V-Cone Troubleshooting Guide
Company name: McCrometer Inc.
Address: 3255 W. Stetson Ave.
Hemet, California, USA 92545-7799
General office phone: +1 (909) 652-6811
Facsimile : +1 (909) 652-3078
E-mail: [email protected]
Internet: www.mccrometer.com
 1999 by McCrometer/Printed in U.S.A. 2-99/Lit #: 24509-90 Rev 1.0
Page 1of 5
Troubleshooting a V-Cone System On-Site
This guide is intended to help you troubleshoot a V-Cone system. Keep several points in
mind as you proceed:
1. Most V-Cones are calibrated devices. The meter has already had flow through it. If a
cone is missing or a leak exists inside the meter, this would be discovered during the
calibration.
2. A flow measurement requires a system. Do not assume a problem exists with the
primary element just because it is called a V-Cone system. Most problems occur in
the DP transmitter or the flow computer.
3. This guide assumes a simple system of meter, manifold, DP transmitter, and flow
computer. Systems can be much more complex with pressure and temperature
transmitters, as well as full scale digital control systems. Do not limit your evaluation
to just these suggestions.
4. If you discover a problem / solution not listed in this guide, please let Stephen Ifft at
McCrometer know at 1-909-765-5344 or [email protected].
This guide separates the flow measurement system into areas. These areas are labeled in
the diagram below:
During troubleshooting, make a preliminary assessment of the symptoms of the problem
and consult the following chart.
V-Cone Manifold Transmitter Flow computer
Gauge lines
 1999 by McCrometer/Printed in U.S.A. 2-99/Lit #: 24509-90 Rev 1.0
Page 2of 5
SYMPTOM AREA POSSIBLE PROBLEM / SOLUTION
Transmitter No power to transmitter.
No signal
(0 mA) Transmitter Transmitter not wired correctly. Perform continuity check on wiring.
Negative signal
(< 0 mA) Transmitter Transmitter wires are reversed.
V-Cone V-Cone installed backwards, with gauge lines attached as marked. In this
case, the high pressure tap would be sensing a lower pressure than the low
pressure tap. This negative DP would force the signal below 4 mA.
Gauge
lines Gauge lines are reversed. Transmitter sees more pressure on low side than
high side. Check “H” and “L” marks on V-Cone and transmitter.
Low signal
(<4 mA)
Transmitter Transmitter is malfunctioning. Some transmitters will send a specified
mA signal when a malfunction occurs. This can be set to low values, such
as 3.8 mA, or high values, such as 20.1 mA.
V-Cone Meter has been damaged. Remove meter and visually inspect.
V-Cone No flow in pipeline. Check other system locations to verify flow through
the meter. The meter could be under pressure but still have no flow.
Manifold Manifold / gauge lines closed or blocked. Ensure valves and lines are
open. If fluid is safe, open vent valves on transmitter to verify pressure in
the gauge lines.
Zero signal
(4 mA)
Transmitter Transmitter is check mode. Some transmitters allow for system checks by
forcing the signal to 4 or 20 mA. Vent low side of transmitter to ensure
the signal responds to pressure changes.
V-Cone Process conditions do not match actual conditions. Contact McCrometer
or your sales representative to recalculate using the correct process
conditions.
V-Cone Wrong meter. Verify serial numbers on meters to ensure correct
specifications. Sometimes two meters are interchanged. Remember each
V-Cone has a unique flow coefficient.
Gauge
lines Foreign material trapped in gauge lines. Dirt and sediment can settle into
the gauge lines. If the fluid is safe, vent the gauge lines and inspect for
spurts of solids, gasses, or liquids (whichever should not be there). If the
fluid is not safe, open the center manifold valve for several minutes under
high DP. Close the valve and compare the signal level to before. In a
horizontal, liquid application, install the meter with the taps on the sides of
the pipe (3 or 9 o’clock) For a horizontal, gas application, install at top or
sides of the pipe (12, 3, or 9 o’clock).
Flow
computer Flow calculations are in error. Use loop calibrator and apply 4, 12, and 20
mA to computer / system. Each of these points should correlate with the
V-Cone sizing information.
Wrong signal –
high or low
Flow
computer mA signal is read incorrectly. Apply a known current to the loop and read
the raw signal in the computer. Most computers allow the user to see the
mA signal directly.
 1999 by McCrometer/Printed in U.S.A. 2-99/Lit #: 24509-90 Rev 1.0
Page 3of 5
V-Cone V-Cone is installed backwards. Look for a flow direction arrow on the
meter body, near the pressure taps. If no arrow is visible and the meter is
large than 2 inches, the flow direction can be determined by the location
of the pressure taps. The pressure taps will be closer to the upstream side.
