–8 –
1*34 COMM. SPLIT REPORTING [0]
0=no; 1=alarms and alarm restores primary, others
secondary; 2=open/close, test secondary, others primary;
3=fire alarms & troubles primary, all others to secondary.
See
7
51 for comments if using with dual reporting.
1*35 ACCESS CONTROL DIALER ENABLES
[0 0 0 0 0 0]
Trace
Trbl
Byp
Not Used
Syst
Alm
1=enable; 0=disable
1*42 CALL WAITING DEFEAT [0]
1=enable; 0=disable
1*43 PERM. KEYPAD BACKLIGHT [0]
1=enable; 0=disable, when disabled, display lights when any
key is pressed, and turns off after period of keypad inactivity.
1*44 WIRELESS KEYPAD TAMPER [0]
DETECTION
1=enable; 0=disable.
Must be "0" for UL Commercial Burglary and Commercial
Fire installations.
1*45 EXIT DELAY SOUNDING [0]
1=enable; 0=disable. Produces quick beeping during exit
delay if enabled.
1*47 CHIME ON BELL 1 [0]
1=enable; 0=disable
1*48 WIRELESS KEYPAD ASSIGNMENT [0]
0=disable; enter partition in which RF keypad used, 1-8.
Must be "0" for UL Commercial Burglary and Commercial
Fire installations.
1*49 SUPPRESS TX SUPERVISION SOUND [1]
1=disable; 0=enable.
Must be "0" for UL Commercial Burglary and Commercial
Fire installations.
1*52 SEND CANCEL IF ALARM + OFF [0]
1=no restriction; 0=within bell timeout period only.
1*53 DOWNLOAD CALLBACK [0]
1=callback not required; 0=callback required.
Must be "0" for UL Commercial Burglary and Commercial
Fire installations.
1*56 AC 50/60 Hz CLOCK SPEED [0]
1=50 Hz; 0=60 Hz.
1*57 5800 RF BUTTON GLOBAL ARM [0]
1=enable; 0=disable
1*58 5800 RF BUTTON FORCE ARM [0]
1=enable. If a zone is faulted after pressing button, console
will beep once. User should press button again within 4 sec.
to force bypass those zones. 0=disable.
Must be "0" for UL Commercial Burglary and Commercial
Fire installations.
1*60 ZONE 5 AUDIO ALARM VERIFICATION [0]
Enter 1 if 2-way audio (AAV) is being used; Enter 0 if it is not.
Must be "0" for UL Commercial Burglary and Commercial
Fire installations.
1*70 EVENT LOG TYPES
[1 0 0 0 1 0]
Alarm
Chk
Byp
O/C
Syst
Test
1=enable; 0=disable
1*71 12/24 HOUR TIME STAMP FORMAT [0]
0=12 hour; 1=24 hour
1*72 EVENT LOG PRINTER ON-LINE [0]
0=disable; 1=enable
1*73 PRINTER BAUD RATE [0]
1=300; 0=1200
1*74 RELAY TIMEOUT XXX MINUTES [000] | |
Enter relay timeout, 0-127 in multiples of 2 minutes, desired
for #80 Menu Mode time-driven event relay command
numbers "04/09" and #93 Menu Mode Output Programming
output command "56."
1*75 RELAY TIMEOUT YYY SECONDS [000] | |
Enter relay timeout, 0-127 seconds, desired for #80 Menu
Mode time driven event relay command numbers "05/10" and
#93 Menu Mode Output Programming command "57."
1*76 ACCESS CONTROL RELAY [00] |
Relay will be pulsed for 2 seconds whenever code + [0] is
pressed. Enter 00-96; 00=none.
Must be "00" for UL Commercial Burglary and Commercial
Fire installations.
1*77 LOG FIRST MAINTENANCE SIGNAL [0]
0=No Log; 1=Log first maintenance signal from each smoke
detector.
3rd Page Programming Fields (press *94)
2*00 NUMBER OF PARTITIONS [1]
Enter 1-8
2*01 DAYLIGHT SAVING TIME [04, 10] | |
START/END MONTH Start End
00-12; if no daylight saving time, enter 00,00
2*02 DAYLIGHT SAVING TIME [1, 5] |
START/END WEEKEND Start | End
Enter 1-7. 1=first; 2=second; 3=third; 4=fourth; 5=last; 6=next
to last; 7=3rd from last [1,5]
2*05 AUTO-ARM DELAY [15] |
Enter the time between the end of the arming window and the
start of auto-arming warning period, in values of 1-14 times 4
minutes 00=instant; [15=no auto arm at all]. When this delay
expires, the Auto-Arm Warning Period begins.
2*06 AUTO-ARM WARNING PERIOD [15] |
This is the time during which the user is warned to exit the
premises prior to the auto-arming of the system (beeps every
15 seconds; "ALERT" displayed). Enter 01-15 minutes.
00=instant at end of arming delay.
2*07 AUTO-DISARM DELAY [15] |
This is the time between the end of the disarming window
and the start of auto-disarming. Enter 01-14 times 4 minutes;
00=instant at end of window; 15=no auto-disarm.
2*08 ENABLE FORCE ARM FOR AUTO-ARM [0]
0=disable; 1=enable