Miura Comm-Link User manual

Guidance
i
Installation Manual
Comm-Link
Document Number
C730-058-6820

No part of this document may be reproduced without Miura's express consent. All rights in the
document are reserved by the Japanese copy right law.
No part of this document may be copied without Miura’s written permission in any way.
The contents of the document will be modified without notification.
October 2014, Miura Co., LTD.

Guidance
iii
Guidance
This manual is written to describe installation of a Comm-Link/ER. Please read this manual carefully and follow the
instruction.
The following caution sign is used to tell you what parts of the manual you need to be careful for your safety.
Please follow the safety notifications for your safety and install the device properly.
CAUTION
A minor injury or physical damage on the device will be expected if you don’t use the
device correctly by following the manual.

Table of Contents
iv
Table of Contants
1 Precautions .................................................................................................................................................... 1
2 Outside View Drawings.................................................................................................................................. 2
2.1 Outside View Drawings.......................................................................................................................... 2
3 Moving........................................................................................................................................................... 3
3.1 Dimensions ............................................................................................................................................ 3
3.2 Moving Instruction................................................................................................................................. 3
3.3 Compornents ......................................................................................................................................... 3
4 Installation ..................................................................................................................................................... 4
4.1 Installation Suggestions ......................................................................................................................... 4
4.2 Mounting ............................................................................................................................................... 5
5 Wirings........................................................................................................................................................... 6
5.1 Cable Holes ............................................................................................................................................ 6
5.2 Main Power and Ground Wirings .......................................................................................................... 6
5.3 Signal Wirings ........................................................................................................................................ 7
5.4 Boiler Network Wirings.......................................................................................................................... 8
5.5 Modbus TCP Wirings............................................................................................................................ 10
6 IPC Installation and Wirings......................................................................................................................... 12
6.1 IPC Installation ..................................................................................................................................... 12
6.2 IPC Wirings........................................................................................................................................... 14
7 Specifications............................................................................................................................................... 18

Comm-Link/ER Installation Manual
1
1 Precautions
The following precautions must be observed whenever a Comm-Link/ER is installed.
1. D-class grounding wiring has to be used. Please an install standard cable for the ground from the ground
terminal in the cabinet. The size of the ground cable must be bigger than that of the power cables (2.0 mm2
or more).
2. An overcorrect circuit breaker must not be installed at the ground wiring.
3. The main power supply must be provided with isolated ground leakage circuit breakers with an over-current
protection function at a location within 3 meters of the main-line junction in the low voltage wiring.
4. Ensure that the ground leakage circuit breaker of the main power supply has a current sensitivity rating of
30mA.
5. The acceptable current of the ground leakage circuit breakers with over-current protection function must be
smaller than that of the main power supply line.
6. Each phase of the main power supply (R and S) must be provided with an isolated ground leakage circuit
breaker.
7. The insulation resistance of the main power supply lines should be no less than 0.1 Mega Ohms.
8. The main power supply cables should be larger than 2.0 mm2and protected by conduits.
9. Please use round terminals and Y terminals with an insulated protection and select those according to the
size of the terminal stands and screws. The terminals should not be bent.
10. The signal cables must be protected by isolated conduits.
11. The signal cables must be separated from the power cables.
12. The Ethernet cables must be separated from the power cables.
13. The main power supply must be provided with isolated ground leakage circuit breakers with an over-current
protection function.
Circuit breaker Current Capacity: 15A
Circuit breaker Current Sensitivity: 30 mA
14. The total length of the twisted-paired cables of the M-NET network must be less than 900 m. When the total
length exceeds 900m you need to install additional option devices. Please consult your closest Miura office
for further information.
15. The CAT5e STP cable (100m or shorter) should be used for Ethernet between devices (device to HUB or HUB
to HUB).