On meters less than 2 inches, the gauge lines will need to be removed.
Look at the base of both pressure taps. One tap will be smooth at the base,
the other will be mostly weld material. The smooth tap is on the upstream
side. With a meter measuring backward flow, the DP signal will be
approximately 30% too high.
V-Cone Flow is going in opposite direction as expected. The assumption of flow
direction is sometimes wrong. Verify with other system readings. With a
meter measuring backward flow, the DP signal will be approximately 30%
too high.
V-Cone Partially full pipe (liquids only). A partially full pipe will cause the meter
to read too high. This can happen even in pressurized systems.
•On horizontal pipes: If the fluid is safe, open a pressure tap on the top
of the pipe. Air release will indicate partially full pipe.
•On vertical pipes: Up flow will guarantee a full pipe. Down flow is
difficult to diagnose if the pipe is full.
V-Cone Foreign object lodged in meter. This will increase the restriction of the
meter and raise the DP. Remove the meter and visually inspect.
Gauge
lines Leak on low pressure gauge line. Perform a leak check from the meter to
the transmitter.
Transmitter Leak on low pressure vent valve. Perform a leak check on valve.
Transmitter Zero point has shifted positively. This will cause errors more pronounced
at the low end of the transmitter range. Verify by closing the manifold side
valves and opening the center valve. The reading should go to zero (4
mA). Recalibrate if necessary.
Transmitter DP span is set too low. Use pressure calibrator or handheld communicator
to verify span point.
Transmitter
/ flow
computer
Both the transmitter and flow computer are set to take the square root of
the signal. The signal will be correct at 20 mA. The positive error will
increase dramatically as the signal decreases from 20 mA. Use a loop
calibrator to check 12 mA point.
Signal too high
Flow
computer 4 mA set to minimum flow. Our calculations assume that 4 mA will be
equal to zero flow. Sometimes 4 mA is set to equal the minimum flow on
the sizing page. This error will be zero at maximum flow and increase as
the flow decreases. The amount of error will depend on the zero offset.
 1999 by McCrometer/Printed in U.S.A. 2-99/Lit #: 24509-90 Rev 1.0
Page 4of 5
Manifold Manifold is cross-vented. The center valve must be closed. To test, close
the two side valves and watch the transmitter signal. If the signal goes to
zero (4 ma), the center valve is not closed completely.
Gauge
lines Leak on high pressure gauge line. Perform a leak check from the meter to
the transmitter.
Transmitter Leak on high pressure vent valve. Perform a leak check on valve.
Transmitter Zero point has shifted negatively. This will cause errors more pronounced
at the low end of the transmitter range. Verify by closing the manifold side
valves and opening the center valve. The reading should go to zero (4
mA). Recalibrate if necessary.
Transmitter DP span is set too high. Use pressure calibrator or handheld
communicator to verify span point.
Signal too low
Transmitter
/ flow
computer
Neither the transmitter nor flow computer is set to take the square root of
the signal. The signal will be correct at 20 mA. The negative error will
increase dramatically as the signal decreases from 20 mA. Use a loop
calibrator to check 12 mA point.
V-Cone Partially full pipe occurring (liquids only). Periods with a partially full
pipe will cause erratic readings. See above for details.
Unsteady signal
Transmitter Power supply not supplying enough power to create signal. Check power
specifications for transmitter.
Slow response
time Transmitter Dampening.
V-Cone Foreign object lodged in meter. This will increase the restriction of the
meter and raise the DP. Remove the meter and visually inspect.
Sudden change
in readings Gauge
lines Leaks have started.
 1999 by McCrometer/Printed in U.S.A. 2-99/Lit #: 24509-90 Rev 1.0
Page 5of 5
Recommended Equipment for
Troubleshooting a V-Cone Installation On-Site:
1. 4 to 20 mA loop simulator – highly recommended
2. Digital multimeter: with VDC, I, and Ωmeasurements
3. Pressure calibrator
4. Handheld Communicator for smart instruments
5. Hand tools: Screwdriver(+), Screwdriver (–), 12 inch crescent wrench, 4
inch crescent wrench
Some suggestions for equipment manufacturers and their products follow. A wide range
of products is available. We do not necessarily endorse these products or companies.
Please choose a product that fits your needs and resources.
www.fluke.com
740 Series Documenting Process Calibrators
718 Pressure Calibrator
717 30G Pressure Calibrator
716 Pressure Calibrator
715 Volt/mA Calibrator
714 Thermocouple Calibrator
713 30G/100G Pressure Calibrator
712 RTD Calibrator
787 Process Meter (combination digital multimeter and loop calibrator)
705 Loop Calibrator

