manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. M-system
  6. •
  7. Security System
  8. •
  9. M-system Mini-M M2SED User manual

M-system Mini-M M2SED User manual

Other M-system Security System manuals

M-system 48NDM User manual

M-system

M-system 48NDM User manual

M-system 48DV User manual

M-system

M-system 48DV User manual

M-system M1EAXV-2 User manual

M-system

M-system M1EAXV-2 User manual

M-system AS4V User manual

M-system

M-system AS4V User manual

M-system M7EASDY User manual

M-system

M-system M7EASDY User manual

M-system 48NDV User manual

M-system

M-system 48NDV User manual

M-system AS User manual

M-system

M-system AS User manual

M-system KSE-x2 User manual

M-system

M-system KSE-x2 User manual

M-system 48NDVA User manual

M-system

M-system 48NDVA User manual

M-system KSL-x5 User manual

M-system

M-system KSL-x5 User manual

M-system AS4T User manual

M-system

M-system AS4T User manual

M-system AYDV User manual

M-system

M-system AYDV User manual

M-system M8SED User manual

M-system

M-system M8SED User manual

M-system ASL User manual

M-system

M-system ASL User manual

M-system 48NAM User manual

M-system

M-system 48NAM User manual

M-system R3-AV8 User manual

M-system

M-system R3-AV8 User manual

M-system KSE-1 User manual

M-system

M-system KSE-1 User manual

M-system M6DXAR User manual

M-system

M-system M6DXAR User manual

M-system 10AS User manual

M-system

M-system 10AS User manual

M-system AS4LC User manual

M-system

M-system AS4LC User manual

M-system AS4R User manual

M-system

M-system AS4R User manual

M-system ASWL2 User manual

M-system

M-system ASWL2 User manual

M-system 48NAT User manual

M-system

M-system 48NAT User manual

M-system KS2V3 User manual

M-system

M-system KS2V3 User manual

Popular Security System manuals by other brands

Polon-Alfa 4000 Installation and maintenance manual

Polon-Alfa

Polon-Alfa 4000 Installation and maintenance manual

Nexcom NViS 14162 Series user manual

Nexcom

Nexcom NViS 14162 Series user manual

Eminent EM8670 Quick install

Eminent

Eminent EM8670 Quick install

urmet domus alpha 1060 INSTALLATION AND USE BOOKLET

urmet domus

urmet domus alpha 1060 INSTALLATION AND USE BOOKLET

SmartPool YardGuard YG03 manual

SmartPool

SmartPool YardGuard YG03 manual

DSC PC5964 Mounting instructions

DSC

DSC PC5964 Mounting instructions

Secure USAB-1 operating instructions

Secure

Secure USAB-1 operating instructions

B&B 480 SERIES Operation & maintenance manual

B&B

B&B 480 SERIES Operation & maintenance manual

ADEMCO VISTA-20P Series Installation and setup guide

ADEMCO

ADEMCO VISTA-20P Series Installation and setup guide

Inner Range Concept 2000 user manual

Inner Range

Inner Range Concept 2000 user manual

Johnson Controls PENN Connected PC10 Install and Commissioning Guide

Johnson Controls

Johnson Controls PENN Connected PC10 Install and Commissioning Guide

Aeotec Siren Gen5 quick start guide

Aeotec

Aeotec Siren Gen5 quick start guide

Swann SW-P-MC2 Specifications

Swann

Swann SW-P-MC2 Specifications

Ecolink Siren+Chime user manual

Ecolink

Ecolink Siren+Chime user manual

EDM Solution 6+6 Wireless-AE installation manual

EDM

EDM Solution 6+6 Wireless-AE installation manual

Siren LED GSM operating manual

Siren

Siren LED GSM operating manual

Detection Systems 7090i Installation and programming manual

Detection Systems

Detection Systems 7090i Installation and programming manual

FRIEDLAND MA10 Installation and operating instructions

FRIEDLAND

FRIEDLAND MA10 Installation and operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-5042 Rev.9 P. 1 / 3
INSTRUCTION MANUAL
Mini-M™
DC ALARM
(thumbwheel switch adjustment) MODEL M2SED
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.
■PACKAGE INCLUDES:
Signal conditioner
(body + base socket + input resistor)..................................(1)
Input resistor is provided only with current input type.
■MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
POINTS OF CAUTION
■CONFORMITY WITH EU DIRECTIVES, UK LEGISLATION OR UL
• This equipment is suitable for Pollution Degree 2, Meas-
urement Category II (output, transient voltage 2500V)
and Installation Category II (transient voltage 2500V).
Reinforced insulation (signal input or output to power in-
put: 300V) and basic insulation (signal input to output:
300V) are maintained. Prior to installation, check that
the insulation class of this unit satisfies the system re-
quirements.
• Altitude up to 2000 meters.
• The equipment must be mounted inside a panel.
• The equipment must be installed such that appropriate
clearance and creepage distances are maintained to con-
form to CE/UKCA/UL requirements. Failure to observe
these requirements may invalidate the CE/UKCA/UL
conformance.
• The actual installation environments such as panel con-
figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated
