Cooling recovery
Setting range: on/off
St temp sup air cooled by exh air
Setting range: -20.0 – 41.0 °C
Min diff outd and exhaust air
Setting range: 3.0 – 10.0 °C
When you do not have a heating demand and it is
warmer outside than inside, ventilation recovery is
stopped to prevent the building from being heated fur-
ther.
Caution
Only ventilation recovery is stopped, not the
ventilation.
Temp stop of heat recovery: Here, you set the outside
temperature at which ventilation recovery is to stop.
Min diff ind and outd air: Here, you set the temperature
difference between the indoor air and the outdoor air
that is required in order for ventilation recovery to start.
Recovery stop during heating: Stopping ventilation re-
covery during the time heating is permitted is possible.
Cooling recovery: When you do not have a heating de-
mand, ventilation recovery is stopped to prevent the
building from being heated further. When it is warm in-
doors and even warmer outdoors, ERS S40 can be used
to prevent the building from being heated further with
the "Cooling recovery" function. "Cooling recovery"
means that the cool temperature in the building can also
be retained when ventilation recovery is running. When
"Cooling recovery" is activated, the exhaust air is used
to cool the supply air, which causes the temperature in
the building to drop slightly.
"Cooling recovery" is started when the exhaust air tem-
perature is a certain number of degrees below the out-
door temperature and it is warm outside.
St temp sup air cooled by exh air: Here, you set the
outdoor temperature at which cooling recovery will start.
Caution
"St temp sup air cooled by exh air" cannot be
lower than "Stop heating" in menu 7.1.10.2 –
"Auto mode setting".
Min diff outd and exhaust air: Here, you set the temper-
ature difference between outdoor air and exhaust air
that is required in order for cooling recovery to start.
Menu 1.2.1 - Fan speed
Alternatives: normal and speed 1 – speed 4
The ventilation in the accommodation can be temporarily
increased or reduced here.
When you have selected a new speed a clock starts a
count down. When the time has counted down the
ventilation speed returns to the normal setting.
If necessary, the different return times can be changed
in menu 1.2.5.
The fan speed is shown in brackets (in percent) after
each speed alternative.
Menu 1.2.2 -Night cooling
Night cooling
Setting range: on/off
Start temp exhaust air
Setting range: 20 – 30 °C
Min diff ind and outd air
Setting range: 3 – 10 °C
Night cooling during heating
Setting range: on/off
Activate night cooling here. When the temperature in
the building is high and the outdoor temperature is low,
a cooling effect can be obtained by forcing the ventila-
tion. When night cooling is activated, the fan operates
at speed 4. In this mode, ventilation recovery is stopped.
Start temp exhaust air: Here, you set the exhaust air
temperature at which night cooling will start.
Min diff ind and outd air: If the temperature difference
is greater than the set value for "Min diff ind and outd
air", and the exhaust air temperature is higher than the
set value for "Start temp exhaust air", the ventilation
operates at speed 4 until one of these conditions is no
longer valid.
Night cooling during heating: It is possible to have night
cooling during the time heating is permitted.
Menu 1.2.5 - Fan return time
speed 1 – speed 4
Setting range: 1 – 24 h
Here, you select the return time for the temporary speed
change (speed 1 – speed 4) of the ventilation in menu
1.2.1.
Return time is the time taken before the ventilation
speed returns to normal speed.
Menu 1.2.6 - Filter cleaning interval
Months between filter cleaning
Setting range: 1 – 24 months
Clean the filter in ERS S40 regularly; how often depends
on the amount of dust in the ventilation air.
Set the interval for the reminder to clean the filter in this
menu.