Comm-Link/ER Installation Manual
2
2 Outside View Drawings
2.1 Outside View Drawings
Figure 2-1 Outside View Drawings
Size (mm)

Comm-Link/ER Installation Manual
3
3 Moving
3.1 Dimensions
See the section 7: Specifications for the dimensions and weights. The transportation sizes are a little larger
than the actual sizes since it is packed in a cardboard box.
3.2 Moving Instruction
Please use a hand lift or carriage to protect the device from damage when you move it.
Caution
Make sure of the device weight and you have enough people to move it to avoid an
injury accident.
Please see the weight on the specification table of section 7.
Please put on the proper safety items.
3.3 Components
Please make sure that all following components are included when before installation.
Table 3-1 Component List
Item #
Component Name
QTY
Note
(1)
Comm-Link/ER Cabinet
1
(2)
IPC Package
(with the Software CD, Audio Adaptor, and USB
cable)
1
(HASP is pre-installed.)
NOTE
IPC: Industrial PC. The device or function may be changed without notification.

Comm-Link/ER Installation Manual
4
4 Installation
4.1 Installation Suggestions
NOTE
Please make sure that the Comm-Link/ER will be installed at a right place which meets the following
requirement. It might cause a problem when it is not installed properly.
The device must be installed indoors. Please install the device at a place where doesn’t have a raining,
snowing, or freezing risk.
Please install the device at a place with the proper condition (temperature and humidity).
Installing the device in any of the following conditions which can result in damage or malfunction
must be avoided.
1. Locations exposed to direct sunlight or close to something hot.
2. Locations where the ambient temperature is high or fluctuates too much.
3. Dusty or humid locations.
4. Locations where the device may be exposed to a risk of vibration or impact.
5. Locations where chemical vapors are present or the device may come into contact with water or
chemical.
6. Locations close to high voltage power-supply lines or equipment producing strong magnetic fields.
7. Locations where the power supply voltage is not stable.
Please keep a necessary space with which the cover can be opened for maintenance or
troubleshooting.

Comm-Link/ER Installation Manual
5
4.2 Mounting
Please tightly install (4)-anchor bolts (pre-installed or hole-in-anchor bolts) in the wall on which you install the
Comm-Link/ER cabinet. Please see the figure 4-1 for the locations and sizes of the anchor bolts.
4-1 Comm-Link/ER Installation Example
Caution
Please make sure that the wall is strong enough to hold the device when installation
to avoid a serious injury.
Please see the weight on the specification table of section 7.
If the bolt length from the wall is longer than 20 mm please use a special tool to
tighten the nuts such as a deep socket.
1150mm
m
Plain Washers 5/16”
Spring Washers 5/16”
Nuts 5/16”
Pre-installed or Hole-in-anchor bolts 5/16”
(5/16” bolt, Length 15-20mm)
650mm
Installation Holes (φ9mm)

Comm-Link/ER Installation Manual
6
5 Wirings
5.1 Cable Holes
You should make cable holes at the bottom side of the Comm-Link/ER cabinet to install the power cables,
ground cables, signal cables, and communication cables. Please use wiring protections such as cord bushings.
5.2 Main Power and Ground Wirings
Please establish the power cable connection to the Comm-Link/ER cabinet.
You can refer to the attached “External Wiring Diagram”for the terminal locations of the
Comm-Link/ER cabinet.
You should use AC120V (60Hz) 1φ for the power cables.
You should put a ground label for the main grounded point.
Figure 5-1 Main Power and Ground Wiring
Figure 5-2 Ground Label
Ground
(D-Class)
Main Power
Single Phase(R, S)
(From Distribution Panel)
AC120V 1φ
R S
Ground

