55,
MP60) can be connected to the gateway.
Communication between the Profibus DP gateway
MP70DP and the modules is handled by the
integrated CAN interface. The modules are linked
together by a 10-pin ribbon cable (see Chapter 3.1
and Chapter 6). In addition to this, MP70DP has an
arithmetic function. The MP70DP forms the sum of
the gross values from a maximum of 8 input channels (measurement
modules). This value is used internally for further signal conditioning (peak
values, limit values). These variables are available both at the CAN-BUS and
the Profibus DP.

11
PME-MP70DP
HBMA0658−7.2 en
MP70DPS7
The MP70DPS7 module is an enhancement of the DP
version. An additional analogue output and four control
inputs and outputs respectively are available via
plug−in terminals.
MP70S7
The MP70S7 module corresponds to the MP70DPS7
described above, although the Profibus functions are
not available here.
Settings and parameters are assigned to the MP70DP module via the
keyboard and the display, or by using the PME Assistent. The PME Assistent
program provides a simple operator interface running under Windows for
assigning parameters to the modules (described in the ”PME Assistent” online
help).
μP
Keyboard & display
MP70DP
24 V
Voltage supply,
electrically isolated
Profibus DP
interface
Data interchange via the
CANopen interface
Up to 8 measurement channels
(MP01, MP30, MP55, MP60)
Scaleable analogu
e
output (only
MP70DPS7 and
MP70S7)
Control I/Os (only
MP70DPS7 and
MP70S7)
Fig. 1.1: Block diagram for the MP70DP module
Analogue output,
control inputs (terminal 3)
Control outputs (terminal 4)
No function
No function

12 PME-MP70DP
HBM A0658−7.2 en
2 Select amplifier settings with DIP switches
NOTE
The DIP switches must be set/adjusted before mounting the PME.
Various settings are defined by the DIP switches and can be read out on the
display (see Chapter 7.2). These are the settings for
synchronisation, bus terminating resistance and value of the slope
steepness
To set the DIP switches, you must proceed as shown in Fig. 2.1.
1
2
* for the analogue output with MP70DPS7 and MP70S7
S5
S10
S11*
S12
Unscrew the
cover
Fig. 2.1: Open housing, DIP switch location
123456
Example:
means
ON
Fig. 2.2: Switch convention

13
PME-MP70DP
HBMA0658−7.2 en
S10
123456
ON
3456
S10 S12
ON
S12
1
2
3
5
4
6
1
2
3
5
4
6
1
2
3
5
4
6
ON ON ON
Synchronisation
Switch positions must not be changed!
Amplifier type
Factory settings:
S11
3456
S12
ON
For module MP70S7
12
S11
ON
Analogue
output1)
ON
1
2
3
S5
123
ON
Analogue output1)
1) only for MP70DPS7 and MP70S7
WARNING

14 PME-MP70DP
HBM A0658−7.2 en
Synchronisation
123456
ON
S10
123456
ON
Master
Slave
S10
S10
S11
Analogue output1)
123456
ON
S11
123
ON
S5
"10V
mA
123456
ON
123
ON
123456
ON
mA
V
mA S5
S11
S11
S5
1) only for MP70DPS7 and MP70S7
S12
Fig. 2.3: Setting the amplifier (continued)
Terminating bus resistor
Toggle switch for termination resistor
(see page 21)
ON OFF
S14
Fig. 2.4: Toggle switch for termination resistor

15
PME-MP70DP
HBMA0658−7.2 en
3 Mounting/dismounting the MP70DP
Fig. 3.1: Mounting on a support rail
Fig. 3.2: Disassembly
CAUTION
The support rail must be connected to protective earth potential .

16 PME-MP70DP
HBM A0658−7.2 en
Fig. 3.3: Fitting of a second spring fore more stable mounting of the module on the
DIN rail
3.1 Linking several modules
1.
2.
3.
Colour−coding
at pin 1
Ribbon cable connector
recommended
distance for the
ribbon cable jack
connector
subsequent devices will be linked
together via this connector.
58 mm
Fig. 3.4: Connecting the ribbon cable
Several measurement modules (MP01, MP30, MP55, MP60) can be linked to
the MP70DP via a ribbon cable. This cable provides the local connection of
supply voltage and synchronisation between the modules. No more than eight
modules should be interlinked via a ribbon cable.