in a panel system. The user may have to review the
CE/
UKCA
requirements in regard to the whole system and
employ additional protective measures to ensure the
CE/
UKCA
conformity.
• Install lightning surge protectors for those wires connect-
ed to remote locations.
■POWER INPUT RATING & OPERATIONAL RANGE
• Locate the power input rating marked on the product and
confirm its operational range as indicated below:
100 – 240V AC rating: 85 – 264V (90 – 264V for UL),
47 – 66 Hz, approx. 3 – 5VA
24V DC rating: 24V ±10%, approx. 3W
11 – 27V DC rating: 11 – 27V, approx. 3W
110V DC rating: 85 – 150V (110V ±10% for UL), approx. 3W
■GENERAL PRECAUTIONS
• Before you remove the unit from its base socket or mount
it, turn off the power supply and input signal for safety.
■ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -5 to +55°C
(23 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
• Be sure that the ventilation slits are not covered with ca-
bles, etc.
■WIRING
• Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■AND ....
• The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
COMPONENT IDENTIFICATION
Input Resistor
31
44
Body Base Socket
Connection
Diagram
Specifications
Fixing Screw
■FRONT PANEL CONFIGURATION
The front cover cannot be turned open by 180 deg.
when there is no extra space between units.
Output 1 Setpoint Adj.
Output 2 Setpoint Adj.
Output 1 Monitor LED
Output 2 Monitor LED
9 9
9 9
M2SED
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-5042 Rev.9 P. 2 / 3
INSTALLATION
Loosen the fixing screw at the front of the unit in order to
separate the body from the base socket.
DIN Rail
35mm wide
Spring Loaded
DIN Rail Adaptor
■DIN RAIL MOUNTING
Set the base socket so that
its DIN rail adaptor is at
the bottom. Position the
upper hook at the rear side
of base socket on the DIN
rail and push in the lower.
When removing the socket,
push down the DIN rail
adaptor utilizing a minus
screwdriver and pull.
■WALL MOUNTING
Refer to “EXTERNAL DIMENSIONS.”
TERMINAL CONNECTIONS
Connect the unit as in the diagram below or refer to the connection diagram on the side of the unit.
When an input resistor is provided with the module, attach it together with input wiring to the input screw terminals.
■EXTERNAL DIMENSIONS unit: mm (inch)
4
8 7
1011
56
123
9
21.5 (.85)
70.5 (2.78)
86.7 (3.41)7.3 (.29) 22 (.87)
6 (.23)
59 (2.32)
DIN RAIL
35mm wide
[4 (.16)]
11–M3
SCREW
72 (2.83)4 (.16)
29.5 (1.16)
2–4.2x5
(.17x.20)
MTG HOLE
6 (.24) deep
116.7 (4.59)
• When mounting, no extra space is needed between units.
■CONNECTION DIAGRAM
6
3
8
7
5
9
N.C.
OUTPUT 1
N.O.
COM
N.C.
OUTPUT 2
N.O.
COM
+
–
*
INPUT
1
R
2
*Input shunt resistor attached for current input.
U(+)
V(–)
POWER
10
11
■TERMINAL ASSIGNMENTS unit: mm (inch)
46
8 7
1011
3
5
9
12
INPUT RESISTOR
(model: REM2)
19 (.75)
Input shunt resistor attached
for current input.
M2SED
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-5042 Rev.9 P. 3 / 3
WIRING INSTRUCTIONS
■SCREW TERMINAL
Torque: 0.8 N·m
■SOLDERLESS TERMINAL
Refer to the drawing below for recommended ring tongue
terminal size. Spade tongue type is also applicable.
Applicable wire size: 0.25 to 1.65 mm2(AWG 22 to 16)
Recommended manufacturer: Japan Solderless Terminal
MFG.Co.Ltd, Nichifu Co.,ltd
6 (.24) max
3.3 (.13) max
mm (inch)
CHECKING
1) Terminal wiring: Check that all cables are correctly con-
nected according to the connection diagram.
2) Power input voltage: Check voltage across the terminal
10 – 11 with a multimeter.
3) Input: Check that the input signal is within 0 – 100% of
the full-scale.
4) Alarm operations: Check the alarm operations referring
to the figure below.
5) Check that the output load is 250V AC/600VA or 125V
DC/150W at the maximum. For maximum relay life with
inductive loads, external protection is recommended.
050 100▲
Input
(%)
Setpoint 2
▲
Setpoint 1
Output 1
(5–7)ON
Output 2
(3–9)ON
(3–6)ON
(5–8)ON
Alarm Trip Operation Terminal No. in parentheses
Trip Operation in Power Failure: Terminals 3 – 9 and 5 – 8 turn on.
SETPOINT ADJUSTMENTS
Turn the thumbwheel switches until desired figures in per-
cent are shown. Output 1 is for Hi trip, while Output 2 is
for Lo. Monitor LED turns on when the coil is energized
([input] > [setpoint] for Output 1, [input] < [setpoint] for
Output 2).
MAINTENANCE
Regular calibration procedure is explained below:
■CALIBRATION
Warm up the unit for at least 10 minutes.
• Hi Alarm
Increase the input signal from a value lower than the set-
point and check that the relay trips at the setpoint.
• Lo Alarm
Decrease the input signal from a value higher than the
setpoint and check that the relay trips at the setpoint.
When the setpoints are shifted, contact M-System’s Sales
Office or representatives.
LIGHTNING SURGE PROTECTION
M-System offers a series of lightning surge protector for
protection against induced lightning surges. Please contact
M-System to choose appropriate models.