Comm-Link/ER Installation Manual
7
NOTE
D-class grounding installation is required. Please use standard wires (2.0 mm2or more) which are larger
than the main power cables from the ground terminals of the Comm-Link/ER cabinet when those are
installed. You should use a round terminal for the ground cables for which you can swage the core wires
and the cover separately (double swage type).
NOTE
Please use cord bushings which are certified by UL, CSA, or an European certificate organization such as
TUV, VDE, or SEMKO) for the wiring inlet holes of the Comm-Link/ER cabinet to install the wires tight
enough.
The cables should not be moved by 2 mm or more with 100 N tension power after installation.
5.3 Signal Wirings
Please establish the signal cable connection to the Comm-Link/ER cabinet.
You can refer to the attached “External Wiring Diagram”for the terminal locations of the
Comm-Link/ER cabinet.
“Digital/Pulse Input Signals”should be Sync-input type signals. Please use a dry contact signal or
NPN open collector signal for the terminals. Please refer to the attached signal list and section 7.
Specifications for the detail.
“Analog Input Signals”should be 4-20 mA tyle signals. Please use shielded wires (0.75mm2or
more). Please refer to the attached signal list and section 7. Specifications for the detail.
NOTE
The pulse length must be 30 msec or longer when a “Digital /Pulse Input”is used for a pulse signal.

Comm-Link/ER Installation Manual
8
5.4 Boiler Network Wirings
As shown in the “Figure 5-3: Boiler Network Communication Cables”and “Figure 5-4: Twisted-Paired Cables
to the Terminal Block”, please connect the boiler network communication cables (twisted-paired cables) from
another M-NET device to the communication adaptor terminal block.
Figure 5-3 Boiler Network Communication Cables
N2 N1 N0 N2 N1 N0 F
G
Communication Adaptor
Terminal block
End
Resistor
Twisted-Paired Cables
FCPEV 0.9mm 2P
(with copper braided shield)
Communication Board
of another M-NET device
N2 N1 N0 N2 N1 N0
FG
Twisted-Paired Cables
FCPEV 0.9mm 2P
(with copper braided shield)
Communication
Adaptor
Twisted-Paired Cables
FCPEV 0.9mm 2P
(with copper braided shield)

Comm-Link/ER Installation Manual
9
NOTE
The boiler network communication is to be set up as a daisy chain connection with the same terminal
numbers. The cables from the N1 terminal should be connected to another N1 terminal, N2 to N2, and N0
to N0, for instance. The shield wires of twisted-paired cables for either of the end network devices should
be connected to the FC terminal. When the Comm-Link/ER is not one of the end network devices please
remove the end resistor and connect the communication cables as well as others.
NOTE
Ensure that the boiler network communication cables are not bundled together with any power cables
which may cause a communication problem.
* Twisted-Paired Cable Connection Tips
In order to install twisted-paired cables to a terminal block, first please strip the cable insulation cover by 10
mm from the end. While you push the small square hole right next to the round shaped cable connection
hole with a small flat-head screwdriver, you should install the twisted-paired cables into the round shaped
cable connection hole. The twisted-paired cables will be engaged by removing the screw driver.
Figure 5-4: Twisted-Paired Cables to the Terminal Block
Small Flat-head Screwdriver
Twisted-Paired Cables
Strip the insulation by 10 mm
Communication
Adaptor
Terminal Block

Comm-Link/ER Installation Manual
10
5.5 Modbus TCP Wirings
The communication cable to the Modbus TCP network needs to be installed to send the Miura boiler system
data to the customer’s system. Please install the Ethernet cable of Modbus TCP to the PROFINET (LAN)
connector port of the Micro controller with the “Figure 5-5 Ethernet Cable Connection”.
Figure 5-5 Ethernet Cable Connection
Cable Specification: Please make sure that a following proper cable is being used.
Cable
Specification
CAT5e or higher, STP straight cable (*1)
(Enhanced category 5 or higher, shielded straight cable)
Connector
RJ-45 Connector (available for shielded grounding)
(*1) “STP”--- Shielded Twisted Paired
“UTP”--- Unshielded Twisted Paired
NOTE
When you install Ethernet cables, the cable length between two devices always has to be within 100 m.
Please don’t bundle up power cables and Ethernet cables of the Modbus TCP network for the
installation.
Ethernet Cable should be installed to the PROFINET (LAN)
connector port of the Micro controller.