Other manuals for V-Cone

1

Other McCrometer Measuring Instrument manuals

McCrometer Water Specialties ML04 User manual

McCrometer

McCrometer Water Specialties ML04 User manual

McCrometer Propeller Meter FlowCom Register FC100 User manual

McCrometer

McCrometer Propeller Meter FlowCom Register FC100 User manual

McCrometer V-Cone Owner's manual

McCrometer

McCrometer V-Cone Owner's manual

McCrometer FlowConnect User manual

McCrometer

McCrometer FlowConnect User manual

McCrometer Dura Mag User manual

McCrometer

McCrometer Dura Mag User manual

McCrometer UltraMag Standard Instruction Manual

McCrometer

McCrometer UltraMag Standard Instruction Manual

McCrometer McMag 2000 Instruction Manual

McCrometer

McCrometer McMag 2000 Instruction Manual

McCrometer Field Mag 3000 Instruction Manual

McCrometer

McCrometer Field Mag 3000 Instruction Manual

McCrometer FPI Mag 394L User manual

McCrometer

McCrometer FPI Mag 394L User manual

McCrometer SPI Mag 282L User manual

McCrometer

McCrometer SPI Mag 282L User manual

McCrometer Water Specialties ML04D User manual

McCrometer

McCrometer Water Specialties ML04D User manual

McCrometer Dura Mag User manual

McCrometer

McCrometer Dura Mag User manual

McCrometer WATER SPECIALTIES FlowCom FC101 User manual

McCrometer

McCrometer WATER SPECIALTIES FlowCom FC101 User manual

McCrometer Dura Mag User manual

McCrometer

McCrometer Dura Mag User manual

McCrometer Ultra Mag User manual

McCrometer

McCrometer Ultra Mag User manual

McCrometer ULTRA MAG 4 User manual

McCrometer

McCrometer ULTRA MAG 4 User manual

McCrometer Ultra Mag User manual

McCrometer

McCrometer Ultra Mag User manual

McCrometer SmartTrax User manual

McCrometer

McCrometer SmartTrax User manual

McCrometer McMag3000 Instruction Manual

McCrometer

McCrometer McMag3000 Instruction Manual

McCrometer SPI Mag 282L User manual

McCrometer

McCrometer SPI Mag 282L User manual

McCrometer FlowConnect FC500 User manual

McCrometer

McCrometer FlowConnect FC500 User manual

McCrometer McMag2000 User manual

McCrometer

McCrometer McMag2000 User manual

McCrometer ULTRA MAG UM06 User manual

McCrometer

McCrometer ULTRA MAG UM06 User manual

McCrometer Water Specialties VF28D User manual

McCrometer

McCrometer Water Specialties VF28D User manual

Popular Measuring Instrument manuals by other brands

PCB Piezotronics 300A12 Installation and operating manual

PCB Piezotronics

PCB Piezotronics 300A12 Installation and operating manual

weschler instruments OMBGP100 owner's manual

weschler instruments

weschler instruments OMBGP100 owner's manual

ISOIL SBM 75 Operator's manual

ISOIL

ISOIL SBM 75 Operator's manual

Hanna Instruments HI 93719 instruction manual

Hanna Instruments

Hanna Instruments HI 93719 instruction manual

LaserLiner ActiveFinder Pro manual

LaserLiner

LaserLiner ActiveFinder Pro manual

Ushio UIT-250 operating manual

Ushio

Ushio UIT-250 operating manual

MDT Technologies SCN-GLED1 01 Series Technical manual

MDT Technologies

MDT Technologies SCN-GLED1 01 Series Technical manual

MEDAP S FLOW operating instructions

MEDAP

MEDAP S FLOW operating instructions

Seta Target Systems SCORE10/Pro operating instructions

Seta Target Systems

Seta Target Systems SCORE10/Pro operating instructions

Stihl Laser 2-in-1 instruction manual

Stihl

Stihl Laser 2-in-1 instruction manual

EUTECH INSTRUMENTS CyberScan IR TB100 instruction manual

EUTECH INSTRUMENTS

EUTECH INSTRUMENTS CyberScan IR TB100 instruction manual

TR-Electronic LLB-502 Series user manual

TR-Electronic

TR-Electronic LLB-502 Series user manual

Cybertek CPL8100A manual

Cybertek

Cybertek CPL8100A manual

K-Patents SAFE-DRIVE PR-23-SD Pocket guide

K-Patents

K-Patents SAFE-DRIVE PR-23-SD Pocket guide

Horizon Hobby Spektrum SPM6740 user manual

Horizon Hobby

Horizon Hobby Spektrum SPM6740 user manual

MADDALENA microCLIMA/SENSOSTAR 2+ MSH Installation and operating instructions

MADDALENA

MADDALENA microCLIMA/SENSOSTAR 2+ MSH Installation and operating instructions

National Instruments CP400X Getting started guide

National Instruments

National Instruments CP400X Getting started guide

Metrohm 930 Compact IC Flex Short instructions

Metrohm

Metrohm 930 Compact IC Flex Short instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.