VA9204-BGA-2, VA9204-BGB-2, VA9204-BUA-2, VA9204-BUB-2
10 LIT-12014315 Rev. —
Specication Description
Power
requirements
-BGx-2 models 24 VAC (19.2 VAC to 28.8 VAC) at 50/60 Hz: Class 2 (North America) or Safety Extra-Low Voltage (SELV) (Europe), 5 VA running,
1.6 VA holding position, 24 VDC (21.6 VDC to 28.8 VDC): Class 2 (North America) or SELV (Europe) 2.8 W running, 0.8 W holding
position. Minimum transformer size: 6 VA for each actuator
-BUx-2 models 100 VAC to 240 VAC (85 VAC to 264 VAC) at 50/60 Hz: 0.06 A running, 0.02 A holding position
Auxiliary switch
rating
-xxB-2 models One single-pole, double-throw (SPDT), double-insulated switch with silver contacts:
24 VAC, 50 VA pilot duty
120 VAC, 5.8 A resistive, 1/4 hp, 275 VA pilot duty
240 VAC, 5.0 A resistive, 1/4 hp, 275 VA pilot duty
Spring return Direction is selectable with mounting position of actuator:
Actuator face labeled A is away from valve: CCW spring return
Actuator face labeled B is away from valve: CW spring return
Rated torque
Power on
(running)
35 lb·in. (4 N•m) all operating temperatures
Power o
(spring returning)
35 lb·in. (4 N•m) all operating temperatures
Rotation range Maximum full stroke: 95°
Rotation time
for 90 degrees
of travel
Power on
(running)
-Bxx-2 models
53 s to 71 s constant for 0 lb·in. to 35 lb·in. (4 N•m) load, at room temperature
60 s nominal at full rated load (0.25 rpm)
Power o
(spring returning)
37 s to 46 s for 0 lb·in. to 35 lb·in. (4 N•m) load, at room temperature
44 s nominal at full rated load
75 s maximum with 35 lb·in. (4 N•m) load at -22°F (-30°C)
Life cycles 60,000 full stroke cycles with 35 lb·in. (4 N·m) load
Audible noise
rating
Power on
(running)
<36 dBA at 35 lb·in. (4 N•m) load, at a distance of 39 13/32 in. (1 m)
Power on
(holding)
<20 dBA at a distance of 39 13/32 in. (1 m)
Power o
(spring returning)
<35 dBA at 35 lb·in. (4 N•m) load, at a distance of 39 13/32 in. (1 m)
Electrical
connections
Actuator
(all models)
48 in. (1.2 m) UL 758 Type AWM halogen-free cable with 18 AWG (0.85 mm2) conductors and 0.25 in. (6 mm) ferrule ends
Auxiliary switches
(-xxB-2 models)
48 in. (1.2 m) UL 758 Type AWM halogen-free cable with 18 AWG (0.85 mm2) conductors and 0.25 in. (6 mm) ferrule ends
Conduit connections Integral 1/2 in. (13 mm) threaded conduit connectors
Fluid
temperature
limits
VG12x1 and
VG18x1 Series
23°F to 203°F (-5°C to 95°C), not rated for steam service
VG12x5 and
VG18x5 Series
-22°F to 212°F (-30°C to 100°C), not rated for steam service
VG12x5 and
VG18x5 Series
with M9000-561
Thermal Barrier
installed
-22°F to 284°F (-30°C to 140°C) water; 15 psig (103 kPa) at 250°F (121°C) saturated steam
Ambient
conditions
Standard
operating
-22°F to 140°F (-30°C to 60°C); 90% RH maximum, non-condensing
Storage -40°F to 185°F (-40°C to 85°C); 95% RH maximum, non-condensing
Enclosure rating NEMA 2 (IP54) for all mounting directions
Compliance United States UL Listed, CCN XAPX, File E27734; to UL 60730-1A: 2003-08, Ed. 3.1, Automatic Electrical Controls for Household and Similar Use;
and UL 60730-2-14: 2002-02, Ed. 1, Part 2 Particular Requirements for Electric Actuators. Plenum Rated (UL 2043). Suitable for use
in other environmental air space (plenums) in accordance with Section 300.22 (C) of the National Electric Code.
Canada UL Listed, CCN XAPX7, File E27734; to UL 60730-1:02-CAN/CSA: July 2002, 3rd Ed., Automatic Electrical Controls for Household
and Similar Use; and CSA C22.2 No. 24-93 Temperature Indicating and Regulating Equipment.
Europe Johnson Controls declares that this products is in compliance with the essential requirements and other relevant provisions of the
EMC Directive and Low Voltage Directive and equivalent UK regulations.
Australia and
New Zealand
RCM Mark, Australia/NZ Emissions Compliant
Shipping weight -xxA Models 2.0 lb (0.9 kg)
-xxB Models 2.4 lb (1.1 kg)
Technical specications
VA9204-Bxx-2 Series On/O Electric Spring Return Actuator