Comm-Link/ER Installation Manual
11
NOTE
Ethernet cables which are generally used for offices or personal uses don’t have the shielding capability.
You should also use connectors which have a shield grounding capability for the Ethernet cables. The shield
will affect the device performance against noise around the device.
Figure 5-6 Ethernet Cable Types
NOTE
You should use an Enhanced category 5 or higher, shielded straight cable (Cat5e STP) and the cable length
between two devices always has to be within 100 m.
Consult your closest Miura office when you have a question.
Non-Shield Type
(Plastic Surface)
Shield Grounding Type
(Metal Surface)

Comm-Link/ER Installation Manual
12
6 IPC Installation and Wirings
6.1 IPC Installation
a) Bracket Installation
You can find two brackets in the shipped box for the IPC installation. Please install the brackets to the IPC
cabinet using (6) - M3 x 6mm screw volts which will also be found in the box. The maximum screw depth in
the box is 5mm.
Figure 6-1 IPC Bracket
Figure 6-2 Installed IPC Bracket
NOTE
The included M3 screw bolts are Hexalobular type. Although they can be installed with a standard flat
head screw driver, a Hexalobular (T10 type) screw driver will be recommended for your easier
operation.
(6)-M3 Screw Bolts

Comm-Link/ER Installation Manual
13
b) IPC Installation
You can find (4)-M4 screw bolts on the Comm-Link/ER cabinet inside. Please install the IPC by using those.
Figure 6-3 IPC Installation
(4)-M4 Screw Bolts

Comm-Link/ER Installation Manual
14
6.2 IPC Wirings
a) COM1- Serial Cable Connection
Please connect the serial cable with a D-sub 9 pin type connector (with COM1 sticker) to the COM1 serial
connector port of the IPC (see Figure 6-4).
b) COM4- Serial Cable Connection
Please connect the serial cable with a D-sub 9 pin type connector (with COM4 sticker) to the COM4 serial
connector port of the IPC (see Figure 6-4).
c) IPC- Power Cable Connection
Please connect the IEC C-13 socket of the power cable to the IEC C-13 power plug port of the IPC (see
Figure 6-4).
Figure 6-4 Power and Serial Cable Installation
D-Sub 9pin connector
(COM1)
D-Sub 9pin connector
(COM4)
Power Cable Connector

Comm-Link/ER Installation Manual
15
d) Keyboard and Mouse Connection
Please connect the keyboard cable to the USB connector (see Figure 6-5). Then please connect the mouse
connector to the keyboard (or the IPC directly).
Figure 6-5 Keyboard and Mouse Connection
USB Keyboard Cable
(On-site)
You can use the side cable
hole for the USB cables.
USB Mouse Cable
(On-site)

Comm-Link/ER Installation Manual
16
e) Display Power Cable and Display Cable Connection
Please connect the DVI-D cable shipped with the display to the connector port of the display as well as
that of the IPC.
Figure 6-6 Display Cable Connection
NOTE
The length of the DVI-D and USB cables should be 5m or shorter. Please place the display, key board, and
mouse within the range.
You can use the side cable
hole for the DVI-D cable.
DVI-D Cable
Table of contents
Other Miura Boiler Supplies manuals

Miura
Miura CONNECT User manual

Miura
Miura STEAM EO-010A User manual

Miura
Miura EJ-210 User manual

Miura
Miura MP1-200 User manual

Miura
Miura CMU-324HE User manual

Miura
Miura WP2-200A User manual

Miura
Miura CMU-324HE User manual

Miura
Miura WP2-200A User manual

Miura
Miura BP-201 Troubleshooting guide

Miura
Miura BP-201 User manual
Popular Boiler Supplies manuals by other brands

JJM Boiler Works
JJM Boiler Works JM-2 Installation operation & maintenance

Immergas
Immergas 3.014083 quick start guide

Fröling
Fröling RS4 Installation and operating instructions

U.S. Boiler Company
U.S. Boiler Company SteamMax STMX100 quick start guide

SmartDHOME
SmartDHOME MyOT user manual

oventrop
oventrop Regumat S-130 Installation and operating instructions