IBC SFC-125 Quick start guide

120-244E2 |1
Note
IfconvertingfromPropanetoNaturalGas,ordertheNaturalGasConversionPartsKit(IBCPart#P-
807)fromyourauthorizedIBCDistributor.
UsethePropaneGasconversionpartskitifthefuelsourceatthesiteusesPropaneandtheappliancehasbeen
setuptooperatewithNaturalGas.Checktheratingplateontheboilertoseewhichfuelsourcetheparticular
appliancehasbeensetupwith.
Usingthisconversionkit,aqualifiedtechnicianwillneedto:
1. Performafuelconversion.
2. Performacombustiontest.
3. Fillintheinformationrequiredonthefuelconversionlabels,andaffixthemtotheboilerafterthe
conversioniscompleted.
Warning
Thisconversionkitshallbeinstalledbyaqualifiedserviceagencyinaccordancewiththe
manufacturer’sinstructionsandallapplicablecodesandrequirementsoftheauthorityhaving
jurisdiction.Iftheinformationintheseinstructionsisnotfollowedexactly,afire,anexplosionor
productionofcarbonmonoxidemayresultcausingpropertydamage,personalinjuryorlossoflife.
Thequalifiedserviceagencyisresponsiblefortheproperinstallationofthiskit.Theinstallationisnot
properandcompleteuntiltheoperationoftheconvertedapplianceischeckedasspecifiedinthe
manufacturer’sinstructionssuppliedwiththekit.
Theboilerwillautomaticallyde-ratethemaximuminputatarateofapproximately2%per1,000’above4,500’.
Thegasvalve'szero-governorwillensurethatthegas-airmixtureisnotaffectedataltitude.
IncludedwiththeConversionKit:
Part# Description Quantity
180-229 LPorifice#370 1
150-175 OrificeO-ring19x2 1
080-305 Ratingplateoverlay 1
080-107 Gasvalveconversionlabel 1
080-244 InstallerIdentificationlabel 1
SFC125/SFB125-FuelConversionto
Propane-P-806

CombustionTestTargetRanges
Figure1Gas valve and fan
TheLowFire(zero-offset)valveadjustmentcaponthegasvalvehasbeenfactoryset.Donotadjustthisscrewin
thefieldunlessindicatedintheseinstructions.
Afterconvertingtheappliancetopropane,acombustion(CO2)readingmustbetakenbyaqualifiedtechnician
usingproperlyfunctioningandcalibratedcombustionanalyzingequipmentandtheresultscomparedtothevalues
inTable1.
Fuel HighFirewithfrontcoveropen LowFirewithfrontcover
open
Max.CO2value 11.5% ActualValueatHighFireMinus
-0.3%
Min.CO2value 9.8% 9.5%
Table 1 - Combustion test target ranges - CO2 / Maximum CO
2|

SFC 125 / SFB 125 - Fuel Conversion to Propane - P-806 |3
FuelConversionInstructions
Youmustbeaqualifiedtechniciantoperformafuelconversion.
ModelNumber OrificeSize
SFC16-125/SFB16-125 370
Table 2 - Propane Orifice Chart
Toperformafuelconversion:
1. Turnoffthegassupplyatthemanualgasvalve.
2. Disconnecttheelectricalpower.
3. Disconnectthenutatthegasvalveoutlet(topofthegasvalve),andremovetheO-ringandorifice.
4. InsertthecorrectorificeintotheO-ring,andre-installintothenutatthegasvalveoutlet(topofthegas
valve),andthentightenthenut.
5. Restorethegassupplybyopeningthegascontrolvalve.
6. Testforleaksbyusinganapprovedleakdetectionsolutiononalljoints.
7. Powerontheboiler/waterheaterappliance.
Now,carefullyfollowtheproceduresonCombustionTestingandAdjustment.