17
PME-MP70DP
HBMA0658−7.2 en
4 Connections
WARNING
Please note the safety instructions before putting into service the
device.
NOTE
Use standard HBM cable for the transducer connection. When using
other shielded, low-capacitance measuring cable, connect the
transducer cable shielding to the connector housing in accordance with
the HBM Greenline concept (Internet download
http://www.hbm.com/Greenline). This ensures EMC protection.
4.1 Functional overview of MP70DP
Plug−in terminal 1:
Voltage supply and CAN-BUS,
synchronisation
Touch−sensitive
control buttons
2 line LCD display
Plug−in terminal 2: (same assignment
as plug−in terminal 1)
CAN adapter for PC/laptop connection,
assigning parameters via the CAN-BUS
LED1)
Local connection of CAN-BUS, supply voltage and synchronisation between
the modules (max. 8 modules can be connected)
Profibus connection socket
1) with MP70DPS7 and MP70S7

18 PME-MP70DP
HBM A0658−7.2 en
4.2 Supply voltage and control inputs/outputs
The MP70DP has two removable plug−in terminals available for connections,
the S7 versions have four.
0V
SYN
LH
Plug−in terminal 1
Connecting the voltage
supply: The MP70DP module must be connected to an external
supply voltage of 18−30 V (24 Vnom).
WARNING
DTwist voltage supply cable terminations and provide end
sleeves for strands.
DScrew cable terminations to plug−in terminal 1.
DInsert the plug−in terminal into the top socket.
DTurn on voltage supply.
CAUTION If there is a power failure at the MP70DP module, all the control
outputs will be set to 0 V.
24V
Label
Plug−in terminal 2
Analogue-OU
T
"10 V
"20 mA
4...20 mA IN1
IN2
IN3
IN4
0 V
24 V
OUT1
OUT2
OUT3
OUT4
Plug−in terminal 3*)
Plug−in terminal 4*)
IN1 −IN4 = digital input OUT1 −OUT4 = digital output
Further details of the inputs and outputs can be found in Chapter 8, page 35.
Label
Label
*) only for MP70DPS7 and MP70S7
Fig. 4.1: Plug−in terminal assignment
The plug−in terminals are coded, so that they cannot be mixed up when
plugged into the 2 (4) sockets. The sockets have coded guides, the plug−in
terminals coded pins.

19
PME-MP70DP
HBMA0658−7.2 en
Control inputs and control outputs are available for the MP70DPS7 and
MP70S7 variants:
4.2.1 External supply voltage for the control outputs
Example: PLC connection
OUT3
24 V*
0 V*
max. 0.5 A
Module MP70 PLC relay
0 V*
max. 0.5 A
OUT1
Plug−in terminal 4
24 V
Fig. 4.2: Connection to a PLC
The control inputs are available at plug−in terminal 3, the control outputs at
plug−in terminal 4 and are electrically isolated from the internal supply voltage
(see Chapter 8, ”Description of the essential parameters” page 35).
*)The control outputs must be supplied with an external voltage
(ground and 24 V).
4.3 Profibus
Profibus
connection socket
1
5
6
9GND
RS485-RTS
RS485-B
RS485-A
Vcc (5V)
Fig. 4.3: Profibus connection in accordance with standard

20 PME-MP70DP
HBM A0658−7.2 en
4.4 CAN interface
The CAN-BUS is connected via plug−in terminal 1. A maximum of 32 CAN
users can be connected to a single bus segment (in accordance with the
CANopen specification). In the first and last bus users, the CAN−BUS
requires a terminating resistance of 120 Ω. The bus line has a maximum of
two terminating resistances. In the MP70DP and MP70DPS7 module has a
built-in terminating resistor which is enabled by toggle switch S14 (see page
14).
Low High
1st Device
Fig. 4.4: CAN interface connections
CAN−High
CAN−Low
CAN connection
in accordance with
Fig. 4.4
First device in the bus line Last device in
the bus line
Connect terminating resistance in the
PME (see page 14)
Connect terminating
resistance in the PME
Do not connect terminating
resistance
MP70DP
MPxx MPxx MPxx
Fig. 4.5: CAN-BUS mode with several modules (the standard allows no more than
32)
NOTE
If the first or last device in the bus line is not a PME module, a
120W-resistance must be connected at each of these separate devices.
Other manuals for MP70DP
1
This manual suits for next models
2
Table of contents
Other HBM Control Unit manuals
Popular Control Unit manuals by other brands

QOLSYS
QOLSYS IQ Water Valve Quick install guide

Global Laser
Global Laser Cameo Series user guide

Zurn Wilkins
Zurn Wilkins ZW204 Installation, Troubleshooting, Maintenance Instructions

Infineon
Infineon CCU6 PWM Capture 1 manual

schmersal
schmersal SLC 430 operating instructions

DEMA
DEMA 154 installation instructions