Combustiontestingandadjustment
Danger
Acombustiontestchecksthatthegasvalveisoperatingproperlyinthefield.Toperformacombustion
test,youmustbeaqualified,trainedandlicensedgasfitter.
Makingadjustmentstothegasvalvewithoutaproperlycalibratedgascombustionanalyzerandby
peoplewhoarenottrainedandexperiencedinitsuseisforbidden.Failuretouseananalyzercan
resultinanimmediatehazard.
ModelNumber HighFireInput
SFC16-125/SFB16-125 125MBH
Table 3 Rated input of a converted boiler
Normalignitionsystemsequenceofoperation:
Theboilercontrol,uponacallforheatorDHW,turnsonthecombustionfanfora5-secondpre-purge,then
energizesthesparkelectrodeandgasvalvefora5-secondtrialforignition.
Iftheburnerdoesnotlight,theprocessisrepeateduntiltheburnerlightsandflameisdetected.After4
unsuccessfultrialsforignition,theappliancelocksoutandwillneedtobemanuallyresetbypressingtheReturn
Arrow button.
Toperformacombustiontestandadjustment:
1. Turnofftheappliance’smanualgasvalve.
2. WithaTorx15screwdriver,opentheinletgassupplypressuretestportby
turningitsscrew1fullturncounterclockwise.
3. Attachamanometertotheinletpressuretestportandturnongasto
appliance.
Staticmanometerreadingshouldbeideally11"w.c.forPropane.
Minimumandmaximumstaticpressuremustbebetween5"and14"
w.c.Monitorpressurethroughoutthecommissioning(start-up)
procedure.Pressuremaydroopupto1"w.c.athighfire.
4. Tosettheappliancetohighfiremanually,createalargeDHWdemandfortheappliancetoheat.:
Allowtheappliancetoignite/runagainstalargeload,tomaintainhighfire.Tosetthehigh-firemanually,
pressandholdtheServiceiconfortwoseconds.ThenwhileholdingtheServiceiconpressthePlusbutton
twice.“H”willshowintheservicedisplayastheapplianceentershighfire.
4|

SFC 125 / SFB 125 - Fuel Conversion to Propane - P-806 |5
Note:AllowtheappliancetooperateatHighFirefor3minutestostabilize.(Theapplianceoperatesin
manualmodefor10minutesthenswitchbacktothenormaloperatingmode.Toextendmanualmode
operation,presstheServiceandPlusbuttonstogethertwicewhiletheapplianceisoperatingin
manualmodetoresetthetimerfor10moreminutes.)Donotmakeadjustmentsiftheservicedisplay
showsan“h”.
5. a. Whileinmanualhighfire,toconfirmfullmaximumratingplateinput(estimated):
i. Press ServicebuttonfortwosecondstoentertheInformationmenu.
ii. Press Plusbuttonrepeatedlyuntiltherightwindowindicates"F".Theinputisdisplayed
intheMainwindow.
iii. Press FlamebuttontoreturntotheServicemenu.
b. Withacombustionanalyzerprobeinthefluegastestport,checkthemeasuredresultsagainst
Table 1 -HighFire.
c. Iftheresultsareoutsidethepermittedrange,checktheinletpressure,andconfirmthatthecorrect
orificeandventuriareinstalled.
6. SwitchthewaterheatertolowfirebypressingtheServicebuttonandMinusbuttonatthesametime.
Thewaterheaterwilldroptolowfire.“L”willshowintheservicedisplay.
a. ComparethereadingswithTable 1 -LowFire.Ifadjustmentisnecessary,removetheLowFire
AdjustmentcaptorevealaTorxheadscrew.
b. Maketinyadjustments,typicallylessthan1/8thofaturnatatime.Turnthescrewclockwiseto
increaseCO2andcounter-clockwisetoreduceCO2.Ifthetargetcannotbemet,evenafterahalf
turn,contactthefactory.
c. Whenfinished,replacetheLowFirecap,andleavethemanualmodebypressing+AND-
simultaneously.
7. Switchofftheappliancebypressingthespaceabovethedot.
8. Turnoffthegasattheappliance'smanualgasvalve.
9. Removethefluegasanalyzerfromthetestport,andreinstallthetestportcap.
10. Removethegaspressuremanometerfromthegasvalve,andfullyclosethetestport.
11. Turnonthegasattheappliance’smanualgasvalve.
12. Ensuretherearenogasleaksbeforereinstallingthefrontcover.
13. Turnontheappliancebypressingthespaceabovethedot.
Nextyoumustfillintheinformationandaffixtheincludedfuelconversionlabelstotheboilerasindicatedafter
theconversioniscompleted.
CompletingandAffixingtheConversionLabels
1. Fillintheconversionlabels(includedinthekit)associatedwiththenewfueltype.
2. Placetheconversionlabelsontotheboilerasindicatedbelow.

6|
This manual suits for next models
1
Table of contents
Other IBC Boiler Supplies manuals
Popular Boiler Supplies manuals by other brands

Galmet
Galmet SG Fusion 100 Installation and operating manual

Siemens
Siemens AGU2.522 Series Mounting instructions

KOM-STER
KOM-STER TIGRA manual

TriangleTube
TriangleTube PGRKIT30 Assembly instructions

Bryan Boilers
Bryan Boilers DSH-10 Specification sheet

Tucson
Tucson GBPHR/8/CCW Installation, operation and maintenance manual